Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 49 53 7 13 1ST FLOOR SAMPADA GALAXY BS LAYOUT NEAR 4TH TOWN POLICE STATION VISAKHAPATNAM ANDHRA PRADESH 530013 | VISAKHAPATANAM | ANDHRA PRADESH | 530013 | Admitted-Finance |
Tender Value
₹23.6 L
EMD Value
₹47,120
Closing Date
5 May 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE No 2 Visakhapatnam
Commander Works Engineer 2 ,Chief Engineer Navy Visakhapatnam Complex, Station Road, Visakhapatnam, 530004
PROVISION OF RMUs FOR HANGER No 10 HANGER 11 AND SHITL HNGER AT INS KALINGA VISAKHAPATNAM
2022_MES_508312_2
82553
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Kalinga
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE Kalinga
₹47,120
Yes
19 May 2022
13 Apr 2022
7 May 2022
13 Apr 2022
5 May 2022
21 Apr 2022
13 Apr 2022 - 20 Apr 2022
60 days
Amount
Supply, install, testing & commissioning of Factory Made 11 KV, 630 Amps, 21 kA for 3 Seconds, SF6 Insulated, Motorized, Outdoor, 6 Way RMU Consisting of 2 Nos VCB Incoming, 1 Nos VCB Outgoing for Feeder and 3 Nos VCB Outgoing for Transformer complete all specified and as directed and shall comprise of the following: [A] RMU shall be 11 KV, 630 Amps, 21 kA for 3 Seconds, SF6 Insulated, Motorized, Outdoor, 6 Way RMU, Right side Extensible with Air Insulated Bus Connected Metering unit, Type tested in line with latest IEC Standards, suitable for operations at a height up to 1000 Meters above sea level and at 40ºC Ambient Temperature without any de-rating, Switchgear and Busbar shall all be contained in a Stainless Steel Enclosure [Minimum 2mm thick AISI 441 Grade] filled with SF6 at 0.3 Bar [300 hPa] Relative Pressure, RMU Tank shall provide Full Insulation and Switchgear shall be insensitive to the environment with Degree of Protection of IP67, Switchgear Operating Mechanism shall have an IP2X Protection and Cable Chamber shall have IP3X Protection, Outer Enclosure shall be IP 54 type tested, Powder Coated with Pure Polyester Based Paint, suitable for the site installation conditions,
Accidental Overpressure due to an Internal Arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator, Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. Extension of cubicle shall require 450mm to handle and the gap between the coupled RMU’s must be within 10mm. [B] Vacuum Circuit Breaker [VCB], comprising of the following: [i] 11 KV, 630 Amps, 21 kA VCB with Manual / Motorised Spring Assisted Mechanism and Series Trip Coil – 1 No, [ii] Load Break Switch with Built-In Earth Switch – 1 No [iii] Position Indicator through clear front mimic in line with IEC 62271-103 – 1 No [iv] Self Powered Relay with O/C, S/C, E/F Protection. Relay shall have a Front USB / RS485 / RS232 Port for Laptop Interface / Modbus Communication, LCD Display, 10 Event Records, 5 Fault Records, min 2 setting group and keypad for setting parameters for the relay – 1 No [v] CT Ratio 200-100/1-1A for Incoming, 200-100/1-1A for 2 Nos Feeder Outgoing and CT Ratio 100-50/1-1A, 4 Nos Transformer Outgoing, Class - 1.0, 2.5VA for Metering and Class 10P10, 2.5 VA for Protection – 1 Set [vi] Live Cable Indicator with indication at the Front and Three Inlets to check the Synchronization of Phases – 1 No
[vii] Cable Termination Bushing suitable for up to 1 Run, 3 Core, 300 Sq.mm, XLPE Cable – 1 Set [viii] Cable Termination Cover Boots [Push on type] – 1 Set [ix] Fault Passage Indicator FPI. [x] Circuit Breakers shall have Two Positions: Open or Disconnected and Closed. A separate and independent 3 Position Earthing Switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorised operations.
[a] Acquiring Analog values from Multifunction Transducers or alternatively through Transducer – less modules and the status inputs of devices from the substation, processing and transmitting to Master stations. Capability to acquire analog inputs from analog input cards receiving standard signals viz. Current Loops 4 – 20 mA, etc. [b] Receiving and processing Digital Commands from the Master Station[s] [c] Data transmission rates – 300 to 19200 BPS for Serial ports for MODBUS and 10/100 MBPS for TCP/IP Ethernet Ports [d] Use of IEC 60870-5-104 Protocol to communicate with the Master Station[s] [e] Use of MODBUS over RS485 interface, Protocol to communicate with the MFTs, Protection Relay. [f] Have required number of Communication Ports for simultaneous communication with Master Station[s], MFTs. [g] FRTU shall have the capability of Automatic Start-Up and initialisation following restoration of Power after an outage without need of manual intervention. All restarts shall be reported to the connected Master Stations.
[h] Remote Database downloading of FRTU from Master Station from SCADA/DMS Control Center. [i] Internal Battery Backup to hold Data in SOE Buffer Memory & also maintaining the Time & Date. [j] Communication with at least Four Master Stations simultaneously on IEC 60870-5-104 [k] RTU shall be capable of Acquiring Analog Values through Transducers having output as 4-20 mA, 0-10 mA, 0-+10 mA etc using Analog Input Modules. [l] FRTU shall have one TCP/IP Ethernet Port for communication with Master Station[s] using IEC 60870-5-104 Protocol. [m] FRTU shall have one Serial RS 485 Port for communication with MFTs and connected in daisy chain using MODBUS Protocol. Minimum 15 Analog Values [Including 4 Energy Values] shall be considered per energy meter.
[viii] Connection with adjacent modules shall be direct through busbar via metering bushing or through MV cables. VT’s and CT’s from the manufacturer conforming to IEC61869-3 and IEC 61869-2 respectively shall be accepted.
Note:[a] The make of Vacuum Interrupter, FRTU offered shall be of the same make as of the Ring Main unit. [b] An operator situated in front, lateral and rear [A-FLR 21kA–1Sec, Downwards Exhaust, for Tank as well as Cable Compartment of the RMU Switchboard during an internal fault shall not be exposed to the effects of Arcing. Internal Arc Type Test Report for IAC AFLR 21 kA for 1 Sec for both Tank & Cable Box shall be for minimum 3 Way/3 Function RMU. [c] All operations shall be from front of the RMU, including access to cable bushings. Bushings along the sides or the rear of the RMU are not acceptable. [d] Construction of Plinth / Foundation for 11KV RMU: The rate quoted is deemed to be including the cost of Plinth / Foundation and shall be paid extra on this account. The foundation shall consists of Two Parallel Brick Walls built using Fly Ash bricks straight or curved on plan to any radius built in CM1:6 of length 2.10m, suitable thickness and height as per the manufacturer’s instructions over PCC Concrete Bed of 150mm thick in PCC 1:4:8, Type D-2, using 40mm graded stone aggregate over 150mm thick Hardcore of gauge not exceeding 63mm of broken stones or boulders, deposited, spread and levelled in layers not exceeding 15 cm thick watered and rolled, over 150mm thick Sand Bed, rendering to brick surfaces, 15 mm thick in CM 1:4, and finishing the top surface even and smooth without using extra cement, applying Three coats of white washing including earthwork excavation of pit size 2.10 X 1.20 X 0.60 Metres complete all as per manufacturer’s recommendations, drawings, as specified and as directed.
[e] The rate quoted is also deemed to be including the cost of disconnection of HT Cables up to 3 Core, 240 Sq.mm from existing 2 Pole / 4 Pole Structures, removing of cable loop and reconnection to RMU complete all as specified and as directed by the Engineer-in-Charge. [f] End termination joints shall be measured and paid separately.
Supply and fix in repair cable joint kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete.
Supply, laying testing and commissioning of XLPE cable insulaed screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 185sqmm
Excavation in trenches not exeeading 1.5m wide and not exceeding 1.5m depth and getting out Hard/dense soil and dense soll for laying of under ground cable all as specified and directed by Engineer - in - Charge.
Excavation in trenches not exeeading 1.5m wide and not exceeding 1.5m depth and getting out Soft / loose soil and dense soll for laying of under ground cable all as specified and directed by Engineer - in - Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm in any type of soil complete all as specified.
Removing excavated material to a distance not exc 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified.
M & L for natural river sand as cushioning of cables, including spreading and punning down complete all as specified. Note : punned thickness (minimum 18 cm) shall be measured for the purpose of payment.
Supply and lay pre-cast concrete cable covers class HV type -1, flat shaped size 300mm x 180 x 40mm, laid in trenches as cable protection complete as spceified.
S&F Galvanised Iron pipe 80 mm bore (light grade) including fittings laid in road cutting as cable protection complete all as specified.
M&L Earthing complete with Copper earth plate electrode 600x600x3.15mm thick, buried directly and preferably vertically in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to 20x3mm copper strip as earth lead (upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of all as shown in electrical plate No 5, connected to earthing with DBs all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber & RCC 1:2:4 type B1 cover 40mm thick, with 8mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 20mm dia GI medium grade pipe for watering , water funnel complete all as specified and testing on completion.
AARAV POWER CONTROLS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .