The Executive Engineer, PMD,PHE.Dte
Office of the Executive Engineer Purulia Mechanical Division,PHE.Dte Ranchi Road,Purulia.
Renovation of old , Earthing and Lightning Conductor Air Terminal arrangement of existing PDB, VCB, Transformer ,Metering room substation building with allied works at Lakshmanpur WTP under Raghunathpur water supply project PMD PHED.
2023_PHED_498616_5
33/ EE/PMD/PHED OF 2022-2023
Open Tender
MECHANICAL
Item Rate
30 days
Purulia
Please refer Tender documents.
5 documents required · 5 mandatory
₹6,000
Yes
17 Jan 2025
27 Mar 2023
20 Apr 2023
27 Mar 2023
18 Apr 2023
27 Mar 2023
Amount
PART A
Dismantling all types of plain cement concrete works, stacking serviceable materials at site and removing rubbish as directed within a lead of 75 m. In ground floor including roof upto 150 mm. thick (as per direction of EIC)
Ordinary Cement concrete (mix 1:3:6) with graded stone chips (40 mm nominal size) excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes. Pakur variety (for laying cable through under ground)
Earthing (a) Excavation of soil for installation of earth electrode and filling and ramping (morrum soil) Detail specification as per SOQ
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts
(d) Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented bricks work (1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos 12 mm dia holes on the GI pipe.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1)
S&F minimax / surex make dry powder chemical/CO2 type fire extinguisher of 5 kg capacity on wall with necessary MS bracket including numbing good damages to original finish (analysis) (i) For CW pump house,
S&F soft treatment chart on wall with necessary screws (i) For CW pump house, Sub-Station
S&F EI danger board (20 cm x 30 cm) on wall 415V as per IE rule (i) For CW pump house,
Supplying and fixing best quality first Aid box (Ad. Body) as per PWD specification complete with all items as required by rule of sub-station MS bracket including mending good damages to original finish. (i) For CW pump house,
Add GST @ 18%
Add CESS @ 1%
DEY ENTERPRISE
DEBJYOTI BASU
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .