Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.1 CrAccepted-AOC 193 1 CIVIL LINES BAREILLY 243001 | BAREILLY | UTTAR PRADESH | 243001 | ₹15.1 Cr | L1 | Accepted-AOC Being L1 and reasonable |
| 2 | L2₹16.2 CrRejected-Finance | ₹16.2 Cr | L2 | Rejected-Finance Being other than L1 |
| 3 | L3₹17.3 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹17.3 Cr | L3 | Rejected-Finance Being other than L1 |
| 4 | L4₹17.3 CrRejected-Finance | ₹17.3 Cr | L4 | Rejected-Finance Being other than L1 |
| 5 | L5₹17.7 CrRejected-Finance | ₹17.7 Cr | L5 | Rejected-Finance Being other than L1 |
Tender Value
₹17.4 Cr
EMD Value
₹11.9 L
Closing Date
20 Feb 2021, 6:00 pmClosed
Chief Enginner Bareilly Zone
HQ Chief Engineer Bareilly Zone Military Engineer Services Sarvatra Bhawan Station Road Bareilly Cantt Bareilly - 243001
PROVN OF SEWAGE TREATMENT PLANT PHASE-II AT BAREILLY
2020_MES_351466_1
CEBZ/T-02/BLY of 2020-21
Open Tender
Civil Works
730 days
Bareilly
As per tender docs
8 documents required · 8 mandatory
₹3,000
GE (P) Bareilly
₹11.9 L
Yes
17 Mar 2021
25 Jul 2020
25 Feb 2021
25 Jul 2020
20 Feb 2021
5 Feb 2021
Amount
SCHEDULE 'A' PART-I A (BUILDING WORK)
Total amount of SCHEDULE 'A' PART-I A (BUILDING WORK) (For details see Schedule 'A' Part-I-A in PDF folder)
SCHEDULE 'A' PART-I B (BUILDING WORK)
Construction of Sewage Treatment Plant (STP) of capacity 1.20 MLD as per flow drawing complete all as specified and shown on drawings comprising the following components: - (a) Sump well - 01 No. (b) Equilization Tank - 01 No. (c) MBBR-02 Nos. (d) Tube Settler Tank - 01 No. (e) Cascade -01 No. (f) Collection water tank - 01 No. (g) Treated Water Tank - 01 No. (h) Sludge Drying Beds - 4 Nos (12mtr x 12 mtr). (j) Platform size 27 mtr x 70.77 mtr with floors, except area covered under various structurers mentioned (a) to (h) here-in-before and (l) as below. Dwarf wall Pillers for pipes, RCC Factorycast Perforated Manhole cover & misc civil wks. (k) Ventilation Duct with exhaust fan (in Sump Well). (l) Plinth Protection (m) Column & ISMB 300 for Lifting arrangements of 2.00 Tonne Capacity CONTD....
Notes:- Following mechanical units to operate the STP shown in drawings will be measured & paid under respective item of schedule/ BOQ herein after- (a) MMF/MGF &ACF Filters (b) Gate Valve (in sump well) (c) Pump sets (in sump well) (d) High flux mixture floating type (in Equalization Tank) (e) Pump sets (in Equalization Tank) (f) Air Blower (in MBBRs) (g) Air Grid (in MBBRs) (h) MBBR media (in MBBRs) (j) Tube settler module (in Tube Settler Tank) (k) Gate Valves (in Tube Settler) (l) Entire piping work connecting all the STP units & piping work in sludge drying beds. (m) Pump sets (in Collection water tank) (n) Pump sets (in treated water storage sump) (o) Control room (Pump house , duty room with toilet at STP 4.00 m X 6.00 m)
Total amount of SCHEDULE 'A' PART-II (INTERNAL WATER SUPPLY) (For details see Schedule 'A' Part-II in PDF folder)
Total amount of SCHEDULE 'A' PART-III-A (INTERNAL ELECTRIFICATION) (For details see Schedule 'A' Part-III-A in PDF folder)
SCHEDULE 'A' PART-III-B (INTERNAL ELECTRIFICATION)
M & L for point wiring using 1.50 sqmm size, PVC insulated, unsheathed 1100 volts grade single core multi-stranded (FRLS) copper conductor cable in proper colour coding drawn into and including non metallic rigid PVC conduit medium grade (not less than 20 mm dia) with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings i.e, normal piano switch / sockets incl cover plate with frame and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.50 sqmm size stranded FRLS copper conductor cable as in earth wire and connecting all metal parts to common earth dolly for One Light point/fan point/switch socket/bell/engagement light controlled by one switch 5/6 Amp complete all as specified and directed
M&L power point wiring of copper cable FRLS grade,multi stranded 2.5 Sqmm size for 15 Amps socket outlet on independent board with 2.5 Sqmm size of copper cable FRLS grade,multi stranded earth conductor cable in proper colour coding drawn into and including non metallic rigid PVC conduit medium grade (not less than 20 mm dia) with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings i.e, normal piano switch / sockets incl cover plate with frame and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 2.50 sqmm size stranded FRLS copper conductor cable as in earth wire and connecting all metal parts to common earth dolly complete all as specified and directed.
M&L for Distribution board (DB) made out of sheet metal enclosure (CRCA sheet) dust and vermin proof SPN 8 way with 200 Amps rated copper bus bar neutral bar ,earth bar, single pole and neutral 240 volts, Double door, flush to wall connecting with cable complete all as specified and directed.
S&F Minature circuit breaker single pole with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, robust design and terminals having heat resistant moulding suitable for single phase circuit of 240 volts and 6 to 32 Amps current rating , C Series, 10 KA complete all as specifed and directed.
S&F Minature circuit breaker Single pole and Neutral with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, robust design and terminals having heat resistant moulding suitable for single phase circuit of 240 volts and 16 to 32 Amps current rating , C Series, 10 KA complete all as specifed and directed.
S&F blanking plate complete all as specifed and directed.
Supply & Fixing ceiling fan ISI Marked complete with electronic fan regulator 230 volts single phase 1200mm sweep white colour energy saving fan Including canopy set,down rod and shackle assembly including providing three core copper conductor cable of size 1.5 Sq mm 3 core from fittings to ceiling rose or connector and writing MES No with black synthetic enamel paint 2.0 cm high complete all as specified and directed. (Make : Havells Cat Part No ES-50 / Bajaj Electra-50 / Crompton Energion / Usha Technix)
S&F Exhaust fan ISI Marked 300 mm sweep Metallic body with louver shutter complete including M&L for providing/cutting the round hole of required size in wall finishing the same supply and grouting the ragged bolts in wall, fixing the frame on the exhaust side (outer surface of the wall) and connecting with and including PVC insulated three core 23/0.0076 copper cable, rubber insulated from ceiling rose to exhaust fan motor and writing MES No with black synthetic enamel paint 2.0 cm high complete all as specified and directed. (Make : Bajaj Supreme / Crompton Transair / Usha Aeroclean)
S&F LED tube light (batten) fitting 18 watt with decorative end caps, LED tube light, surface mounting, with integrated electronic driver, bipin holders, connector block, etc complete with all accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable of 1.5 sqmm with suitable size complete all as specified and directed. (Make : Crompton Cat No LCTL-18-CDL / Bajaj Cat NO BCLSB18NW / Havells Cat LHEXBLP79N1W018)
S&F LED mirror light fitting 7 watt aesthetically designed, provided with a high output PMMA diffuser for glare free light incl LED lamp etc complete with all accessories in and including connecting up with twin core twisted flexible copper conductor cable with suitable size copper wire complete all as specified and directed.
S&F LED Security light fitting of 25 watt made up of pressure die cast aluminium housing with toughened glass and individual high power LEDs with secondary optics with IP 66 protection including connecting up with twin core twisted flexible copper conductor cable of size 1.5 sqmm and GI pipe 'medium grade' 25 mm dia bracket of suitable size 1.2 mtr long alongwith clamps, nuts, bolts & washers etc duly painted with two coats of synthetic enamel paint over a coat of red oxide metal primer complete all as specified and directed. (Make : Crompton Cat Part No LSTS-25- CDL / Bajaj Cat BCLST25WLED / Havells Cat Endura citylite25WLED)
Note for item Nos 18 to 20 : Note for LED items (a) Tenderer shall submit test report of LED street light fitting from Government accredited test laboratory for LM - 79 and LM - 80. (b) Contractor has to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. The product will be replaced free of cost in the following case :- (i) Manfacturing defects. (ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (c) All LED light/luminare must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (d) Scope of work shall include supply and fixing street light fittings walls/building which includes needful T & P and required accessories etc if any, complete including making connection , testing etc complete .No extra payment is admissible on these account.
Sch 'A' Sec - IV (SITE CLEARANCE AND EARTHWORK)
Sch 'A' Sec - V A (MISCELLANEOUS ITEMS OF STP)
Sch 'A' Sec - V B (MISCELLANEOUS ITEMS OF STP)
Supplying, laying jointing & testing UPVC Sch. 40 pipes 200mm bore in any length with and including clamping at exposed walls complete all as specified and directed. (For complete STP location as per drawings and process and instrumentation diagram). NOTES :- UPVC fittings & hanging at wall and celling with clamps, tees with and flanges with all accessories etc are included in this rates.
Supply and Fixing pipe, GI Pipe, IS- 1239:2011 of 'heavy grade' and max permissible working pressure 5 Bar of size 200 mm complete all as specified and directed. Notes :- (Fittings & hanging at wall and celling with clamps, tees with and flanges with all accessories etc are included in this rates.)
Supply and Fixing pipe, GI Pipe, IS- 1239:2011 of 'heavy grade' and max permissible working pressure 5 Bar of size 300 mm complete all as specified and directed. Notes :- (Fittings & hanging at wall and celling with clamps, tees with and flanges with all accessories etc are included in this rates.)
Supply and fixing gun-metal, globe or gate valves, with iron wheel head, flanged both ends CI gate wih Brass PN - 1.6, ISI marked conforming to IS- 14846-2000 suitable for 25 mm bore complete all as specified and directed.
Supply and fixing gun-metal, globe or gate valves, with iron wheel head, flanged both ends CI gate wih Brass PN - 1.6, screwed both ends for iron pipe, ISI marked conforming to IS- 14846-2000 suitable for 50 mm bore complete all as specified and directed.
Supply and fixing Cast Iron Sluice/ Gate valve flanged Type, class PN-1.6, ISI marked conforming to IS- 14846-2000 suitable for 100 mm bore CI/DI flanged tube complete with gunmetal spindle flanged both ends CI gate with brass ring and iron wheel handle complete all as specified and directed.
Supply and fixing Cast Iron Sluice/ Gate valve flanged Type, class PN-1.6, ISI marked conforming to IS- 14846-2000 suitable for 150 mm bore CI/DI flanged tube complete with gunmetal spindle flanged both ends CI gate with brass ring and iron wheel handle complete all as specified and directed.
Supply and fixing Cast Iron Sluice valve flanged Type, class PN-1.6, ISI marked conforming to IS- 14846-2000 suitable for 200 mm bore CI/DI flanged tube complete with gunmetal spindle flanged both ends CI gate with brass ring and iron wheel handle complete all as specified and directed.
Supply and fixing Cast Iron Sluice/ Gate valve flanged Type, class PN-1.6, ISI marked conforming to IS- 14846-2000 suitable for 300 mm bore CI/DI flanged tube with gunmetal spindle flanged both ends CI gate with brass ring and iron wheel handle complete all as specified and directed.
Supply & Fixing of CI Non Return Valve conforming to IS 14846:2000 pressure rating PN 1.0 and maximum permissible working pressure 15 Bar of size 25 mm bore complete all as specified and directed.
Supply & Fixing of CI Non Return Valve conforming to IS 14846:2000 pressure rating PN 1.0 and maximum permissible working pressure 15 Bar of size 50mm bore of pipe complete all as specified and directed.
Supply & Fixing of CI Non Return Valve conforming to IS 14846:2000 pressure rating PN 1.0 and maximum permissible working pressure 15 Bar of size 100mm complete all as specified and directed.
Supply & Fixing of CI Non Return Valve, IS 14846:2000 pressure rating PN 1.0 and maximum permissible working pressure 15 Bar of size 150mm complete all as specified and directed.
Supply & Fixing of CI Air release Valve conforming to IS 14845:2000 double orifice kinetic, ball type of size 100mm complete all as specified and directed.
Supply and fixing of manual cleaning continuous rake type Coarse Bar Screen suitable for site. Bar to bar gap will be 28mm, Thickness of bar will be 8mm square bar with ISA 14mm x 14mm x 6 mm SS Angle and 3 mm thick SS perforated sheet as per design complete all as specified and directed. (MOC- SS304)
Supply and fixing of manual cleaning continuous rake type Coarse Bar Screen suitable for site. Bar to bar gap will be 20mm, Thickness of bar will be 8mm sq. bar with angle iron 14x14x6 mm SS Angle and 3 mm thick SS perforated sheet as per design complete all as specified and directed. (MOC- SS304)
Supply and fixing of High Flux Mixer Floting Type capacity sufficient For 520 KL reservior power as per Manufacturer complete all as specified and directed.
Supply and fixing of MBBR media made of poly propylene with virgin plastic UV stabilized milky white specific gravity 0.95 to 0.98, cylindrical shape of approximate dia 22 mm & height 20 mm, surface area 500 sqm/cum complete all as specified and directed. Make - Cool Deck/MM Aqual/ Guddi
Supply and fixing of Tube Settler modules in position as per manufacturers recommendations and as directed, made of strong, rigid, chemical resistant PVC (Resin utilized for PVC shall be prime grade, virgin, high impact and having specific gravity not less than 1.43 as per drawing. It shall be suitable for efficient operation at the design flow as required for STP 1.2 MLD) complete all as specified and directed. (For Anaerobic Digestor and Settling Tank)
Supply and fixing LT panel cubical type 2 mm thick CRCA sheet of suitable size, front & rear side openable, SCADA based (for operation logic only), 415 volts, factory made dust proof vermin proof (Kiosik type) for indoor use with following specifications:- ( For Pumping Station -1) 1. Indoor type enclosure panel Near Transformer A Digital 3 Phase Energy Meter 415V Secure / Elmeasure 1 No 2. Main Panel Design, manufacture, supply, installation, testing and commissioning of Pump Starter Panel fabricated out of 14 SWG sheet steel, floor mounting type fixed on angle Iron 40x40x6 mm frame / channel of suitable size, powder coated by seven tank process, 415 V electrolitic aluminium Bus bar 200 A, removable gland plates, cable glands, including connection with outgoing feeders and internal wiring with copper wires complete all as specified and directed.
A. MAIN INCOMER 1. 125A 4 Pole MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) - 1 No, No Derating up to 50 c 2. ON/OFF/TRIP INDICATION ESBEE -3 Nos 3. PHASE INDICATION ESBEE -3 Nos 4. VIF Meter 0-500V, 0-125A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune- 1 No 5. MFM Meter with RS Port Conzerv/ Neptune -1 No 6. C. T. 125/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO- 3 Nos 7. C. T. 125/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO- 1 No For APFC Sensing 8. 125A, 4P Change Over Socomac/L&T- 1 Nos
B. DG INCOMER 1. 125A 3P MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 2. ON/OFF/TRIP INDICATION ESBEE- 3 Nos 3. PHASE INDICATION ESBEE -3 Nos 4. VIF Meter 0-500V, 0-125A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5. MFM Meter with RS Port Conzerv/ Neptune- 1 No 6. C. T. 125/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos 7. C. T. 125/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -1 No For APFC Sensing
C. Bus Bar 200A TPN Aluminum Bus bar Set 1 Bus bar calculation 1 sqmm =0.8 amp D. MCCB/MCB/Starters Feeder 1. 20 HP Star Delta Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -3 Nos 2. 63A TP MCB, c-curve ABB/L&T- 4 Nos 3. 32A DP MCB, c-curve ABB/L&T- 2 Nos 4. 10A DP MCB, c-curve With Timer & Contactor for Street Light ABB/L&T -1 No 29 KVAR Capacitor Panel - 1 Set Single phase preventor - 1 No
E. Incomer: 1. 63A 3P MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) -1 No 2. PHASE INDICATION ESBEE -3 Nos 3. VIF Meter 0-500V, 0-60A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune- 1 No 4. C. T. 60/5A, CAST RESIN, 15VA AE/KAPPA/HA - 3 Nos 5. 2A SP MCB FOR CONTROL ABB/ L&T -3 Nos F. Relay Section 1. APFC DUAL RELAY 6 STAGE Epcos 1 No 2. 6A DP MCB ABB/L&T No 1 3. AUTO MANUAL SEL. SWITCH ABB/SALZER 1 No G. Bus bar 200A TP Aluminum Bus bar Bus bar calculation 0.8 sqmm =1 amp
H. Outgoing 1. CAPACITOR FEEDERS :- 0.5kvar x 1, 1kvar x 1, 2.5kvar x 1, 5kvar x 1, 10kvar X 2 2. 32A TP MCB, , c-curve ABB/L&T- 2 Nos 3. 16A TP MCB, , c-curve ABB/L&T -1 No 4. 10A TP MCB, , c-curve ABB/L&T -1 No 5. 6A TP MCB, , c-curve ABB/L&T -2 Nos 6. MO C12.5 CONTACTOR 2NO+2NC L&T -2 Nos 7. MO C8.5 CONTACTOR 2NO+2NC L&T -4 Nos 8. CAPACITOR BANK Standard DUTY MPP-S, (Shall Offer net Capaictance 440V) L&T/ EPCOS KVAR 29.00 9. Suitable nos of cooling fan of appropriate capacity
I. Readymade DB 10 Way SPN DB - 1 Set A. MAIN INCOMER 1. 32A DP RCBO, 30mA ABB/L&T -1 No B. MCB Feeder 1. 6A SP MCB, c-curve ABB/L&T -4 Nos 2. 16A SP MCB, c-curve ABB/L&T -4 Nos J Cables 1) 3.5CX70 Sqmm Al. Arm. Cable Finolex/Havells (Length as required at site, quantity will be measured and paid) 2) 3CX4 Sqmm Cu. Flex. Cable Finolex/Havells - 20 RM Note : The above cables of length required as per site shall be measured and paid separately.
Supply and fixing LT panel cubical typemade of 2 mm thick CRCA sheet of suitable size, front & rear side openable of suitable size SCADA based (for operation logic only), 415 volts, factory made dust proof vermin proof (Kiosik type) for indoor use with following specifications:- ( For Pumping Station -2) 1. Energy Meter:- Digital 3 Phase Energy Meter 415V Enclosure at gate of pumping station Secure / Elmeasure -1 No 2. Main Panel Design, manufacture, supply, installation, testing and commissioning of Pump Starter Panel fabricated out of 14 SWG sheet steel, floor mounting type fixed on angle iron 40x40x6 mm frame / channel of suitable size, powder coated by 7 tank process with 415 V electrolitic Aluminium Bus bar, removable gland plates, cable glands, including connection with outgoing feeders and internal wiring with copper wires of suitable size including PCC platform with foundation in PCC (1:2:4) complete all as specified and directed.
A. MAIN INCOMER 1 ) 63A 4 Pole MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 2) ON/OFF/TRIP INDICATION ESBEE -3 Nos 3) PHASE INDICATION ESBEE -3 Nos 4) VIF Meter 0-500V, 0-60A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5) MFM Meter with RS Port Conzerv/ Neptune -1 No 6) C. T. 30/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos 7) 63A, 4P Change Over Rotary Type Socomac/L&T 1 No
B. DG INCOMER 1) 63A 3P MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 2) ON/OFF/TRIP INDICATION ESBEE -3 Nos 3) PHASE INDICATION ESBEE -3 Nos 4) VIF Meter 0-500V, 0-60A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5) KWH Meter with RS Port Conzerv/ Neptune -1 No 6) C. T. 30/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos
C. Bus Bar 100A TPN Aluminum Bus bar Set 1 Bus bar calculation 1 sqmm =0.8 amp D. MCB/Starters Feeder 1) 10 HP Star Delta Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -2 Nos 2) 32A TP MCB, c-curve ABB/L&T -3 Nos 3) 25A DP MCB, c-curve ABB/L&T -2 Nos 4) 10A DP MCB, c-curve With Timer & Contactor for Street Light ABB/L&T -1 No 3 Readymade DB 8 way SPN DB - 01 Set
A. MAIN INCOMER 1) 25A DP RCBO, 30mA ABB/L&T -1 No B. MCB Feeder 1) 6A SP MCB, c-curve ABB/L&T -3 Nos 2) 16A SP MCB, c-curve ABB/L&T -3 Nos 5 Cables 1) 3.5CX25 Sqmm aluminium armoured. cable Finolex/Havells (Length as required at site, quantity will be measured and paid separately) 2) 3CX4 Sqmm Cu. Flex. Cable Finolex/Havells - 20 RM Note : The above cables of length required as per site shall be measured and paid separately.
Supply and fixing LT panel cubical type made of 2 mm thick CRCA sheet of suitable size, front & rear side openable of suitable size SCADA based (for operation logic only), 415 volts, factory made dust proof vermin proof (Kiosik type) for indoor use with following specifications:- (For Pumping Station -3) 1) Energy Meter Digital 3 Phase Energy Meter 415V Enclosure at gate of pumping station Secure / Elmeasure -1 No 2) Main Panel Design, manufacture, supply, installation, testing and commissioning of Pump Starter Panel fabricated out of 14 SWG sheet steel, floor mounting type, powder coated by 7 tank process with, 415 V electrolitic aluminium bus bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect.
A. MAIN INCOMER 1) 63A 4 Pole MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 NO, No Derating up to 50 c 2) ON/OFF/TRIP INDICATION ESBEE -3 Nos 3) PHASE INDICATION ESBEE -3 Nos 4) VIF Meter 0-500V, 0-60A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5) MFM Meter with RS Port Conzerv/ Neptune -1 No 6) C. T. 60/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos 7) 63A, 4P Change Over Rotary Type Socomac/L&T -1 No 8) Suitable Nos of cooling fans of appropriate capacity
B. DG INCOMER 1) 63A 3P MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 2) ON/OFF/TRIP INDICATION ESBEE -3 Nos 3) PHASE INDICATION ESBEE -3 Nos 4) VIF Meter 0-500V, 0-60A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5) KWH Meter with RS Port Conzerv/ Neptune -1 No 6) C. T. 30/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos
C. Bus Bar 100A TPN Aluminum Bus bar Set 1 Bus bar calculation 1 sqmm =0.8 amp D. MCB/Starters Feeder 1) 1 HP DOL Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -2 Nos 2) 6A TP MCB, c-curve ABB/L&T -2 Nos 3) 25A DP MCB, c-curve ABB/L&T -3 Nos 4) 32ATPMCB, c-curve With Timer & Contactor for Street Light ABB/L&T -1 No 3 Ready made DB 8 Way SPN DB -01 Set Single phase preventor - 1 No
A. MAIN INCOMER 1) 25A DP RCBO, 30mA ABB/L&T -1 No B. MCB Feeder 1) 6A SP MCB, c-curve ABB/L&T -3 Nos 2) 16A SP MCB, c-curve ABB/L&T -3 Nos 5 Cables 1) 3.5CX25 Sqmm Al. Arm. Cable Finolex/Havells (Length as required at site, quantity will be measured and paid separately) 2) 4CX6 Sqmm Cu. Arm. Cable Finolex/Havells - 40 RM 3) 3CX4 Sqmm Cu. Flex. Cable Finolex/Havells - 20 RM Note : The above cables of length required as per site shall be measured and paid separately.
Supply and fixing LT panel cubical type made of 2 mm thick CRCA sheet of suitable size, front & rear side openable of suitable size SCADA based,(For operation ligic only) 415 volts, factory made dust proof vermin proof (Kiosik type) for indoor use with following specifications:- (For STP Control Room) 1) 11KV Side A. Double Pole Structure with TPMO, 20A Fuse Set, Pin Insulators and all fittings for 160KVA Transformer Mounting -1 No B. Supply of 160KVA, 11KV/ 415 Volts, Indoor transformer as per Technical specifications & equipment schedule inclusive of oil for topping up. (Annexture-B) Kotsons/ GTB -1 No C. ACSR- Weasel Conductor RM As Per Site
2) Canopy type Enclosure panel Near Transformer A. Digital 3 Phase Energy Meter 415V Secure / Elmeasure -1 No B. 250A 3P MCCB, 35KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 3) Main Panel Design, manufacture, supply, installation, testing and commissioning of Pump Starter Panel floor mounting type, fabricated out of 14 SWG sheet steel, powder coated by 7 tank process with 415 V electrolitic Al. Bus bar, removable gland plates, cable glands, including connection with outgoing feeders and internal wiring with copper wires of suitable size complete all as specified and directed.
A. MAIN INCOMER 1) 250A 4 Pole MCCB, 35KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 2) ON/OFF/TRIP INDICATION ESBEE -3 Nos 3) PHASE INDICATION ESBEE -3 Nos 4) VIF Meter 0-500V, 0-250A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5) MFM Meter with RS Port Conzerv/ Neptune -1 No 6) C. T. 200/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos 7) C. T. 200/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -1 No For APFC Sensing 8) 250A, 4P Change Over Socomac/L&T -1 No
B. MAIN INCOMER 1) 250A 4P MCCB, 35KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) 1 No, No Derating up to 50 c 2) ON/OFF/TRIP INDICATION ESBEE -3 Nos 3) PHASE INDICATION ESBEE -3 Nos 4) VIF Meter 0-500V, 0-250A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune -1 No 5) MFM Meter with RS Port Conzerv/ Neptune -1 No 6) C. T. 200/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO -3 Nos 7) C. T. 200/5A, CAST RESIN TYPE, 15VA AE/KAPPA/INDO 1 No For APFC Sensing
C. Bus Bar 300A TPN Aluminum Bus bar 01 Set Bus bar calculation 1 sqmm =0.8 amp D. MCCB/MCB/Starters Feeder 1) 30 HP Star Delta Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -3 Nos 2) 10 HP Star Delta Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -3 Nos 3) 7.5 HP DOL Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -9 Nos
4) 2 HP DOL Starter with Incoming MCB, Contactor, Relay, SPP, ON/OFF PB, ON/OFF/TRIP Indication & Provision for Remote ON/OFF ABB / L&T -2 Nos 5) 100A 3P MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) - 03 Nos 6) 32A TP MCB, c-curve ABB/L&T -4 Nos 7) 25 Amp TPMCB, c-curve ABB/L&T No - 9 Nos 8) 16A DP MCB, c-curve With Timer & Contactor for Street Light ABB/L&T -1 No 63.5 KVAR Capacitor Panel - 01 Set 9) Single phase preventor - 01 No. 10) 32A DP, 10 KA MCB, C curve - 02 Nos 11) 10A TP, 10 KA MCB, C curve - 02 Nos
E. Incomer: 1) 125A 3P MCCB, 25KA, thermal magnetic type with ROH (with Spreader Link) ABB (T-Max)/ L&T (D-Sine) -1 No 2) PHASE INDICATION ESBEE -3 Nos 3) VIF Meter 0-500V, 0-125A, AC DIGITAL WITH INBUILT VSS AND ASS Conzerv/ Neptune 1 No 4) C. T. 125/5A, CAST RESIN, 15VA AE/KAPA/HA -3 Nos 5) 2A SP MCB FOR CONTROL ABB/ L&T -3 Nos F. Relay Section 1) APFC Dual RELAY 8 STAGE Epcos -1 No 2) 6A DP MCB ABB/L&T -1 No 3) AUTO MANUAL SEL. SWITCH ABB/SALZER -1 Nos
G. Bus bar 160A TPN Aluminum Bus bar Bus bar calculation 0.8 sqmm =1 amp H. Outgoing 1) CAPACITOR FEEDERS :-1kvar x 1, 2.5kvar x 1, 5kvar x 1, 10kvar X 1, 15kvar X 3 2) 63A TP MCB, , c-curve ABB/L&T -3 Nos 3) 32A TP MCB, , c-curve ABB/L&T -1 No 4) 16A TP MCB, , c-curve ABB/L&T -1 No 5) 10A TP MCB, , c-curve ABB/L&T -1 No 6) 6A TP MCB, , c-curve ABB/L&T -1 No 7) MO C15 CONTACTOR 2NO+2NC L&T -3 Nos
8) MO C12.5 CONTACTOR 2NO+2NC L&T - 1 No 9) MO C8.5 CONTACTOR 2NO+2NC L&T -3 Nos 10) CAPACITOR BANK Standard DUTY MPP-S, (Shall Offer net Capaictance 440V) L&T/ EPCOS KVAR 63.50 11) Suitable No of Cooling fans of appropriate capacity 4 Readymade DB 10 Way SPN DB - 01 Set A. MAIN INCOMER 1) 32A DP RCBO, 30mA ABB/L&T -1 No B. MCB Feeder 1) 6A SP MCB, c-curve ABB/L&T - 4 Nos 2) 16A SP MCB, c-curve ABB/L&T - 4 Nos 5 Cables 1) 3.5CX185 Sqmm Al. Arm. Cable Finolex/Havells RM As Per Site 2) 3CX4 Sqmm Cu. Flex. Cable Finolex/Havells - 20 RM Note : Length of cables as required at site, the quantity will be measured and paid separately.
Supply, installation, commissioning and testing of non clog submersible sewage Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 100 mm) having minimum Discharge 87.5 KLH at a minimum head of 16 metre suitable for delivery pipe 150 mm bore and minimum depth of sump upto 10 metre , 415V (+ 5% & +10%) & frequency 50Hz + 3%) . (For Sump well) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction: Pump casing (Pump+ Motor) CI (FG 260), Impeller: CI (FG 260) ; Shaft: SS – 410, Fast: SS
The pump shall consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life. (b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent the motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry.
(e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck foot bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life (g) Flanged duck wood bend for discharge pipe – 01 No (h) MS flange 150 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 150 mm dia 5 mm thick duly drilled holes 01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to starter. (l) Flow Meter of requisite range -01 No Note : (a) Pump will operate in such a way that two nos pumps will be working, and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump. (c) Operation as per hydrauliic depth : (i) For 1 m to 2.5 m : 01 pump in operation (ii) For depth above 2.5m - 02 Pumps in operation. (iii) No pumps to operate below 1 m depth
Supply, installation, commissioning and testing of non clog submersible sewage Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 100 mm) having min Discharge 26 KLH at a min head of 22 metre suitable for delivery pipe 50 mm dia bore and minimum depth of sump upto 10 metre , 415V (+ 5% & +10%) & frequency 50Hz + 3%). (For Equalization Tank) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction : Pump casing (Pump+ Motor) CI (FG 260), Impeller : CI (FG 260) ; Shaft : SS – 410 Fast : SS
The pump shall be consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life. (b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent the motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry.
(e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck foot bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life (g) Flanged duck wood bend for discharge pipe – 01 No (h) MS flange 100 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 100 mm dia 5 mm thick duly drilled holes -01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to LT panel board, (l) Flow Meter of suitable range -01 No Note : (a) Pump will operate in such a way that two nos pumps will be working and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump.
Supply, installation, commissioning and testing of non clog submersible sewage Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 100 mm) having min Discharge 29 KLH at a min head of 35 metre suitable for delivery pipe 150 mm dia bore and minimum depth of sump upto 10 metre , 415V (+ 5% & +10%) & frequency 50Hz + 3%). (For Pumping Station -1) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction : Pump casing (Pump+ Motor) CI (FG 260), Impeller : CI (FG 260) ; Shaft : SS – 410 Fast : SS The pump shall be consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life.
(b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry. (e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck wood bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life (g) Flanged duck foot bend for discharge pipe – 01 No
(h) MS flange 100 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 100 mm dia 5 mm thick duly drilled holes 01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to Stater (l) Level switches to facilitate start ON/OFF of the pump automatically. (m) Flow Meter of suitable range -01 No Note : (a) Pump will handle breakdown in such a way that two Nos pump will be working and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump.
Supply, installation, commissioning and testing of non clog submersible sewage Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 100 mm) having min Discharge 25 KLH at a min head of 25 metre suitable for delivery pipe 100 mm dia bore and minimum depth of sump upto 10 metre, volt 415V (+ 5% & +10%) & frequency 50Hz + 3%). (For Pumping Station -2) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction : Pump casing (Pump+ Motor) CI (FG 260), Impeller : CI (FG 260) ; Shaft : SS – 410 Fast : SS The pump shall be consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life.
(b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent the motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry. (e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck wood bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life (g) Flanged duck foot bend for discharge pipe – 01 No
(h) MS flange 100 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 100 mm dia 5 mm thick duly drilled holes 01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to LT panel board, (l) Level switches to facilitate start ON/OFF of the pump automatically. (l) Flow Meter of suitable range -01 No. Note : (a) Pump will handle breakdown in such a way that one no. pump will be working and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump.
Supply, installation, commissioning and testing of non clog submersible Grinder Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 40 mm) having min Discharge 10 KLH at a min head of 20 metre suitable for delivery pipe 50 mm dia bore with radial cutter & cutter ring moc ss304 and minimum depth of sump upto 10 metre, volt 415V (+ 5% & +10%) & frequency 50Hz + 3%). (For Pumping Station -3) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction : Pump casing (Pump+ Motor) CI (FG 260), Impeller : CI (FG 260) ; Shaft : SS – 410 Fast : SS The pump shall be consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life.
(b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent the motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry. (e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck wood bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life (g) Flanged duck wood bend for discharge pipe – 01 No
(h) MS flange 100 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 100 mm dia 5 mm thick duly drilled holes 01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to LT panel board, (l) Level switches to facilitate start ON/OFF of the pump automatically. (m) Flow Meter -01 No. Note : (a) Pump will handle breakdown in such a way that one no. pump will be working and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump.
Supply & fixing dosing pump high pressure single head gear motored adjustable dosing pump with all accessories such as lead tubing, connecting nuts, injection check valve, clay weight and ferrules complete all as specified and directed with following specifications :- (i) Adjustable high pressure - 0-100 PSI (ii) Power - 230 Volts, 50 Hz (iii) RPM - 44 (iv) HP - 1/30 fractional (v) Output - 2 US GPD to 40 US GPD
Supply and fixing dosing system (Model ads-1) consising of 100 litre PE/FRP tank with PE/FRP lid & level gauge along with agitator (920 rpm) with shaft and blade in SS 316 (FRP/Epoxy coated/ Plastic mounted on tank). Lid will have port hole for pouring Altoch and water when necessary. Lid will have provision for mounting Decrin Dosing pump on lid / wall. Motor: Voltage input - 230 volts single phase 50 Hz, Current Consumption - 0.4 Amp, Power - 120 watt, Speed- 6 pole induction no synchronous 920 RPM approx under load complete all as specified and directed.
Supply only ALTOCH-GP (Calcium based granular disinfectant for water treatment (packing in 45 Kg plastic drum) complete all as specified and directed.
Supply, fixing & making connections for Air blower of capacity 950 Cum/hour at 0.55 meter head, 415 V, 3 Phase 50 Hz complete all as specified inclusive of NRV, Air Filter, Cleaner etc complete all specified and directed. (MAKE : Kay / Everest / Ingersoll Rand) Note : Blower will be twin lobe or tri lobe system having turbo type blower.
Supply, installation, commissioning and testing of non clog submersible sewage Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 100 mm) having min Discharge 30 KLH at a min head of 40 metre suitable for delivery pipe 100 mm dia bore and minimum depth of sump upto 10 metre, volt 415V (+ 5% & +10%) & frequency 50Hz + 3%). (For BufferTank) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction : Pump casing (Pump+ Motor) CI (FG 260), Impeller : CI (FG 260) ; Shaft : SS – 410 Fast : SS The pump shall be consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life.
(b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent the motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry. (e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck wood bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life
(g) Flanged duck wood bend for discharge pipe – 01 No (h) MS flange 100 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 100 mm dia 5 mm thick duly drilled holes 01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to stater. (l) Level switches to facilitate start ON/OFF of the pump automatically. (m) Flow Meter -01 No. Note : (a) Pump will handle breakdown in such a way that two nos. pump will be working and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump.
Supply, installation, commissioning and testing of non clog submersible Pump set for type of installation stationary suitable to handle domestic sewage water (having PH value 7 and solid particle size 100 mm) having min Discharge 28.8 KLH at a min head of 20 metre suitable for delivery pipe 100 mm dia bore and minimum depth of sump upto 10 metre, volt 415V (+ 5% & +10%) & frequency 50Hz + 3%). (For Treated WaterTank) (MAKE : Kirloskar/Grundfoss/Wilo-Mather&Platt) Material of Construction : Pump casing (Pump+ Motor) CI (FG 260), Impeller : CI (FG 260) ; Shaft : SS – 410 Fast : SS The pump shall be consist of following features :- (a) Double bi-directional mechanical seal with silicon carbide faces for long service life.
(b) Lateral cable entry to avoid transport and installation damage & also having resin filled triple protection cable assembly to avoid leakage in the motor even in the event of damage of cable. (c) Temperature sensors to prevent the motor winding form overheating. (d) Special moisture sensor to prevent motor winding even in the event of accidental water entry. (e) Automatic, bolt-free connection, leakage prevented by means of elastic seal to allow operator-friendly to easy installation and removal of the pump sets from duck wood bend for stationary installation. (f) Antifriction ball bearing, packed with grease for life (g) Flanged duck wood bend for discharge pipe – 01 No
(h) MS flange 100 mm dia 5 mm thick duly drilled hole with nuts, bolts, washers and rubber gaskets etc -01 No (j) MS dead plate 100 mm dia 5 mm thick duly drilled holes 01 No (k) Submersible cable three core x 02 runs of required size and length from non clog submersible pump set to stater. (l) Level switches to facilitate start ON/OFF of the pump automatically. (m) Flow Meter -01 No. Note : (a) Pump will handle breakdown in such a way that two nos. pump will be working and one standby. (b) Operation logic would be such a way that duty cycle for each pump should equal 60 min for each pump.
Supply and fixing of tubuler air diffusers of 1000mm length and of 65mm dia with silicon membrane, threaded type for fine bubble of aeration with retrachable arrangement inclusive of proper hanger and ropes need to be provided for pulling of diffusers in future for maintancence complete all as specified and directed. (Make : Bobkay/ Airflex/ Raubioxon or equivalent)
Supply and fixing of tublar air diffusers of 500mm length and 65mm dia with silicon membrane, threaded type for fine bubble of aeration with retrachable arrangement inclusive of proper hanger and ropes need to be provided for pulling of diffusers in future for maintancence complete all as specified and directed. . (Make : Bobkay/ Airflex/ Raubioxon or equivalent)
Supply , install, testing and commissioning of silent (acoustic enclouser type) Diesel Engine driven generating set complying CPCB norms of capacity 160KVA, 415 volts, 3 phase 4 wire with Auto Main Failure Panel directly coupled complete with self starting system including accessories, equipment control panel etc as per BS/IS-5514/10002, complete and including of the followings:- (For STP Control Room) (Make : Kirloskar/ Cummins/ Greaves/ Mahindra)
(a) Alternator:- 160 KVA output at 0.8 PF AC 3 phase 4 wire 415 volts 50 C/S, brush less, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces, class 'H' insulation with IP-23 protection and voltage regulation + 1.5% as per IS-4722 or BS 2613 -1970 all as specified and directed. (b) Diesel engine : Diesel engine multi cylinder 4 stroke, water cooled electric start suitable capacity to drive above alternator independently, coupled directly through flexible coupling, cold starting, speed of DG set from No load to full load complete with fuel tank of capacity as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated with asbestos rope and with support and residential silencer mufflers etc for continuous operation and standard accessories, sump preheaters etc all as specified.
(c) Control panel. The standard control panel consisting of control cubical fabricated sheet steel construction indoor type suitable for the followings- (i) Gen set controller microprocessor based multifunctional with LED display for engine water temperature, Lub oil pressure, Engine RPM, Engine shut down display, total Hours run and suitable for protection against high water pressure, low lub oil pressure, over speed and battery charger failure. (ii) Digital multifunctional meter with LED display suitable to display all electrical parameters of individual phase such as Voltage, current, frequency, KVA, KW, power factor and having RS 485 communication port complete with appropriate CTs and control wiring.
(iii) MCCB 4 pole 415 volt AC of suitable capacity not less than 250 Amps all as required complete with copper bus bar all as per standard engineering practice and as per manufacturer recomendations. (iv) HRC fuses for protection as per standard engineering practice and manufacturer recommendations for protection of meters etc. (d) Electric Starter Equipment :- The equipment will comprise the followings:- (i) Start Stop push button. (ii) Maint free Battery duly initial charged & Battery lead of adequate capacity
(iii) Starter motor (iv) Starter gearing (v) Alternator/ dynamo of suitable capacity to charge the batteries while DG set is running complete with auto cut. (e) Invertor cum battery charger 500 VA capacity suitable to work on 230 volts 50 Hz AC supply system for charging of DG set batteries externally when DG set is off position. PCC foundation of DG set all as per manufacturer recommendation or required at site or directed by Engineer-incharge
Supply , install, testing and commissioning of silent (acoustic enclouser type) Diesel Engine driven generating set complying CPCB norms of capacity 63 KVA, 415 volts, 3 phase 4 wire with Auto Main Failure Panel directly coupled complete with self starting system including accessories, equipment control panel etc as per BS/IS-5514/10002, complete and including of the followings:- (For Pumping Station No -1) (Make : Kirloskar/ Cummins/ Greaves/ Mahindra)
(a) Alternator:- 63 KVA output at 0.8 PF AC 3 phase 4 wire 415 volts 50 C/S, brush less, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces, class 'H' insulation with IP-23 protection and voltage regulation + 1.5% as per IS-4722 or BS 2613 -1970 all as specified and directed. (b) Diesel engine : Diesel engine multi cylinder 4 stroke, water cooled electric start suitable capacity to drive above alternator independently, coupled directly through flexible coupling, cold starting, speed of DG set from No load to full load complete with fuel tank of capacity as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated with asbestos rope and with support and residential silencer mufflers etc for continuous operation and standard accessories, sump preheaters etc all as specified.
(c) Control panel. The standard control panel consisting of control cubical fabricated sheet steel construction indoor type suitable for the followings- (i) Gen set controller microprocessor based multifunctional with LED display for engine water temperature, Lub oil pressure, Engine RPM, Engine shut down display, total Hours run and suitable for protection against high water pressure, low lub oil pressure, over speed and battery charger failure. (ii) Digital multifunctional meter with LED display suitable to display all electrical parameters of individual phase such as Voltage, current, frequency, KVA, KW, power factor and having RS 485 communication port complete with appropriate CTs and control wiring.
(iii) MCCB 4 pole 415 volt AC of suitable capacity not less than 250 Amps all as required complete with copper bus bar all as per standard engineering practice and as per manufacturer recomendations. (iv) HRC fuses for protection as per standard engineering practice and manufacturer recommendations for protection of meters etc. (d) Electric Starter Equipment :- The equipment will comprise the followings:- (i) Start Stop push button. (ii) Maint free Battery duly initial charged & Battery lead of adequate capacity
(iii) Starter motor (iv) Starter gearing (v) Alternator/ dynamo of suitable capacity to charge the batteries while DG set is running complete with auto cut. (e) Invertor cum battery charger 500 VA capacity suitable to work on 230 volts 50 Hz AC supply system for charging of DG set batteries externally when DG set is off position. PCC foundation of DG set all as per manufacturer recommendation or required at site or directed by Engineer-incharge
Supply , install, testing and commissioning of silent (acoustic enclouser type) Diesel Engine driven generating set complying CPCB norms of capacity 15 KVA, 415 volts, 3 phase 4 wire with Auto Main Failure Panel directly coupled complete with self starting system including accessories, equipment control panel etc as per BS/IS-5514/10002, complete and including of the followings:- (For Pumping Station No -2) (Make : Kirloskar/ Cummins/ Greaves/ Mahindra)
(a) Alternator:- 15 KVA output at 0.8 PF AC 3 phase 4 wire 415 volts 50 C/S, brush less, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces, class 'H' insulation with IP-23 protection and voltage regulation + 1.5% as per IS-4722 or BS 2613 -1970 all as specified and directed. (b) Diesel engine : Diesel engine multi cylinder 4 stroke, water cooled electric start suitable capacity to drive above alternator independently, coupled directly through flexible coupling, cold starting, speed of DG set from No load to full load complete with fuel tank of capacity as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated with asbestos rope and with support and residential silencer mufflers etc for continuous operation and standard accessories, sump preheaters etc all as specified.
(c) Control panel. The standard control panel consisting of control cubical fabricated sheet steel construction indoor type suitable for the followings- (i) Gen set controller microprocessor based multifunctional with LED display for engine water temperature, Lub oil pressure, Engine RPM, Engine shut down display, total Hours run and suitable for protection against high water pressure, low lub oil pressure, over speed and battery charger failure. (ii) Digital multifunctional meter with LED display suitable to display all electrical parameters of individual phase such as Voltage, current, frequency, KVA, KW, power factor and having RS 485 communication port complete with appropriate CTs and control wiring.
(iii) MCCB 4 pole 415 volt AC of suitable capacity not less than 250 Amps all as required complete with copper bus bar all as per standard engineering practice and as per manufacturer recomendations. (iv) HRC fuses for protection as per standard engineering practice and manufacturer recommendations for protection of meters etc. (d) Electric Starter Equipment :- The equipment will comprise the followings:- (i) Start Stop push button. (ii) Maint free Battery duly initial charged & Battery lead of adequate capacity
(iii) Starter motor (iv) Starter gearing (v) Alternator/ dynamo of suitable capacity to charge the batteries while DG set is running complete with auto cut. (e) Invertor cum battery charger 500 VA capacity suitable to work on 230 volts 50 Hz AC supply system for charging of DG set batteries externally when DG set is off position. PCC foundation of DG set all as per manufacturer recommendation or required at site or directed by Engineer-incharge
Supply , install, testing and commissioning of silent (acoustic enclouser type) Diesel Engine driven generating set complying CPCB norms of capacity 10 KVA, 415 volts, 3 phase 4 wire with Auto Main Failure Panel directly coupled complete with self starting system including accessories, equipment control panel etc as per BS/IS-5514/10002, complete and including of the followings:- (For Pumping Station No -3) (Make : Kirloskar/ Cummins/ Greaves/ Mahindra)
(a) Alternator:- 10 KVA output at 0.8 PF AC 3 phase 4 wire 415 volts 50 C/S, brush less, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces, class 'H' insulation with IP-23 protection and voltage regulation + 1.5% as per IS-4722 or BS 2613 -1970 all as specified and directed. (b) Diesel engine : Diesel engine multi cylinder 4 stroke, water cooled electric start suitable capacity to drive above alternator independently, coupled directly through flexible coupling, cold starting, speed of DG set from No load to full load complete with fuel tank of capacity as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated with asbestos rope and with support and residential silencer mufflers etc for continuous operation and standard accessories, sump preheaters etc all as specified.
(c) Control panel. The standard control panel consisting of control cubical fabricated sheet steel construction indoor type suitable for the followings- (i) Gen set controller microprocessor based multifunctional with LED display for engine water temperature, Lub oil pressure, Engine RPM, Engine shut down display, total Hours run and suitable for protection against high water pressure, low lub oil pressure, over speed and battery charger failure. (ii) Digital multifunctional meter with LED display suitable to display all electrical parameters of individual phase such as Voltage, current, frequency, KVA, KW, power factor and having RS 485 communication port complete with appropriate CTs and control wiring.
(iii) MCCB 4 pole 415 volt AC of suitable capacity not less than 250 Amps all as required complete with copper bus bar all as per standard engineering practice and as per manufacturer recomendations. (iv) HRC fuses for protection as per standard engineering practice and manufacturer recommendations for protection of meters etc. (d) Electric Starter Equipment :- The equipment will comprise the followings:- (i) Start Stop push button. (ii) Maint free Battery duly initial charged & Battery lead of adequate capacity
(iii) Starter motor (iv) Starter gearing (v) Alternator/ dynamo of suitable capacity to charge the batteries while DG set is running complete with auto cut. (e) Invertor cum battery charger 500 VA capacity suitable to work on 230 volts 50 Hz AC supply system for charging of DG set batteries externally when DG set is off position. PCC foundation of DG set all as per manufacturer recommendation or required at site or directed by Engineer-incharge
Supply and install Triple spur gear type (Chain pulley block) heavy duty class II conforming IS : 3832 tested at 50 % overload, hook as per IS 15560-2005 LOAS CHIAN 8 mm, grade 80, alloy steel wheel SG iron of capacity 05 ton lift height 3 meter of size 672 mm x 295 mm x 173 mm, weight 30 kg, complete all as specified and directed.
Supply only following lab equipments and consumables required for testing of treated water in laboratory complete all as specified and directed : A. Lab Equipments : 1. Breaker Borosil 1000 cc - 3 Nos. 2. Breaker Borosil 500 cc - 3 Nos 3. Breaker Borosil 250 cc - 3 Nos 4. Reagent bottle Borosil glass 1 litre - 2 Nos 5. Reagent bottle Borosil glass 500 ml - 2 Nos 6. Reagent bottle Borosil glass 250 ml- 2 Nos 7. B.O.D. Botlle 300 ml Borosil glass - 4 Nos 8. Reagent bottle amber Wm SC Borosil Glass - 4 Nos
9. Leibig Condenser B19/26, 300 mm - 3 Nos 10. Kjeldahl Long Neck B-24 Borosil Glass - 4 Nos 11. Pipette Volumetric 10 ml Borosil Glass - 1 No 12. Pipette Volumetric 25 ml Borosil Glass - 1 No 13. Pipette Graduated 1 ml Borosil Glass - 2 Nos 14. Pipette Graduated 5 ml Borosil Glass - 2 Nos 15. Pipette Graduated 10 ml Borosil Glass - 2 Nos 16. Burette 50 ml SC Borosil Glass - 1 No 17. Burette 10 ml SC Borosil Glass - 1 No 18. Double stage distillation 5 lit Borosil Glass - 1 No 19. Measuring Cylinder 1 liter Borosil Glass 20. Measuring Cylinder 500 ml Borosil Glass 21. Measuring Cylinder 250 ml Borosil Glass
22. Measuring Cylinder 100 ml Borosil Glass 23. Funnel 100 ml - 2 Nos 24. Funnel 75 ml - 2 Nos 25. Desiccator 200 mm - 1 No 26. Volumetric Flask 500 ml - 1 No 27. Volumetric Flask 250 ml - 1 No 28. Burette 50 ml - 1 No 29. Pippette 10 ml - 1 No 30. Volumetric Flask 1000ml - 1 No 31.. Burette stand (Polycab) 225x150 mm - 2 Nos 32. Clamp fisher type (Polycab) - 2 Nos 33. Test tube stand - 2 Nos 34. Pipette stand - 2 Nos
35. Conical flask (Borosil) 250 ml - 2 Nos 36. Conical flask (Borosil) 100 ml - 2 Nos 37. Test tube (Borosil) 18x150 mm - 10 Nos 38. Test tube (Borosil) 15x125 mm - 10 Nos 39. Volumetric flask (Borosil) 250 ml - 3 Nos 40. Crucible tong SS 38 cms - 1 No 41. Hot plate 20 cm - 1 No 42, Hot air oven 600x600x600cm SS (Digital with fan) - 1 No 43. Vacuum pump with fowl trap, release valve, high vacuum pipe and other fittings - 1 No 44. Muffle furnace 9x494" digital - 1 No 45. PH meter - 1 No
46. Electronic scale 80 mg - 1 No 47. BOD incubator (4 cuft, SS with PID Controller) 1 Pcs 48. Bacteriological Incubator - 1 Pc 49. Autoclave 10"x18" (Alln SS with PID controller, timer and low water cut off) - 1 No. 50. Heating mantle 500 ml - 1 No 51. Heating mantle 1000 ml - 1 No 52. Conductivity meter - 1 No Chemicals : 1. Starch 500 gm Qualigens - 1 Pkt 2. Salicylic acid 500 mg - 1 Pkt 3. Di-potassium hydrogen phosphate 500g - 1 Pkt 4. Di-sodium hydrogen phosphate 500 g - 1 Pkt 5. Sodium Thiosulphate 500 g - 1 Pkt
6. Potassium dihydrogen phosphate 500 g - 1 Pkt 7. Calcium chloride 500 g - 1 Pkt 8. Ferric chloride 500 g - 1 Pkt 9. Sodium hydroxide 500 g - 1 Pkt 10. Manganese sulphate 500 g - 1 Pkt 11. Sodium sulphate - 1 bottle 12. Sodium Azide 100 g - 1 Pkt 13. Manganese sulphate 500 g - 1 Pkt 14. Potassium Iodide - 1 Pkt 15. Sulfamic Acid GR 100 g - 1 Pkt 16. Membrane filter Sartorious 0.45u, 47 mm - 1 Pkt
17. Ammonium Chloride - 1 Pkt 18. Potassium Dichromate - 1 bot. 19. Ammonium Ferrous Sulphate - 1 bot. 20. Ferroin indicator 100 ml - 1 bot. 21. Buffer tab. (4, 7 and 9.2) - 3 Pkt (1 Pkt each) 22. Chlorotex Reagent 100 ml - 1 Pkt 23. Copper Sulphate - 1 bot. 24. Acetic Acid Qualigens - 1 Pkt 25. Mercuric Sulphate 250 g - 1 Pkt 26. SIlver Sulphate 25 gm - 1 bottle
Supply of aerobic culture microbes for innoculation at the time of commissioning of STP complete all as specified and directed.
Total amount of Sch 'A' Part - VI (ROAD & HARDSTANDING) (For details see Schedule 'A' Part- VI in PDF folder)
Total amount of Sch 'A' Part - VII ( Security Fencing Works) (For details see Schedule 'A' Part- VII in PDF folder)
Total amount of Sch 'A' Part - VIII A (External Electrification) (For details see Schedule 'A' Part- VIII A in PDF folder)
SCHEDULE 'A' PART-VIII B (EXTERNAL ELECTRIFICATION)
Supply, instalation, testing and commissioning of pole mounted transformer copper wound stepdown outdoor type conforming to IS : 1180 (Part-II), Level- II complete with standard fittings HT 11 KV 3 phase, LT 433 volts,3 phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per latest IS of capacity 160 KVA copper wound including intial oil filling to appropriate level with desired dielectric strength and connected with the electric system including jointing materials, temperature rise 50/55 degree C and standard accessories complete all as specified and directed.as under :-
(a) Cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side. (b) Arrangement for connecting busbar trunking with neutral brought out as earthing terminal . (c) Off load tap changer +/- 7.5% in steps of 2.5% (d) Bi-directional roller. (e) conservator with drain valve (f) earthing terminals 02 Nos of the body of transformer & 02 Nos for neutral earthings. (g) Double diaphragm explosion vent.
(h) Radiator with top & bottom shut off valve . (j) first filling of oil including make up fill. (k) Silica gel breather with oil seal . (l) Rating and diagram plate . (m) Air release plug. (n) Winding temprature indicator.(WTI) (o) Oil temperture indicator. (p) Magnetic oil level gauge. (q) Marshalling Box
S&F LED security light fitting 72 watt made up of pressure die cast aluminium housing with toughened glass and individual high power LEDs with secondary optics with IP 66 protection including GI pipe bracket medium grade, 1.2 m length of 40 mm dia clamps, nuts, bolts & washers etc duly painted with two coats of synthetic enamel paint over a coat of red oxide metal primer all as specified and directed. (Make : Crompton Cat part no LSTP-72-CDL / Bajaj Cat no BRTFG72WLED V-3 / Havells Endura cityliner 72W)
M&L for cable route indicators for marking route of HT cable '11 KV HV' embossed etc to be embedded in ground with PCC foundation complete all as specified and directed.
M&L for cable route indicators for marking route of LT cable with '440 V LV' embossed etc to be embedded in ground with PCC foundation complete all as specified and directed.
Supply & Fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, aluminium conductor cable of size 25 to 50 sqmm, Indoor/Outdoor type complete all as specified and directed.
-ditto- as per item no. 75 above but for cable of size 70 to 95 sqmm.
Supply and laying cable XLPE PVC insulated PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 Sqmm, 4 core complete all as specified and directed.
-ditto- as per item no. 77 above but for cable of size 10 sqmm,2 core.
-ditto- as per item no. 77 above but for cable of size 25 sqmm, 4 core.
-ditto- as per item no. 77 above but for cable of size 35 Sqmm 3.5 core.
-ditto- as per item no. 77 above but for cable of size 50 Sqmm 3.5 core.
-ditto- as per item no. 77 above but for cable of size 70 Sqmm 3.5 core.
-ditto- as per item no. 77 above but for cable of size 185 Sqmm 3.5 core.
M & L for earthing complete with galvanized steel earth plate electrode size 60cmx60cmx6.3 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level connected to GI earth strip 32x6 mm dia by means of nuts, bolts, check nuts, washers GI earth strip incase in and including 50mm dia GI pipe light grade for protection of earth strip upto a length of 7.5mtr including earth work/excavation in hard/dense/rock soil, common salt, charcoal etc., PCC 1:2:4 type B-1 as in earth pit. RCC pit cover 50mm thick precast RCC 1:2:4 type B-1 duly reinforced with 6mm dia mild steel round bars @ 150mm c/c both ways with 10mm dia MS bar for lifting handle including 20mm dia GI pipe medium grade 1.5m long as watering pipe, GI sheet 0.63 mm thick funnel, wire mesh etc complete all as specified and shown in electric plate No 3 of SSR Part-I 2009 on page No 497 including testing on completion etc complete all as specified and directed.
Material and labour Earthing complete with copper earth plate electrode of size 60cm x 60cm x 3.15 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including CopperS strip 20 X 3 mm (upto the body of equipment) by means of Cu bolts/nuts/washers, protected by 40 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mm bore GI light grade pipe for watering and including funnel, wire mesh,RCC cover & frame, PCC (1:3:6) type C2 (using 40 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, complete all as specified & shown in electrical plate No. 3 of SSR Part – I.
Total amount of Sch 'A' Part - IX A (Gravity Sewer Collection Network) (For details see Schedule 'A' Part-IX A in PDF folder)
Sch 'A' Part-IX B (Gravity Sewer Collection Network)
Material and labour for HDPE DWCP (SN8) confirming to IS16098, 150 mm nominal size complete laid in trenches and jointed including testing alongwith necessary jointing material tees/ union/ socket etc complete all as specified and directed. Note:- (Earthwork, removal, return filling and PCC shall measured and paid separately.)
Material and labour for HDPE DWCP (SN8) confirming to IS16098, 200 mm nominal size complete laid in trenches and jointed including testing alongwith necessary jointing material tees/ union/ socket etc complete.complete all as specified and directed. Note:- (Earthwork, removal, return filling and PCC shall measured and paid separately.)
Material and labour for HDPE DWCP (SN8) confirming to IS16098, 250 mm nominal size complete laid in trenches and jointed including testing alongwith necessary jointing material tees/ union/ socket etc complete.complete all as specified and directed. Note:- (Earthwork, removal, return filling and PCC shall measured and paid separately.)
Material and labour for HDPE DWCP (SN8) confirming to IS16098, 300 mm nominal size complete laid in trenches and jointed including testing alongwith necessary jointing material tees/ union/ socket etc complete all as specified and directed. Note:- (Earthwork, removal, return filling and PCC shall measured and paid separately.
Material and labour for HDPE DWCP (SN8) confirming to IS16098, 400 mm nominal size complete laid in trenches and jointed including testing alongwith necessary jointing material tees/ union/ socket etc complete all as specified and directed. Notes:- (i) Earthwork, removal, return filling and PCC shall measured and paid separately. (ii) The diamenstions of HDPE DWPC pipes (SN-8) shall be as per specification of IS - 16098 (Part-II) : 2013.
Supply & Fixing of Factory made precast cement concrete man holes Covers including frame as per IS standerd (Heavy Duty) EHD35 560 MM DIA complete all as specified and directed.
S&F SFRC Foot Rest with PCC (1:2:4) TYPE B-1, 20 MM graded stone aggregate of size 350 X230X150 MM complete all as specified and directed.
M&L for making hole under road and hard standing suitable for laying and inserting pipe upto 150 mm bore (any length) by mechanical drill system or Auger system and and making the surface good as existing surface including removal of surplus soil complete all as specified and directed. (For sewer line and treated water supply both)
Material & Labor in Construction of masonry Automatic Flushing Tank Complete of capacity 1200.00 Lit Size 120x120x1000 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for RCC top slab 1:2:4 mix type B-1 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), including necessary excavation, foundation concrete 1:5:10 type E-2 (1 cement : 5 fine sand:10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 15 mm thick finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 , complete complete all as specified and directed.
Demolition of existing manholes for the part projecting above the GL and sand/soil/earth filling under floors or in foundations including watering and consolidation distance n. exc. 500 m complete all as specified and directed.
Sch 'A' Part - X (PRESSURISED SEWAGE COLLECTION NET WORK)
Total amount of SCHEDULE 'A' PART-XI A (EXTERNAL WATER SUPPLY) (For details see Schedule 'A' Part-XIA in PDF folder)
SCHEDULE 'A' PART-XI B (EXTERNAL WATER SUPPLY)
Material & Labor in Construction of masonry Valve Pit 75x75x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, air release valve & gate valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), including necessary excavation, foundation concrete (1 cement :5 fine sand :10 graded stone aggregate 40 mm nominal size )and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 complete all as specified.
M&L for drilling and providing water connection from existing CI / DI pipe line of size 80 mm/ 100 mm / 150 mm dia in position incl jointing accessories complete all as specified and directed.
Supplying, laying jointing & testing DI pipes 100 mm bore, spigot and socket ends, centrifugally cast (spun) class "K-9" conforming to IS-8329 -2000 in any length with & including Tyton Joints laid in trenches complete all as specified and directed.
-ditto- as per item no 104 above but of DI pipe size 150 mm bore complete all as specified and directed.
-ditto- as per item no 104 above but of DI pipe size 200 mm bore complete all as specified and directed. Note for item Nos 104 to 106 : DI fittings & Excavation and earthwork will be measured and paid for separately under respective item of Schedule 'A'.
Supply & Fixing DI special fittings upto 200 mm bore of any type, radius, angle, tapers, increasing, decreasing sockets, tees, tail pieces and collars etc ISI marked confirming to IS: 9523-1980 complete all as specified and directed.
Total amount of Sch 'A' Part - XII A (TREATED WATER DISTRIBUTION NET WORK) (For details see Schedule 'A' Part-XII A PDF folder)
Sch 'A' Part - XII B (TREATED WATER DISTRIBUTION NET WORK)
Supply, laying, jointing and testing pipe HDPE in violet colour, Spigot and Socketed conforming to IS : 7634 (Part - II) including specials, Class “PE63”, 100 mm (4”) dia complete all as specified and directed.
Supply, laying, jointing and testing pipe HDPE in violet colour, Spigot and Socketed conforming to IS : 7634 (Part - II) including specials, Class “PE63”, 75 mm (3”) dia complete all as specified and directed. Note for item 109.00 & 110.00 : (i) All the HDPE fittings / specials shall be conforming to IS : 8360 (Part I & II). (ii) HDPE fittings / specials shall be strictly of same make as that of HDPE pipe.
M & L constructing masonry Chamber 750x750x1000 mm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, air release valve & gate valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), including necessary excavation, foundation concrete 1:5:10 (1cement : 5 fine sand:10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 with and incl 40x40x6 mm MS angle frame, 3.15 mm thick MS sheet cover with appropriate size, lifting handles and locking arrangement including painting steel / iron surfaces with two coats of black bituminious paint over a coat of red oxide primer complete all as specified and directed. (For treated water supply)
Ditto as per item no. 111 above, but chamber size 900x900x1000 mm complete all as specified and directed.
Supply and fixing Cast Iron Sluice/Gate valve flanged type PN-1.0, ISI marked conforming to IS- 14846-2000 suitable for 80 mm bore CI/DI flanged type complete with gunmetal spindle flanged both ends CI gate with brass ring and iron wheel handle complete all as specified and directed.
Total amount of Sch 'A' Part - XIII (DEMOLITION AND RECONSTRUCTION OF BDY WALL) (For details see Schedule 'A' Part-XIII PDF folder)
Sch 'A' Part - XIV (Manning & Operation)
Manning and operation of Sewage Treatment Plant System for 12 months (After completion of Phase I) with one skilled FGM, one electrician/Mechanic and plant supervisor in three shift of 08 hours each for each continious operation and for STP and three pumping station shift of 08 hours each in a day (including sunday/holiday) including cleaning to complete permises, ensuring attending all repairs, breakdowns etc promptly with out delay, servicing and maintenance of plant as per PS, involving own conveyance and communication system like mobile etc arrangement complete for STP plant and three pumping station with all minor consumable and expandable items and labour and tools for smooth and efficient operation complete all as specified and directed.
Manning and operation of Sewage Treatment Plant System for 12 months (After completion of M&O as given in Item No 116 here in before) with one skilled FGM, one electrician/Mechanic and plant supervisor in two shift of 08 hours each for each continious operation for STP and three pumping station shift of 08 hours each in a day (including sunday/ holiday) including cleaning to complete permises, ensuring attending all repairs, breakdowns etc promptly with out delay, servicing and maintenance of plant as per PS, involving own conveyance and communication system like mobile etc arrangement complete for STP and three pumping station with all minor consumable and expandable items and labour and tools for smooth and efficient operation complete all as specified and directed.
Note for Item 117 & 118 (a) The shift timming will be as mentioned below :- (i) First Shift 0600 hrs to 1400 hrs. (ii) Second Shift 1400 hrs to 2200 hrs. (b) Records of activity such as voltage/current/PF/energy consumed/ temperature of transformer, breakdown, day to day maintenance of STP and three pumping station etc. Log book and other consumable to be provided by contractor. (c) The contractor shall ensure the all safety precautions are strictly exercised by the staff employed him. Adherance to IE rule and satutory rules in vogues must be ensured. The contractor shall be fully responsible for any mishap that occurs due to any fault of the employee or no adherance of safety norms. He shall provide all shafty gear/pamplete/poster at all installation. (d) One STP of capacity 1.2 MLD & three pumping stations.
(e) Sludge drying beds shall be cleaned regularly. (f) Dual media bed shall be regularly cleaned. (g) Contractor shall attend any type of electrical fault in the panel with minor stores i.e cable jumpers, insulating materials, glands packing and grease etc without any extra cost. (h) Daily log sheet as per specimen given by department shall be provided and maintained by the contractor without any extra charges. (j) First aid box complete with medicines shall be kept at all the Installations.
Note: Tenderers may be noted that amount of credit Rs. 14600.00 will be deducted from the total amount arrived, at the time of acceptance of contract. (For details please refer Schedule of credit).