| 1.00 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C | 826 | Point | 1,520 ₹12,55,520 Lowest | 1,521 ₹12,56,346 |
| 2.00 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C | 422 | Point | 885 ₹3,73,470 Lowest | 886 ₹3,73,892 |
| 3.00 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. | 34 | Point | 1,615 ₹54,910 Lowest | 1,618 ₹55,012 |
| 4.00 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. | 7,875 | M | 330 ₹25,98,750 Lowest | 333 ₹26,22,375 |
| 5.00 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. | 9,165 | Metre | 285 ₹26,12,025 | 284 ₹26,02,860 Lowest |
| 6.00 | 2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire | 1,050 | Metre | 445 ₹4,67,250 | 440 ₹4,62,000 Lowest |
| 7.00 | 2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire | 120 | Metre | 530 ₹63,600 Lowest | 535 ₹64,200 |
| 8.00 | 4 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire | 1,760 | Metre | 840 ₹14,78,400 Lowest | 843 ₹14,83,680 |
| 9.00 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. | 581 | Each | 500 ₹2,90,500 Lowest | 505 ₹2,93,405 |
| 10.00 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. | 315 | Each | 620 ₹1,95,300 Lowest | 622 ₹1,95,930 |
Tender Value
₹3.7 Cr
EMD Value
₹7.4 L
Closing Date
17 Feb 2024, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
External and Internal Electrification work for 50 Bedded District Hospital, Someshwar Distt. Almora
2024_BRID3_68911_1
187/BRIDCUL/868/24 Dated 02/02/2024
Open Tender
Electrical Works
Item Rate
365 days
Someshwar Almora
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹7.4 L
BRIDCUL Dehradun
20 Feb 2024
3 Feb 2024
17 Feb 2024
3 Feb 2024
17 Feb 2024
11 Feb 2024
9 Feb 2024
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire.
2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire
2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire
4 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as Required. Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 6 Way (4 + 18), Double Door
8 Way (4 + 24), Double Door
Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 8 Way Double door.
12 way , Double door
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required. 40 Amps
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required. 40 Amps
Supplying and Fixing Following Size/ Modules, GI Box Alongwith Modular Base & Cover Plate for Modular Switches in Recess etc. as Required. 1 or 2 Module (75 mm x 75 mm)
Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required. Telephone Socket outlet.
TV Antenna socket outlet.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable
SITC Modular Type Computer jack RJ 45 ISI mark 1 Module on existing Mounting plate and box Complete.
SITC Modular Type Computer jack RJ 45 ISI mark 1 Module on existing Mounting plate and box Complete.
Supply of 36W (2x2) LED Light (surface) fitting suitable for 36Watt LED Light with all accessories as required.
Supply of 42W (2x2) LED Light (surface) fitting suitable for 42 Watt LED Light with all accessories as required.
Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT (Round/Square) complete with with all accessories as required.
Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT (Round) Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required. (Technical Data - System power 12W, CRI ≥80, Power Factor ≥0.95, System Luminous Efficacy ≥94).
Supply of Surface Mounted Energy Efficient, LED Luminaires 18W LED DOWN LIGHT (Round) complete with with all accessories as required.
Supply of Surface Mounted Energy Efficient, LED Luminaires 18W LED DOWN LIGHT (Round) Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required. (Technical Data - System power 18W, CRI ≥80, Power Factor ≥0.95, System Luminous Efficacy ≥90)
Supply, of Linear & Compact 10W Mirror Light with Decorative Grey Caps, Polycarbonate Body & Ribbed Opal Diffuser. (Technical Data - System power 10W, CRI ≥80, Power Factor ≥0.95, System Luminous Efficacy ≥100).
Supply of LED Luminaires BATTEN 40W 6500K LED Tube Light complete with with all accessories as required.
Supply of LED Luminaires BATTEN 20W LED Tube Light complete with with all accessories as required. As Per havells 20 Watt/2000 lumen 5700 KLED Tubelight havells
Supply of LED Luminaires BATTEN 40W LED Tube Light of Box Type Prewired Indoor Luminaire with Energy Efficient Electronic Ballast, with End Caps Complete as Required.(Technical Data - System power 40W, CRI ≥80, Power Factor ≥0.95, System Luminous Efficacy ≥100).
Supply of Bulk Head Luminaire, heat resistant Glass cover . suitable for 10W to 15W LED or Equivalent. (Technical Data - System power 10W, CRI ≥80, Power Factor ≥0.95, System Luminous Efficacy ≥80)
Supply of 10W Bulk Head Luminaire complete with with all accessories as required.
Supply of Following sweep exhaust fan with guard suitable operation on single phase 230 V, 50Hz. AC Supply, with lowers /shutters in the existing opening. As per propeller type ac ventilating fan-exhaust 300 mm Sweep 900 rpm
Supply & Installation of AC 230/250 volts, 50 HZ Wall Fan Including Providing Nuts, Bolts, & Other Accessories as Required. 400 mm Dia
Supply of Following sweep exhaust fan with guard suitable operation on single phase 230 V, 50Hz. AC Supply, with lowers / shutters in the existing opening. 300 mm Sweep 900 rpm
Supply & Installation of AC 230/250 volts, 50 HZ Wall Fan Including Providing Nuts, Bolts, & Other Accessories as Required. 450 mm Dia
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting /compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as Required.
Installation of Exhaust fan in the existing opening, including making good the damage, Connection, Testing, Commissioning etc. as Required.Upto 450 mm sweep
Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing
GROUND FLOOR PANEL:-Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 100 AMP FP MCCB, , BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 1 No 63 AMP 4P MCB (Light DB), 1 No 63 AMP 4P MCB (Power DB), 4 No 63 AMP 4P MCB (Spare)
FIRST FLOOR PANEL:-Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 160 AMP FP MCCB, BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature., OUT GOINGS : 1 No 63 AMP 4P MCB (Light DB 1), 1 No 63 AMP 4P MCB (Light DB 2), 1 No 63 AMP 4P MCB (Light DB 3), 1 No 63 AMP 4P MCB (Power DB 1), 1 No 63 AMP 4P MCB (Power DB 2), 1 No 63 AMP 4P MCB (Power DB 3), 4 No 63 AMP 4P MCB (Spare)
SECOND FLOOR PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid., INCOMER : 160 AMP FP MCCB, BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature., OUT GOINGS : 1 No 63 AMP 4P MCB (Light DB 1), 1 No 63 AMP 4P MCB (Light DB 2), 1 No 63 AMP 4P MCB (Light DB 3), 1 No 63 AMP 4P MCB (Power DB 1), 1 No 63 AMP 4P MCB (Power DB 2), 1 No 63 AMP 4P MCB (Power DB 3), 1 No 63 AMP 4P MCB (Power DB 4), 1 No 63 AMP 4P MCB (Power DB 5) 2 No 63 AMP 4P MCB (Spare)
THIRD FLOOR PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.INCOMER : 160 AMP FP MCCB, BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature., OUT GOINGS : 1 No 63 AMP 4P MCB (Light DB 1), 1 No 63 AMP 4P MCB (Light DB 2), 1 No 63 AMP 4P MCB (Light DB 3), 1 No 63 AMP 4P MCB (Power DB 1), 1 No 63 AMP 4P MCB (Power DB 2),, 1 No 63 AMP 4P MCB (Power DB 3), 1 No 63 AMP 4P MCB (Power DB 4), 1 No 63 AMP 4P MCB (Power DB 5), 2 No 63 AMP 4P MCB (Spare)
FOURTH FLOOR PANEL :- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. , INCOMER : 160 AMP FP MCCB, BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. , OUT GOINGS : 1 No 63 AMP 4P MCB (Light DB 1), 1 No 63 AMP 4P MCB (Light DB 2), 1 No 63 AMP 4P MCB (Power DB 1), 1 No 63 AMP 4P MCB (Power DB 2), 4 No 63 AMP 4P MCB (Spare)
UPS INPUT PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid., INCOMER : 200 AMP FP MCCB, BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature., OUT GOINGS : 1 No 125 AMP 4P MCCB (UPS Output panel supply 1), 1 No 125 AMP 4P MCCB (UPS Output panel supply 2) , 1 No 125 AMP 4P MCCB (Spare)
UPS OUTPUT PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER 1 : 125 AMP FP MCCB (Thru Bypass Switch 60 kva UPS) Including UPS ByPass Switch, INCOMER 2 : 125 AMP FP MCCB (Thru Bypass Switch 60 kva UPS) Including UPS ByPass Switch, BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature., OUT GOINGS : 1 No 40 AMP DP MCB (Ground Floor EMG Light DB), 1 No 100 AMP 4P MCCB (First Floor UPS Panel) 1 No 100 AMP 4P MCCB (Second Floor UPS Panel) 1 No 100 AMP 4P MCCB (Third Floor UPS Panel) 1 No 100 AMP 4P MCCB (Fourth Floor UPS Panel), 2 No 100 AMP 4P MCCB (Spare), 1 No 63 AMP 4P MCB (Spare), 1 No 40 AMP DP MCB (Spare)
FIRST FLOOR UPS PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER 1 : 100 AMP FP MCCB , BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 1 No 63 AMP 4P MCB (UPS DB 1), 1 No 63 AMP 4P MCB (UPS DB 2), 1 No 40 AMP DP MCB (UPS DB 3) , 1 No 40 AMP DP MCB (EMG Light DB 1) , 1 No 40 AMP DP MCB (EMG Light DB 2), 1 No 40 AMP DP MCB (EMG Light DB 3), 2 No 63 AMP 4P MCB (Spare) , 2 No 40 AMP DP MCB (Spare)
SECOND FLOOR UPS PANEL :- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. , INCOMER 1 : 100 AMP FP MCCB, BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 1 No 63 AMP 4P MCB (UPS DB 1), 1 No 63 AMP 4P MCB (UPS DB 2), 1 No 63 AMP 4P MCB (UPS DB 3) , 1 No 63 AMP 4P MCB (UPS DB 4), 1 No 63 AMP 4P MCB (UPS DB 5), 1 No 40 AMP DP MCB (EMG Light DB 1), 1 No 40 AMP DP MCB (EMG Light DB 2), 1 No 40 AMP DP MCB (EMG Light DB 3), 1 No 63 AMP 4P MCB (Spare), 1 No 40 AMP DP MCB (Spare)
THIRD FLOOR UPS PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid., INCOMER 1 : 100 AMP FP MCCB, BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature., OUT GOINGS : 1 No 63 AMP 4P MCB (UPS DB 1), 1 No 63 AMP 4P MCB (UPS DB 2), 1 No 63 AMP 4P MCB (UPS DB 3), 1 No 63 AMP 4P MCB (UPS DB 4), 1 No 63 AMP 4P MCB (UPS DB 5) 1 No 40 AMP DP MCB (EMG Light DB 1) , 1 No 40 AMP DP MCB (EMG Light DB 2), 1 No 40 AMP DP MCB (EMG Light DB 3), 1 No 63 AMP 4P MCB (Spare) , 1 No 40 AMP DP MCB (Spare)
FOURTH FLOOR UPS PANEL:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid., INCOMER 1 : 100 AMP FP MCCB, BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp., The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 1 No 63 AMP 4P MCB (UPS DB 1), 1 No 63 AMP 4P MCB (UPS DB 2), 1 No 40 AMP DP MCB (EMG Light DB 1), 1 No 40 AMP DP MCB (EMG Light DB 2), 1 No 63 AMP 4P MCB (OT Room), 2 No 63 AMP 4P MCB (Spare), 1 No 40 AMP DP MCB (Spare)
G/F PANEL Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 100 AMP FP MCCB BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 5 No 63 AMP 4P MCB
UPS PANEL Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.INCOMER 1 : 100 AMP FP MCCB , BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 2 No 63 AMP 4P MCB , 2 No 40 AMP DP MCB
LIFT PANEL :- Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 1 Nos 125 AMP FP MCCB, BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature OUT GOINGS : 1 No 63 AMP 4P MCB (LIFT 1), 1 No 63 AMP 4P MCB (LIFT 2) ,1 No 63 AMP 4P MCB (Machine Room DB), 2 No 63 AMP 4P MCB (SPARE)
ISOLATOR PANEL FOR OT & CENTRAL LAB: & Emergency -Design, manufacture, supply, installation, testing and commissioning of Isolator panel - Incomer cum Outgoing : 1 Nos 63 AMP FP MCB fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
ISOLATOR PANEL FOR FIRST FLOOR:- Design, manufacture, supply, installation, testing and commissioning of Isolator panel - Incomer cum Outgoing : 1 Nos 100 AMP FP MCCB fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INTERLOCKING Interlocking logic electrical Interlocking between incomers and bus coupler and it should have auto start and auto trip facility for Automatic Operation of The Breakers WITH MANUAL OVER RID FACILITY
BUS COUPLER One Number 1000A 50KA 4 pole ACB as Bus Coupler with ON/OFF Indication.
BUS BAR 1250 A TPN Aluminium bus bar with heat Shrink Sleeve
OUTGOINGs ALL THE MCCB'S SHALL BE EQUIPPED/ PROVIDED WITH ALL ACCESSORIES & IN BUILT PROTECTION RELEASES
1 Nos. 400 AMPS TP MCCB (Capacitor Panel)
1 No. 400A 50KA 4P MCCB (SPARE)
1 No. 200A 50KA 4P MCCB (SPARE)
2 No. 160A 50KA 4P MCCB (SPARE)
1 No. 125A 50KA 4P MCCB (SPARE)
1 No. 100A 50KA 4P MCCB (SPARE)
Other items such as 1 set of control wiring, 1 Set of designation plates
NOTE :- Adequate Quantity of Fire Suppression system with Pneumatic gas cylinder and Heat Sensitive Pneumatic tubing to be used in panel as per the current fire norms & SURGE PROTECTION DEVICES Type 1 ( Class B), 4 Mode, spar type suitable for 10/350µs surge, 3Nos. phase to earth and 1Nos. neutral to earth with impulse Current Iimp. ≥ 50KA Per mode & In ≥ 25kA per Mode.
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required. 3.5 C X 300 Sq.mm Al. XLPE arm.
3.5 C X 185 Sq.mm Al. XLPE arm.
3.5 C X 150 Sq.mm Al. XLPE arm.
3.5 C X 120 Sq.mm Al. XLPE arm.
3.5 C X 95 Sq.mm Al. XLPE arm.
3.5 C X 70 Sq.mm Al. XLPE arm.
3.5 C X 50 Sq.mm Al. XLPE arm.
3.5 C X 35 Sq.mm Al. XLPE arm.
3.5 C X 25 Sq.mm Al. XLPE arm.
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required. 3½ X 25 sq. mm (28mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 70 sq. mm (38mm)
3½ X 95 sq. mm (45mm)
3½ X 120 sq. mm (45mm)
3½ X 150 sq. mm (50mm)
3½ X 185 sq. mm (57mm)
3½ X 300 sq. mm (70mm)
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
SITC of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board with supply of all material labour T & P etc for proper completion of work. (Approx front area = 1.20 sq M)
SITC of First aid box as approved by Indian red cross conforming to IS : 2217.
SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked.
SITC of ABC FIRE EXTINGUISHER 4 KG capacity complete in all respect ISI : 15683 marked.
SITC of Fire Bucket stand made of M S angle suitable for and with 4 Nos Fire Buckets of 9.5 Ltrs capacity.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Providing and laying 1.6 mm thick pregalvanized GI factory fabricated raceways of the following sizes including 2 mm thick GI covers, providing knock out holes and all required fixing accessories including 6 SWG GI earth wire complete as required including floor /wall supports, bends, access boxes and tap off boxes as per specification and cross over as per site requirement. Note:- Blue & Orange colour shall be considered for Power & Data raceway respectively. The item shall include the cost of chipping, cutting the floor for laying the raceway and making good the finish including chicken mesh complete as required as per site requirement. 50x40x15x1.6mm & Cover 2mm
100x40x15x1.6mm & Cover 2mm
200x40x15x1.6mm & Cover 2mm
300x40x15x1.6mm & Cover 2mm
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement) 150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
600 mm width X 50 mm depth X 2.0 mm thickness
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.Above 4.5 metre and upto 6.5 metre
Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape , Hole Seeling to be done complete as required.32 mm dia
Supply , Installation, Testing & Commissioning of Integrated Post Top Lantern With 30W LED Lamp including Pole & connection with 3 x 2.5 sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required.
Supply , Installation, Testing & Commissioning of 50 W LED with complete with pot optic reflector connection with 3x2.5sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required
Supply, Installation, Testing and Commissioning of 200x160x70 Polycarbonate thermoplastics enclosure - junction box with I.P - 66 Protection
Supplying of ADP Octagonal Pole Single Arm 6 m ADP, Material of Octagonal pole : Grade ISH430LA as perIS:5986:2017 latest, Base plate material : Grade: E250, Quality:BR(as per IS:2062:2011 latest)
Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing laid in ground including cost of digging upto required depth, 150 mm sand all around the cable, brick protection and back filling, clamped to wall with suitable clamps including saddles fixing bolts, Connection Testing and commissioning as Required. 2x6 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering.Upto 35 sq. mm
Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing trenches/pipes, cable trays, ducts, clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning as Required. 2x6 sqmm
Supply & Fixing of 2.0 ton split AC hot/Cold type with necessary Accessoires, Cu-piping etc. complete in all respect.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 core 2.5 sq.mm (for 6 Mtr Poles)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
Suppling, installation testing & commissioning of 20 kw grid interactive roof top solar photo voltaic power generation system including space frame conforming to MNRE specifications as amended, consisting of Mono/PolyCrystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:-a)Solar Photovoltaic Module of capacity 330Wpor above, manufactured in India, conforming to IS14286/IEC61215, IS/IEC61730-Part-1, IS/IEC61730-Part-2.Solar Photovoltaic Module conversion efficiency shall not be lessthan 16.5%. PV module used in solar power plants/systems must be warranted for their output peak watt capacity, which should not be lessthan 90% at the end of 10years and 80% at the end of 25 years. b)Power Conditioning Unit (PCU) of350-800V DC Input voltage range and 400V AC, three phase, 4wire, 50Hz+/-2.5Hz, out put voltage suitable to generate AC Power with efficiency not lessthan 97%, total harmonic distortion lessthan 3% and suitable for ambient temperature from 0to50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d)Fixing of Array junction box & Main junction box with IP65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f)Connections & Inter connections by supplying & fixing required size XLPE insulated copper conductor 1.1kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required.
SITC of 60 KVA /54 KW High Performance IGBT / PWM based True Online Double Conversion Fully Microprocessor Controlled DSP based UPS System. UPS System consisting of 100% Capacity Static IGBT / PWM Inverter 100% Capacity Thyristor Based Rectifier Active Output Power @ 0.9 Inbuilt Standard 1:1 Galvanic Isolation Transformer. 100% Capacity Static Bypass Switch. 100% Capacity Manual Maintenance Bypass (Service Bypass) Online Mode Efficiency up to 93% ECO Mode Efficiency up to 98% Wide Input Voltage and Frequency Tolerance. Inbuilt Standard Potential Free Contacts. Parallel Feature Inbuilt Standard Programmable Battery Test and Battery Management Software. Inbuilt LCD Display for Fault Diagnostic. Input Reverse Phase Sequence Protection Circuitry. SMF(12V) VRLA Batteries for 30mins back up on 60KVA UPS Running load. Complete with Battery Rack, Interlinks, DC Cable (upto 10 Mtrs.) and Battery Circuit Breaker (BCB).
SITC of 10 KVA High Performance IGBT / PWM based True Online Double Conversion Fully Microprocessor Controlled DSP based UPS System. UPS System consisting of 100% Capacity Static IGBT / PWM Inverter 100% Capacity Thyristor Based Rectifier Active Output Power @ 0.9 Inbuilt Standard 1:1 Galvanic Isolation Transformer. 100% Capacity Static Bypass Switch. 100% Capacity Manual Maintenance Bypass (Service Bypass) Online Mode Efficiency up to 93% ECO Mode Efficiency up to 98% Wide Input Voltage and Frequency Tolerance. Inbuilt Standard Potential Free Contacts. Parallel Feature Inbuilt Standard Programmable Battery Test and Battery Management Software. Inbuilt LCD Display for Fault Diagnostic. Input Reverse Phase Sequence Protection Circuitry. SMF(12V) VRLA Batteries for 30 mins back up on 10KVA UPS Running load. Complete with Battery Rack, Interlinks, DC Cable (upto 10 Mtrs.) and Battery Circuit Breaker (BCB).
Supplying, installation, testing and commissioning of 33kV/0.433kV or 11kV/0.433 kV substation equipments comprising HT Panel, Dry typetype Transformers, HT cable, Bus trunking from Transformer to LT Panel, LT Panel, Automatic Power factor correction panel, Active Harmonic Filters, TVSS (Transient Voltage suppression system),SPD (Surge protection system), Essential panel, Earthing, required inter-connections,substation safety equipments including LT cabling from sub station to the buildings fed by the sub station.
The 11kV Outdoor Package Sub-Station as per IEC:62271-202 shall be consisting of following
HT Switchgear as per IEC 62271-200
11kV, 630A, 21kA for 3sec SF6 insulated non-extensible Ring Main Unit consisting of 1Nos. Load Break Switch & 1No. Fixed manual Vacuum Circuit Breaker in SF6 insulated enclosure, self-powered microprocessor based numerical over current relay. 1No.
Transformer
11/0.415 KV 500 KVA Dry type TRANSFORMER, OFFLOAD Tap changer OCTC.:- 1No.
Low Voltage Panel (TTA/DVA) as per IEC 61439 1-2
Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439- 1 &2 as DVA from OEM Authorized Partners and of suitable size fabricated in compartmentalized design with CRCA sheet steel of 1.6mm thickness. Complete with 7 tank process, powder coating in the approved shade, the Panel shall be suitable for Internal Arc Test 85kA for 300mS as per IEC61641 and Seismic Zone-V tested, Form of Separation Form 3b, Mechanical Impact IK10 as per IEC. The board shall be dust and vermin-proof with a degree of protection IP 54 :- 1 No.
Incomer from Transformer: 1000 A,415/440 V, 4P,50 Hz,ICS=ICU=ICW=50KA 1 sec, MDO Air Circuit Breaker with microprocessor-based release for LSING protection with Accessories and Multifunction meter as incomer and outgoing breaker for the main LT panel. :-01 No.+ 01 spare
Outdoor Enclosure
Outdoor type enclosure having construction of Galvanised Sheet Steel of thickness 3mm load bearing and 2 mm other members. The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23D degree of protection for transformer compartment. The Enclosure exterior shall be Powder coated . Each compartment will be provided with the door and pad locking arrangement. Roof of CSS should be slant to avoid water logging. 1 Set complete as require
Supply & Testing of following 11 KV( UE) grade multicore Aluminium conductor XLPE insulated cable, insulation screening with extruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required. 3 C x 240 Sq. mm 11 KV (UE)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
Supply and making Indoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required. 3 C x 240 Sq.mm
Supply and making Outdoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required. 3 C x 240 Sq.mm
Supply and Making Straight Through Cable Jointing With Cast Resin Compund, Including Ferrule & Other Jointing Materials for Following Size of 3 core, XLPE Aluminium conductor cable of 11KV grade as required. 3 C x 240 Sq.mm
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single Red colour on front side as required.
SITC of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board with supply of all material labour T & P etc for proper completion of work. (Approx front area = 1.20 sq M)
SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked
SITC of ABC FIRE EXTINGUISHER 4 KG capacity complete in all respect ISI : 15683 marked
SITC of Fire Bucket stand made of M S angle suitable for and with 4 Nos Fire Buckets of 9.5 Ltrs capacity
SITC of of rubber gloves of 11 KV grade as per IS : 4770.
SITC of cable route marker
SITC of ANTI SKID RUBBER MAT 1 mtr x 2 mtr. 3mm thick ISI - 15652 marked
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 300 mm dia
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 200 mm dia (OD-200 mm & ID-175 mm nominal)
DIESEL GENERATOR SET - 200 KVA DG SET :-
Supply, intastallation, Testing & Commissioning of 200 KVA Capacity Radiator cooled DG Set with Suitable Standard AMF Panel & suitable capacity engine directly coupled with alternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosure for the DG SET (75 db @ 1m) , including supply, fixing of antivibration pads suitable for 200 KVA DG Set as per standards of Engine manufacture, provision of conrol cable from engine to control panel to engine. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge.
Diesel Engine (CPCB-2 NORMS COMPLANT) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 160 KW Having Following Arrangement :-
Flywheel With Starter Ring for Generating Set
Air Filter , Lube Oil Cooler Assembly with Accessories.
Exhaust Air Manifold
Exhaust Bellow
Fuel Fiter
Diesel engine pre heating arrangement
Lube Oil Filter
Exhaust Gas Turbo Charger with After Coller
Day Tank For fuel with Markings
ECP Panel mounted on a Separate Frame.
Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump
12V Electrical Starting System with Starter Motor and Battery Charging Alternator
Engine Mounting Supports
ALTERNATOR Rated at 200 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification
Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.
Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).
Excitation: Self Excited - Self Regulated.
Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.
Vibration: Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.
Enclosure: Screen protected drip proof enclosure with IP – 23 degree of protection.
Cooling: Air Cooled type with radial fan mounted on Rotor.
Winding and Insulation: Insulation class H as defined in IEC – 60034-1
ACCESSORIES :-
MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.
Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.
Residential Silencer (1.5 Meter with 750 mm dia Approx) Including Insulation of Silencer.
2 Nos 12 Volts DC Battery of SUITABLE Capacity with Leads.
1 Set of AVM Pads Fitted in Base Frame.
DIESEL GENERATOR SET - 160 KVA DG SET :-
Supply, intastallation, Testing & Commissioning of 160 KVA Capacity Radiator cooled DG Set with Suitable Standard AMF Panel & suitable capacity engine directly coupled with alternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosure for the DG SET (75 db @ 1m) , including supply, fixing of antivibration pads suitable for 160 KVA DG Set as per standards of Engine manufacture, provision of conrol cable from engine to control panel to engine. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engine to fuel tank complete gate valve and fitting leader maker etc. Supply , Intallation of starting batteries of suitable AH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge.
Diesel Engine (CPCB-2 NORMS COMPLANT) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 128 KW Having Following Arrangement :-
Flywheel With Starter Ring for Generating Set
Air Filter , Lube Oil Cooler Assembly with Accessories.
Exhaust Air Manifold
Exhaust Bellow
Fuel Fiter
Diesel engine pre heating arrangement
Lube Oil Filter
Exhaust Gas Turbo Charger with After Coller
Day Tank For fuel with Markings
ECP Panel mounted on a Separate Frame.
Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump
12V Electrical Starting System with Starter Motor and Battery Charging Alternator
Engine Mounting Supports
ALTERNATOR Rated at 160 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification
Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.
Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).
Excitation: Self Excited - Self Regulated.
Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.
Vibration : Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.
Enclosure : Screen protected drip proof enclosure with IP – 23 degree of protection.
Cooling: Air Cooled type with radial fan mounted on Rotor.
Winding and Insulation: Insulation class H as defined in IEC – 60034-1
ACCESSORIES :-
MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.
Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.
Residential Silencer (1.5 Meter with 750 mm dia Approx) Including Insulation of Silencer.
2 Nos 12 Volts DC Battery of Suitable Capacity with Leads.
1 Set of AVM Pads Fitted in Base Frame.
Shubham Traders
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.46 MB
sbdinternalexternalf.pdf
Tender Documents • 1.74 MB
BOQ_82856.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .