EE Electrical Division HPPWD Mandi
EE Electrical Division HPPWD Mandi
Providing electrical installation of lift and passage at Mini Secretariat building at Sunder Nagar, Distt. Mandi.HP.
2026_PWD_134078_1
No.PW-MED-TA-Tender/2025-26- 8086-99 Dated- 31.03.2026
Open Tender
Electrical Works
Percentage
180 days
Sunder Nagar, Distt- Mandi
As per SBD
13 documents required · 13 mandatory
₹350
₹2,950
20 Apr 2026
12 Apr 2026
20 Apr 2026
13 Apr 2026
18 Apr 2026
13 Apr 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge. i) Group C -Make:- Havells,Finolex,RR Kable,KEI, Grandley,Plaza,SSK
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge. Make:- Havells (REO) (Athena), Goldmedal(Air)(GIFa),Anchor(Penta),Legrand (arteor), L&T(Entice), SSK
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required complete in all respects and to the best satisfaction of Engineer-in-charge. i) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Make;- Make:- Havells,Finolex,RR Kable, KEI, Grandley, Plaza, SSK
Wiring for Circuit/Submain Wiring with 4X1.5 sq. mm FRLSH PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 2 Nos 1.5 sq. Mm (4x1.5 Sq.mm +2x1.5 Sq.mm) FRLSH PVC insulated copper conductor single core cable for loop earthing as required complete in all respects and to the best satisfaction of Engineer-in-charge. Make:- Havells, Finolex, RR Kable, KEI, Grandley, Plaza, SSK
Providing and installation of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.as required complete in all respects and to the best satisfaction of Engineer-in-charge. Make:- bajaj,havells,panasonic,Philips,Wipro,LT,Changi
Wattage of LED fittings- As per following parameters
Total lumens of the LED fittings- Minimum 800 lumen
Diffuser-polycarbonate diffuser/PMMA
Operating voltage-140V to 270V, AC supply
Input frequency-50 Hz + 1 Hz
Power factor-Minimum 0.90
Luminaire efficacy->80 lm/w
Color rendering index-CRI shall be greater than 80
Working/ operating temperature-0 to + 45c or better
Color temperature-6000K to 10%
Electronic Driver
Drive current (LED)-As per OEM.
Operating voltage-140 V to 270 V AC supply or better
Type of driver-Constant current output driver
THD-Less than 10%
Surge Protection-2 KV minimum
Efficiency Driver->85%
Protection-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver-2 years against manufacturing defect.
Fixture-Should comply with LM 79 test from NABL/UL lab.
LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED-50000 burning hours at 70% lumen maintenance
LED Bulk head > 1600 Lumens 20 watt
Providing and installation of following type of LED Batten with aluminium housing ,anti glare polycarbonate diffuser, complete with all accessories, connections, testing etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge. Make bajaj, havells, panasonic, Philips,Wipro,LT,Changi
Wattage of LED fittings- As per following parameters
Diffuser-polycarbonate diffuser/PMMA
Operating voltage-140V to 270V, AC supply
Input frequency-50 Hz + 1 Hz
Power factor-Minimum 0.90
Luminaire efficacy->100 lm/w
Color rendering index-CRI shall be greater than 80
Working/ operating temperature-0 to + 45c or better
Color temperature-6000K to 10%
Electronic Driver
Drive current (LED)-As per OEM.
Type of driver-Constant current output driver
THD-Less than 10%
Surge Protection-2.5 KV minimum
Efficiency Driver->85%
Protection-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver-2 years against manufacturing defect.
Fixture-Should comply with LM 79 test from NABL/UL lab.
LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED-25000 burning hours at 70% lumen maintenance
LED Batten Light >2000 Lumens.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge. i) Single pole. Cat-A. make:- Havells,ABB,Legrand,L&T,schneider,C&S, SSK
Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge. i) MCB DP 40 Amp Make:-Havells,ABB,Legrand,L&T,schneider,C&S, SSK
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge. (But without MCB/RCCB/Isolator) Approved Make :-Havells,ABB,Legrand,L&T,schneider,C&S, SSK
6 way , Double door
4 way , Double door
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surfaceas required complete in all respects and to the best satisfaction of Engineer-in-charge. i) Armoured cable 25 sq. mm (3.5 core) Make Universal Cables, Havells,Grandlay & Kei.
Supplying & Erection of following MCCB 4 Pole 415 Volt with Thermal Magnetic Release for overload and short circuit protection breaking Capacity (Ics=100% Icu with positive isolation) with Spreader links etc complete in all respcets as per the satisfaction of Engineer-in-charge.Make :-Havells,ABB, Legrand, L&T,schneider,C&S, SSK
MCCB 40- 100 Amp. 36 ka 4 Pole Release without rotary handle
Providing and fixing SS Enclosure for DU/DH MCCBs suitable for 4-Pole MCCBs etc. as required. Make: L&T, Schneider, Siemens, ABB, C&S, or any other equivalent make approved by Engineer-in- Charge: i) Enclosure for MCCB Make :-Havells,ABB, Legrand, L&T,schneider,C&S, SSK
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required complete in all respects and to the best satisfaction of Engineer-in-charge. i) 150 mm width X 50 mm depth X 1.6 mm thickness
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required complete in all respects and to the best satisfaction of Engineer-in-charge.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required complete in all respects and to the best satisfaction of Engineer-in-charge.
Supplying and fixing of Residual Current Breaker with Overcurrent Protection Conforming to IEC 61009-1, IS 12640-2, EN 61009-1 with precise sensitivity and suitable for isolation with all connections required and complete in all respects as per satisfaction of Engineer-in-charge. i) RCBO 4 Pole 40 Amp 300mA Make :-Havells,ABB,Legrand,L&T,schneider,C&S, SSK
stage.html
html • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.23 MB
SBD_Mini_Sec_SNR.pdf
Tender Documents • 4.12 MB
BOQ_198277.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .