CWE MAMUN
HQ CWE MAMUN PATHANKOT 145001
REPAIR/MAINTENANCE TO HT PANELS UNDER GE SAMBA
2020_MES_377076_1
CWE/M-48/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SAMBA
Class D Category b ii
5 documents required · 5 mandatory
₹500
GE SAMBA
₹40,000
Yes
12 Nov 2020
12 Sept 2020
13 Oct 2020
12 Sept 2020
12 Oct 2020
30 Sept 2020
Amount
Excavation in trenches n. exc. 1.5 mtr wide and n. exc. 1.5 mtr in depth for foundation of pole and laying of UG cable and getting out in any type of soil complete all as specified and directed.
All as per srl item No.1 above but depth exceeding 1.5 Mtr and not exceeding 3 mtr complete all as specified and directed.
Removing excavated material (soil) to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as spd and directed.
Returning filling in, including spreading, watering and well ramming in layers not exceeding 25 cm thick in any type soil complete all as spd and directed. (Note : Punned thickness shall be measured & paid for)
M & L for Sand cushioning for under ground cable upto 8 cm before laying the cable and 15 cm after laying and stretching the cable complete all as spd and directed. Note : Punned thickness shall be measured & paid )
Material and labour for sub class 'B' bricks well burnt of size laid dry flat for protection of cable complete all as spd and directed.
Material and labour for Plain cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation of poles including necessary form work for rough finished surface complete all as specified and as directed.
Material and labour for Plain cement concrete 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in coping to poles including necessary form works for rough finished surface complete all as specified and as directed.
Supply, laying & testing cable XLPE insulated, screened PVC bedded galvanised steel strip armoured HT electric power cable (heavy duty) 11000 volts grade with aluminum conductor 6.35 KV (UE)/11 KV (E) grade, cross sectional area 120 Sqmm 3 core as per IS-7098 suitable for earth system laid in trenches of complete all as specified and as direcetd.
Supply, laying & testing cable XLPE insulated, screened PVC bedded galvanised steel strip armoured HT electric power cable (heavy duty) 11000 volts grade with aluminum conductor 6.35 KV (UE)/11 KV (E) grade, cross sectional area 95 Sqmm 3 core as per IS-7098 suitable for earth system laid in trenches complete all as specified and as direcetd.
M & L in repairs Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination Heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE HT armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed, Make - BIRLA 3 M/RAYCHEN/CAB SEAL/ M.Seal
M & L in repairs Cable end jointing kit for 11 KV (earthed) grade cable for out door type termination heat shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE HT armoured aluminium conductor cable of size 95 sq mm complete , all as specified and directed, Make - BIRLA /3 M/RAYCHEN/CAB SEAL/M.seal
M & L in repairs Cable end jointing kit for 11 KV (earthed) grade cable for indoor type termination heat shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE HT armoured aluminium conductor cable of size 120 to 185 sq mm complete , all as specified and directed, Make - BIRLA/ 3 M/RAYCHEN/CAB SEAL/M.seal
M & L in repairs Cable end jointing kit for 11 KV (earthed) grade cable for out door type termination heat shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE HT armoured aluminium conductor cable of size 120 to 185 sq mm complete , all as specified and directed, Make - BIRLA/ 3 M/RAYCHEN/CAB SEAL/M.seal
M & L in repairs Cable end jointing kit for 11 KV (earthed) grade cable for indoor type termination heat shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sq mm to 300 sqmm complete , all as specified and directed, Make - BIRLA /3 M/RAYCHEN/CAB SEAL/M.seal
M & L in repairs Cable end jointing kit for 11 KV (earthed) grade cable for out door type termination heat shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sq mm to 300 sqmm complete , all as specified and directed, Make - BIRLA 3 M/RAYCHEN/CAB SEAL/M.seal
M & L in repairs Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified, Make - BIRLA/ 3 M/RAYCHEN/CAB SEAL/M.seal
M & L in repairs Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified, Make - BIRLA/3 M/RAYCHEN/CAB SEAL/M.seal
Taking down old unservicable lightning arresters and Supply and fixing for lightning arresters expulsion type complete with all fittings transmisson class,discharge capacity 65 kilo amps suitable for 11000 volts conforming to IS complete all as specified and directed. Make - Pactil/OBLUM/CROMPTON GREAVES/ BHEL.
Taking out the unserviceable gand operated device after disconnecting the electric HT supply and Supply and fixing air break switch gang operated (GOD) triple pole with drop out fuses mechanically operated, mounted on insulators (15 insulators) & steel frame with operating mechanism & operating rod of GI pipe 25mm medium grade with necessary clamps to be operated from ground level 11 KV grade working pressures and current upto 200 amps etc complete, all as specified and directed. Make: Jaipuria/Rastriya/BHEL.
Taking out the unserviceable gand operated device after disconnecting the electric HT supply and Supply and fixing air break switch gang operated (GOD) triple pole with drop out fuses mechanically operated, mounted on insulators (15 insulators) & steel frame with operating mechanism & operating rod of GI pipe 25mm medium grade with necessary clamps to be operated from ground level 11 KV grade working pressures and current upto 400 amps etc complete, all as specified and directed. Make:PACTIL/OBLUM/ABB/BHEL.
M & L in replcement of structural steel work conforming to grade Fe-410S as in cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections, including , nuts, bolts, washers, welding , bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one coat of zink chrome primer and two coats of aluminium paint for 11KV insulation complete all as specified and directed.
Taking down existing unserviceable / old ACSR conductor from over head lines complete all as spd and directed.
Supply and fixing aluminum conductor steel reinforced (ACSR) for HT/LT lines on PCC/steel tubular poles, streching without kinks and bends including aluminum binding wires of size Ferret to Dog as per load complete all as spd and directed Make- Aliend/ICC/NICCO
S & F stay assembly complete comprising of 16mm dia, 40cm long stay bow rod 16mm dia x 1.8 Mtr long galvanised stay rod threaded and with nuts including 300mm x 300mm x 6mm thick plate GI, stay wire, stay clamps and necessary clamps for any type of pole etc as shown on plate No. 1 on page 495 of SSR Part-I, 2009 complete including taking down U/S stay assembly all as specified and directed ( Note : Loop type insulator, excavation and concrete work shall be measured and paid separately).
S & F in replacement loop type insulator with complete fitting porcelain, vitreous white or brown large size with over all dismensions 90x140mm , clearance of hole 25.5mm all as specified and directed
S & F in replacement galvanised steel stranded stay wire size 7/3.15mm for stay assembly complete all as specified and directed.
Restretching of ACSR conductor of any size of over head lines LT/HT on poles including binding with insulators, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed. Note: (1) ACSR conductor Required for winding etc is deemed included in quoted rates. (2) The distance between two poles shall be considered as one Span for measurement proper.
M&L for repair and servicing of HT 11 KV RCC four pole structure by replacing galvanized PG clamps, GI bolts and nuts, pieces of ACSR conductor with insulation of any size as jumpers including lubricating the moving parts of AB switch and cleaning of all disc /pin insulators and applying silicon compound for prevention of arcing due to dust/ salt deposits over the surfaces including applying one coat of zinc oxide primer on rusted portions after preparation of surfaces & a coat of aluminum paint to the entire steel structure complete all as directed. Note:-Rate quoted shall be inclusive of paiting of steel structure, two coats of white wash on exposed concrete surfaces, ACSR conductor for jumpering, GI hard ware like nuts, bolts etc complete and no claim whatsoever shall be entertained on this account.
M&L for repair and servicing of HT 11 KV RCC two pole structure by replacing galvanized PG clamps, GI bolts and nuts, pieces of ACSR conductor with insulation of any size as jumpers including lubricating the moving parts of AB switch and cleaning of all disc /pin insulators and applying silicon compound for prevention of arcing due to dust/ salt deposits over the surfaces including applying one coat of zinc oxide primer on rusted portions after preparation of surfaces & a coat of aluminum paint to the entire steel structure complete all as directed. Note:-Rate quoted shall be inclusive of paiting of steel structure, two coats of white wash on exposed concrete surfaces, ACSR conductor for jumpering, GI hard ware like nuts, bolts etc complete and no claim whatsoever shall be entertained on this account.
Cutting, trimming of hanging/ extended braches of trees upto a distance 3 meter from the overhead HT/LT line and making the line clear upto the entire length of the feeder including removal and disposal of the cut tree branches 50 meters away from the site complete all as specified and directed. Note : The Rates shall inclusive of T&P, hydraulic ladder, equipment such as motorised diesel operated hacksaw etc complete all as specified and as directed. Note : 1. One span comprises of 3 to 5 conductors of any distance between one pole to adjacent pole including trimming of all tree branches in vicinty & around poles /conductor & will be measured as one span. 2. Necessary prior permission shall be obtained from concerned Engineer-incharge before carrying out the work. 3. All safety measures & insurance to the staff undertaking the Job shall be the Contractor's responsibility.
Supply & fixing Prestreesed concrete pole 11 Mtr long 152x152 mm at top and 152x260 mm at bottom class-9 errecting in truely vertical position complete all as specified. Note :(Excavation and PCC shall be measured and paid for separately under relevent item of this BOQ).
Supply and filling of silica gel in to the existing breather assembly of transformer complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron strip 32X6mm by means of nuts bolts,washers,check nuts of GI steel all as shown in electric plate no 3 of SSR -2009 Part II, all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe medium grade 40mm and GI watering pipe 20mm light grade with funnel and wire mesh ,40mm thick pre-cast RCC N-15 (nominal mix) cover reinforced with XPM weight not less than 4 kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover ,PCC M-15 (nominal Mix) pit,excavation and earth work in any type of soil and connected all as specified and as directed. Notes: 1. Earth lead & protection pipes length upto & including 7.50 metre is deemed included in unit rate quoted by the contractor. 2. Earth filling shall be done by vegitable soil. 3. Soil shall be free from stone, boulders, aggregate, gravels .
Supply and fixing aluminium strip 25 x 3.15 mm with saddles and fixing screws etc for roof and ground conductors and down conductors above ground complete all as specified and directed.
M & L earthing complete with galvanised steel earth plate electrode , 600x600x6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level)with top edge of the plate not less than 1.5mtr below ground level connected to galvanised iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point , GI tubing 15mm bore medium grade protection pipe , GI watering pipe 20mm bore light grade with funnel and wire mesh , charcoal , and salt precast PCC 1:2:4 (Nominal mix ) cover with suitable steel handle , and angle iron 40x40x3mm frame for pit cover , PCC 1:2:4 pit including earth work in any type of soil , removal of surplus soil to a distance n.exc 50mtr and connecting , testing on completion all as shown on electric plate No 03 of SSR -2009 Part II complete all as directed. Notes: 1. Earth lead & protection pipes length upto & including 7.50 metre is deemed included in unit rate quoted by the contractor. 2. Earth filling shall be done by vegitable soil. 3. Soil shall be free from stone, boulders, aggregate, gravels .
M & L for GI pipe in replacement ( Light grade ) for protection of HT cable fixed to walls/ poles/road crossing including suitable size clamps complete of size 80mm bore, all as specified and directed.
Taking down the old/unserviceable Ammeter from the HT panel and Supply and fixing new digital ammeter programmable suitable for 11 KV VCB range having 1A /5A ratio suitable flush pattern square type 96mm x 96mm with adopter including wiring, make: Secure /Rishosn/AE complete all as specified and directed.
Taking down the old/unserviceable and Supply and fixing new digital voltmeter programmable 96mm x 96mm suitable for 11KV HT VCB panel axiliery voltage 0-500 volt, as per installed panel make and model or equivalent complete all as specified and directed.
M & L for construction of platform of size 3000 x 2500 x 1200 mm for transformer with PCC (1:4:8) in foundation and PCC 1:2:4 type B1, 100 mm thickness at top portion of platform , brick work with cement mortar (1:4) and complete plaster work of 15 mm thick to exposed surface in CM (1:4) including necessary MS work ( i.e. MS jali/fencing/MS angle ) on the top of platform around transformer up to height 90 cm and one coat of white wash on plastered surface complete all as specified and shown on drawing No CEPZ/C-TD/002/13 Sheet 2/5.
M&L for Rendering 15mm thick in two layers (base layer 10mm in CM 1:6 & finishing layer 5mm thick in CM 1:4) using liquid water proofing compound (in 2nd layer only) on brick work or concrete surfaces of wall surfaces finished even and smooth using extra complete all as specified & directed. (Note : WPC shall be measured and paid separately)
Supply only Polymer liquid water proofing compound of make ilite/Bauchemic/Fosrock complete all as specified and directed.
S&F chain link fencing mild steel galvanised with 100 mm size of mesh, 10 gauge including line wire secured and fitted to angle/RCC poles complete all as specified and directed. Note:- PCC/angle shall be measured and paid separately.
M&L for spreading of graded course aggregate 20mm nominal size to be spread over sand complete all as directed.
Repair /servicing /Calliberation to HT panel of make : Crompton having vacuum circuit breaker 11 KV rating of capacity 250 MVA and current rating up to 630 Amp by replacing defective/wornout part, adjustment of gaps for smooth operation all as detailed below:-
Cleaning of VCB with air blower and removing dust particals
Cleaning of insulating places of VCB by using CTC/CRC/Thinner as required and recommended
Checking the arcing contact gap of vaccum intrupter if gap exceeds the permissible limis, readjust as recommended
Cleaning the main contacts to remove carbon or any other unwanted particals if visible.
Dismentling and cleaning the insulated surfaces and arc barrier with CTC and CRC.
Checking/repair replacement of all electrical wiring for electrical/manual operation of panel including measuring IR values.
Checking of all nuts/bolts, springs, levers, latches, connnectors etc and adjustments as required and recommended.
Recording IR values of CTs and PTs.
Cleaning of bus bar spout.
Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations. Note :- (i) Service will be carried out through Service Engineer of Manufacturer only. The service engineer so hired should be the manufacturer employee only. No employee of authorised dealer shall be hired for servicing of VCB. (ii) The cost of minor spare parts i.e nut and bolts, springs, grommets, dust cover, ring of isolator contacts, clips, pin for release prop, 'Y' Phase shround, over ride stop pin etc essentially required to make the panel serviceable shall deemed to be included in the unit rate by contractor.
Repair /servicing /Calliberation to HT panel of make : ABB having vacuum circuit breaker 11 KV rating of capacity 250 MVA and current rating up to 630 Amp by replacing defective/wornout part, adjustment of gaps for smooth operation all as detailed below:-
Cleaning of VCB with air blower and removing dust particals
Cleaning of insulating places of VCB by using CTC/CRC/Thinner as required and recommended
Checking the arcing contact gap of vaccum intrupter if gap exceeds the permissible limis, readjust as recommended
Cleaning the main contacts to remove carbon or any other unwanted particals if visible.
Dismentling and cleaning the insulated surfaces and arc barrier with CTC and CRC.
Checking/repair replacement of all electrical wiring for electrical/manual operation of panel including measuring IR values.
Checking of all nuts/bolts, springs, levers, latches, connnectors etc and adjustments as required and recommended.
Recording IR values of CTs and PTs.
Cleaning of bus bar spout.
Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations. Note :- (i) Service will be carried out through Service Engineer of Manufacturer only. The service engineer so hired should be the manufacturer employee only. No employee of authorised dealer shall be hired for servicing of VCB. (ii) The cost of minor spare parts i.e nut and bolts, springs, grommets, dust cover, ring of isolator contacts, clips, pin for release prop, 'Y' Phase shround, over ride stop pin etc essentially required to make the panel serviceable shall deemed to be included in the unit rate quoted by contractor.
Repair /servicing /Calliberation to HT panel of make : Kirloskar having vacuum circuit breaker 11 KV rating of capacity 250 MVA and current rating up to 630 Amp by replacing defective/wornout part, adjustment of gaps for smooth operation all as detailed below:-
Cleaning of VCB with air blower and removing dust particals
Cleaning of insulating places of VCB by using CTC/CRC/Thinner as required and recommended.
Checking the arcing contact gap of vaccum intrupter if gap exceeds the permissible limis, readjust as recommended
Cleaning the main contacts to remove carbon or any other unwanted particals if visible.
Dismentling and cleaning the insulated surfaces and arc barrier with CTC and CRC.
Checking/repair replacement of all electrical wiring for electrical/manual operation of panel including measuring IR values.
Checking of all nuts/bolts, springs, levers, latches, connnectors etc and adjustments as required and recommended.
Recording IR values of CTs and PTs.
Cleaning of bus bar spout.
Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations. Note :- (i) Service will be carried out through Service Engineer of Manufacturer only. The service engineer so hired should be the manufacturer employee only. No employee of authorised dealer shall be hired for servicing of VCB. (ii) The cost of minor spare parts i.e nut and bolts, springs, grommets, dust cover, ring of isolator contacts, clips, pin for release prop, 'Y' Phase shround, over ride stop pin etc essentially required to make the panel serviceable shall deemed to be included in the unit rate quoted by contractor.
S&F in replacement of plug & socket assembly suitable for VCB 11 KV complete all as specified.
S&F in replacement of manual spring charging handle suitable for VCB/OCB 11 KV complete all as specified.
S&F in replacement of TNC switch suitable for VCB/OCB 11 KV Panel complete all as specified.
S&F in replacement of electric hooter suitable for VCB 11 KV Panel complete all as specified.
Dismantling insulators any type and size complete all as specified and directed.
M&L pin type insulator vitreous, white, brown, or green insulator includig one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed.
S&F disc type insulator, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000 Volts complete all as specified and directed.
M&L anti climbing device, spikes type fabricated out of MS bars (round/square/flat) including nuts,bolts, washers and welding in two halves made to shape to suit the cross section of the pole including dismantling old one complete all as specified and directed.
S&F danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts, nuts of approved size for HT 25x20 cm size including dismantling old onecomplete all as specified and directed.
Taking down unservicable triping coil from HT panel and supply and fixing new triping coil 30 volt DC suitable for 11KV HT panel of make : Kirloskar ,cat part no as per OEM of existing panel complete all as directed and specified by Engr-in-chagre.
Taking down unservicable triping coil from HT panel and supply and fixing new Master Trip Relay 30 V DC suitable for 11 KV HT panel for protection system complete all as directed and specified by Engr-in-chagre. Make: ABB, model no: RXMVB2 or technocommerically equivalant model in Schneider / Kirloskar /Alstom.
Taking down unservicable triping circuit supervision relay and S&F new trip circuit supervision relay of 30 V DC suitable for 11 KV HT panel for protection system complete all as directed and specified by Engr-in-chagre. Make: ABB model no : RXI series or technocommerically equivalant model of Siemens/ Schneider.
Taking down unservicable triping circuit supervision relay and S&F new trip circuit supervision relay of 110-125 V DC suitable for 11 KV HT panel for protection system of make: ABB model no : RXI series or technocommerically equivalant of Siemens/ Schneider complete all as directed and specified by Engr-in-chagre.
Taking down unservicable anmunciator window type relay and S&F new anmunicator window relay 15 window suitable of 110-125 V DC suitable for 11 KV HT panel for protection system of make:Alan ,MP series or technocommerically equivalant of Proton/Minilec complete all as directed and specified by Engr-in-chagre.
Taking down unservicable over current and earth fault relay and S&F new over current and earth fault relay suitable of 30 V DC suitable for 11 KV HT panel for protection system of make:Easergy of Schneider of P3 series or technocommerically equivalant of ABB /Siemens complete all as directed and specified by Engr-in-chagre.
Supply and fixing LED panel Indication Lamps 45V DC of Red colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 45V DC of Green colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 45V DC of Blue colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 45V DC of Yellow colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 45V DC of white colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 110V DC of Red colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 110V DC of Green colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 110V DC of Blue colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 110V DC of Yellow colour. Make: Pyroteon or as per sample complete all as specified and directed.
Supply and fixing LED panel Indication Lamps 110V DC of White colour. Make: Pyroteon or as per sample complete all as specified and directed.
vishesh engineers
M/S GUPTA TRADING CO
Standard engineers
Jiwan Singh
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .