Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.8 LAccepted-AOC DOOR NO 32 939C 1ST FLOOR CITY SCAPE BUILDING CHANGAMPUZHA NAGAR P O SOUTH KALAMASSERY ERNAKULAM KERALA 682033 | ERNAKULAM | KERALA | 682033 | ₹11.8 L Quoted ₹10.0 L | L1 | Accepted-AOC First Lowest quoted rate |
| 2 | L2₹10.5 L+₹46,563.06 (4.66%)Rejected-AOC | ₹10.5 L+₹46,563.06 (4.66%) | L2 | Rejected-AOC Second lowest rate |
| 3 | Rejected-Technical | - | - | Rejected-Technical Technical qualification not complied |
| 4 | Rejected-Technical | - | - | Rejected-Technical Technical qualification not complied |
| 5 | Rejected-Technical | - | - | Rejected-Technical Technical qualification not complied |
Tender Value
₹10.7 L
EMD Value
₹27,000
Closing Date
22 Dec 2025, 5:00 pmClosed
Assistant Executive Engineer
Generation Subdivision,Panniar,Vellathooval
Providing fire suppression system for the Generators of Panniar Power Station
2025_KSEB_821742_1
07/AEE/PGSD/25-26/10.12.25
Open Tender
Electrical Works
Percentage
30 days
Panniar Power House
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,950
Yes
₹27,000
30 Apr 2026
11 Dec 2025
24 Dec 2025
11 Dec 2025
22 Dec 2025
11 Dec 2025
Refilling of Co2 gas in Master Cylinder & Slave cylinders (8 Nos) if necessary.
Modification and re-erection of Cylinder bank assembly suaitable for hanging weight monitoring mechanism
Checking & servicing of Online Monitor
Checking & servicing of Non Return Valve
Checking & servicing of Pressure Switch
Checking & servicing of existing probe type heat detectors with heat blower. The service incldue ensuring the funcitonality test and collecting data in the presence of enigneer in charge
Checking & servicng of Hooter cum strobe. The rate including replacing of minor spares, speaker etc
Loop checking, continuity checking of existing cable inclduing checking of meggar value in the presence of enigneer in charge
General servicing, checking of entire existing system nozzles, accessories including schedule 40 pipe and accessories
Master Co2 Valve Supply and Installation of 24V DC 200 bar, Solenoid and Manual Lever fitted for automatic/manual operation type Valve for Master & slave cylinders (If necessary)
Online Weight Monitor Supply and Installation of Online Monitor (hanging type) with Normal indication Analog LED type - 4 wire input (If necessary)
Discharge Hose Supply installation, testing & commissioning of High pressure discharge hose-suitable size for all cylinder etc as required.
Pilot Hose Supply installation, testing & commissioning of High Pressure actuation hose suitable size for all cylinders
Non Return Valve Supply installation, testing & commissioning of Non Return Valve for Master & Slave cylinders (If necessary)
Bleeder Valve Supply and Installation of Bleeder Valve Gun Metal/SS
SafetyValve Supply & erection of Safety Valve
Lockout Valve Supply & erection of high Pressure Lockout valve with limit switch
HeatDetector (Probe type) Supply, installation, testing & commissioning of probe type heat Detectors 150 degree with mounting base (If necessary)
Hooter cum Strobe Supply and Installation of Dual tone Hooter with strobe light 24V DC(if necessary)
Cable Supply, installation, testing & commissioning of 2C x 1.5 sqmm FRLS Copper armoured cable
Gas Release Panel Supply & erection of Gas release panel 4 Zone UL listed having Battery backup with built in charging and LCD display and Gas Inhibit and Instant release facility Manual Gas Release with timer. Suitable for intial and extended discharge, Actuator pressure low sensing facility
Abort Switch Supply and Installation of Abort switch (2 Nos at Control room & 2 Nos nearby machine)
Manual Release Switch Supply of Manual release switch to manually activate the Gas release.
Test Valve Supply & erection of Test Valve 1" for dump testing without discharging Co2 in generator area . The Valve shall be with SS body PN 100 provide with three way mechanism Test/Close/Open
Auto Dialer Supply & fixng of Emergency Security PSN+GSM based Auto Dialer for voice call/SMS to pre-defined number in the case of emergency
Sign Boards Supply and Installation of LED type with 3 hr battery back-up Warning Sign Board having size 29Cm x 13Cm as per requirement and as per standards
Spares Supply of minor spares for repalcing (Heat detectors)(if necessary)
Automatic Modular Gas Suppression system in the Battery room Supply & Installation Of Automatic hanging type FK-5-1-12/FM 200 Gas system with 15 Kg gas, solenoid valve, pressure gauge, nozzles & gas release panel etc
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.10 MB
Tendernotice_2.pdf
PDF • 0.82 MB
BOQ_1377408.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .