Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.4 LAccepted-AOC 274 210 DAFNALA ROAD SHAHIBAUG AHMEDABAD GUJARAT 380009 | AHMADABAD | GUJARAT | 380009 | ₹20.4 L Quoted ₹22.9 L | L1 | Accepted-AOC ACCEPTED BEING LOWEST QUOTED |
| 2 | L2₹23.9 L+₹1.0 L (4.44%)Rejected-AOC | ₹23.9 L+₹1.0 L (4.44%) | L2 | Rejected-AOC NOT ACCEPTED DUE TO HIGHER RATE QUOTED |
| 3 | L3₹24.8 L+₹1.9 L (8.33%)Rejected-AOC 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | ₹24.8 L+₹1.9 L (8.33%) | L3 | Rejected-AOC NOT ACCEPTED DUE TO HIGHER RATE QUOTED |
| 4 | Rejected-Technical | - | - | Rejected-Technical WLR NO SUBMITTED TO HQ CWE FOR QE JUN 24 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
3 Sept 2024, 6:00 pmClosed
GE ARMY GANDHINAGAR
GE ARMY GANDHINAGAR PO BSF CAMPUS GANDHINAGAR 382045
REPAIR REPLACEMENT MAINTAINENEC OF UNSV LT PANELS, UG CABLE, OVERHEAD LINES, DISTRIBUTION BOARDS AND SWITCHGEAR AT MIL STN GANDHINAGAR
2024_MES_661325_1
GE(A)/GNR/TOKEN/20 of 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
MIL STN GANDHINAGAR
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
GE ARMY GANDHINAGAR
₹50,000
Yes
14 Oct 2024
21 Jun 2024
10 Sept 2024
21 Jun 2024
3 Sept 2024
6 Jul 2024
21 Jun 2024 - 3 Jul 2024
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cable etc including getting out in Soft/Loose soil complete all as specified.
Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested,poles, stays , struts have been erected and tested all as specified and directed.
Removing excavated surplus soil (Soft/hard soil) obtained from excavation to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5m above the starting point all as specified and directed.
M&L for sand cushioning to under ground cable with dry sand locally available 8cm thick before laying the cable and 15 cm above the cable, stretching and testing of cable complete all as specified & directed by Engineer-in-Charge. Note : for payment purpose punned thickness of 18 cm shall be measured against spread thickness of 23 cm as mentioned in para 10.75 of SSR Part-I
Supply & laying of Sub class 'B' old size well burnt brick laid flat in trenches as protection to LT cable complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 Core x 240 Sqmm with double compression/ single compression gland in panel side, cost of gland deemed to be included in quoted rate.
All as per item No.6 here-in-before but of 3.5 x 120 sqmm.
All as per item No.6 here-in-before but of 3.5 x 95 sqmm.
All as per item No.6 here-in-before but of 3.5 x 70 sqmm.
All as per item No.6 here-in-before but of 3.5 x 50 sqmm.
All as per item No.6 here-in-before but of 3.5 x 35 sqmm.
All as per item No.6 here-in-before but of 3.5 x 25 sqmm.
All as per item No.6 here-in-before but of 4 x 16 sqmm.
All as per item No.6 here-in-before but of 4 x 10 sqmm.
All as per item No.6 here-in-before but of 2 x 10 sqmm.
All as per item No.6 here-in-before but of 2 x 6 sqmm.
All as per item No.6 here-in-before but of 2 x 4 sqmm.
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to using galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion all as specified and directed by ENgr-in-charge
M&L for horizontal drilling, in any type of soil, using trenchless technology suitable for insertion of GI pipe and LT cables along the pipe for 50mm dia of GI pipe complete all as specified and directed.
M&L for horizontal drilling, in any type of soil, using trenchless technology suitable for insertion of GI pipe and LT cables along the pipe for 100mm dia of GI pipe complete all as specified and directed.
Supply, installation, commissioning and testing, in repair, feeder pillar board, LT (415 Volts, 50 Hz , 3-phase, 4 wire supply), CPRI approved, plinth mounted, factory made, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 50mm x 50mm x 5mm angle iron frame and 3.15 mm thick CRCA sheet powder coated with front & back hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint (First Quality) over a coat of red oxide primer, grouting panel through angle iron, 0.2 mtr in ground and 0.5 mtr over the ground including excavation & earth work in any type of soil and PCC (1:3:6) type C-2 using 40mm graded stone aggregate complete comprising of the followings:- (a) Incoming supply:- (i) 25 X 10 mm. EC grade aluminium busbars 400 amps rating of 04 strip - 01 Nos (ii) Mains incomer, 125 A, 25 kA, 4-pole MCCB with adjustable thermal-magnetic release - 01 No (iii) MFM without RS-485 port, class - 1.0- 01 Nos (iv) Indicating lamp Neon type for R-Y-B - 3 Nos (vi)Extended rotary handle & spreader terminals for above MCCB-01 Nos (vii)6 A TP MCB-01 Nos (viii) 6 A SP MCB-01 Nos (ix) CT - 125 / 5 A, class - 1.0-03 Nos (b) Outgoing supply:- (i) MCCB, thermal and magnetic setting, 3 pole, AC, 415volts,63 Amp rating, 25KA rupturing capacity - 06 Nos (ii) Extended rotary handle for above MCCB - 01 Nos (iii) Wire - 16 sq. mm. for power wiring (iv) Terminal connectors for power connections complete all as specified and directed by Engr-in-Charge MAIN BUSBAR SIZE- 25 X 10 mm. EC grade aluminium busbars MAIN BUSBAR SIZE (For neutral)-25 X 5 mm. EC grade aluminium busbars EARTHING BUS 25 X 5 mm. EC grade aluminium busbars PANEL MOUNTING-Floor mounted CABLE ENTRY-Bottom for both incoming and outgoing PANEL FABRICATION-From 3.15mm CRCA sheet steel FINISHING-Powder coating (min. 80 micron) after 7-tank process to shade RAL-7035 PANEL DIMENSIONS- App. 1700 mm. (H) X 1000 mm. (W) X 350 mm. (D)
Supply, installation, commissioning and testing, in repair, feeder pillar board, LT (415 Volts, 50 Hz , 3-phase, 4 wire supply),CPRI approved, plinth mounted, factory made, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 50mm x 50mm x 5mm angle iron frame and 3.15 mm thick CRCA sheet powder coated with front & back hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint (First Quality) over a coat of red oxide primer, grouting panel through angle iron, 0.2 mtr in ground and 0.5 mtr over the ground including excavation & earth work in any type of soil and PCC (1:3:6) type C-2 using 40mm graded stone aggregate complete comprising of the followings:- (a) Incoming supply:- (i) 25 X 10 mm. EC grade aluminium busbars 400 amps rating of 04 strip - 01 Nos (ii) Mains incomer, 200 A, 25 kA, 4-pole MCCB with adjustable thermal-magnetic release - 01 No (iii) MFM without RS-485 port, class - 1.0- 01 Nos (iv) Indicating lamp Neon type for R-Y-B - 3 Nos (vi)Extended rotary handle & spreader terminals for above MCCB-01 Nos (vii)6 A TP MCB-01 Nos (viii) 6 A SP MCB-01 Nos (ix) CT - 125 / 5 A, class - 1.0-03 Nos (b) Outgoing supply:- (i) MCCB, thermal and magnetic setting, 3 pole, AC, 415volts,100 Amp rating, 25KA rupturing capacity - 06 Nos (ii) Extended rotary handle for above MCCB - 01 Nos (iii) Wire - 16 sq. mm. for power wiring (iv) Terminal connectors for power connections complete all as specified and directed by Engr-in-Charge MAIN BUSBAR SIZE- 25 X 10 mm. EC grade aluminium busbars MAIN BUSBAR SIZE (For neutral)-25 X 5 mm. EC grade aluminium busbars EARTHING BUS 25 X 5 mm. EC grade aluminium busbars PANEL MOUNTING-Floor mounted CABLE ENTRY-Bottom for both incoming and outgoing PANEL FABRICATION-From 3.15mm CRCA sheet steel FINISHING-Powder coating (min. 80 micron) after 7-tank process to shade RAL-7035 PANEL DIMENSIONS- App. 1400 mm. (H) X 1900 mm. (W) X 350 mm. (D)
S&F GI tubing light grade galvanised with all fittings & fixed complete wall/pole for 40mm bore complete all as specified and directed.
S&F GI tubing light grade galvanised with all fittings & fixed complete wall/pole for 50 mm bore complete all as specified and directed.
S&F GI tubing light grade galvanised with all fittings & fixed complete wall/pole for100 mm bore complete all as specified and directed.
M/L for PCC (1:2:4) type B-1 using 20mm graded aggregate as in foundation/surface repair etc complete all as specified and directed.
S & F cable route indicator for LT, 6mm thick CI plate of size 100mm dia welded to MS angle iron 50mm x 50mm x 6mm embedded in PCC 1:3:6 type C-1 block size 150mm x 150mm x 160mm complete all as specified and directed.
Supply, installation, commissioning and testing, in repair, Junction Box , LT (415 Volts, 50 Hz , 3-phase, 4 wire supply),CPRI approved, plinth mounted, factory made, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 50mm x 50mm x 5mm angle iron frame and 3.15 mm thick CRCA sheet powder coated with front & back hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint (First Quality) over a coat of red oxide primer, grouting panel through angle iron, 0.2 mtr in ground and 0.5 mtr over the ground including excavation & earth work in any type of soil and PCC (1:3:6) type C-2 using 40mm graded stone aggregate complete comprising of the followings:- (a) Incoming supply:- (i) Mains incomer, 125 A, 25 kA, 4-pole MCCB with adjustable thermal-magnetic release - 01 No (ii) Indicating lamp Neon type for R-Y-B - 3 Nos (vi)Extended rotary handle & spreader terminals for above MCCB-01 Nos (vii) 6 A TP MCB-01 Nos MAIN BUSBAR SIZE- 25 X 10 mm. EC grade aluminium busbars MAIN BUSBAR SIZE (For neutral)-25 X 10 mm. EC grade aluminium busbars EARTHING BUS 25 X 5 mm. EC grade aluminium busbars PANEL MOUNTING-Floor mounted CABLE ENTRY-Bottom for both incoming and outgoing PANEL FABRICATION-From 3.15mm CRCA sheet steel FINISHING-Powder coating (min. 80 micron) after 7-tank process to shade RAL-7035 PANEL DIMENSIONS- App. 1500 mm. (H) X 700 mm. (W) X 350 mm. (D)
S&F, in repair, MCCB 3 Pole 415 volt Fixed type 125 Amps with breaking capacity 36 KA Complete all as specified and directed. Make Standard/ Legrand/ Havells/ABB
S&F, in repair, MCCB 3 Pole 415 volt adjustable type 160 Amps with breaking capacity 36 KA Complete all as specified and directed. Make Standard/ Legrand/ Havells/ABB
S&F, in repair, MCCB 4 Pole 415 volt adjustable type 160 Amps with breaking capacity 36 KA Complete all as specified and directed. Make Standard/ Legrand/ Havells/ABB
S&F, in repair, MCCB 4 Pole 415 volt adjustable type 200 Amps with breaking capacity 36 KA Complete all as specified and directed. Make Standard/ Legrand/ Havells/ABB
S&F, in repair, MCCB 4 Pole 415 volt adjustable type 250 Amps with breaking capacity 36 KA Complete all as specified and directed. Make Standard/ Legrand/ Havells/ABB
S&F, aluminum lugs for cable size 25 sqmm complete all as specified and directed.
S&F, aluminum lugs for cable size 35 sqmm complete all as specified and directed.
S&F, aluminum lugs for cable size 50 sqmm complete all as specified and directed.
S&F, aluminum lugs for cable size 70 sqmm complete all as specified and directed.
S&F, aluminum lugs for cable size 120 sqmm complete all as specified and directed.
TRIMURTHI ENTERPRISES (BID ID -3058595)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3073285)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .