Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.3 LAccepted-AOC | L1 | Accepted-AOC Being Lowest Bidder | |
| 2 | L 2₹15.9 L+₹21,857 (1.39%)Rejected-Finance | L 2 | Rejected-Finance Higher Side | |
| 3 | L3₹16.2 L+₹51,567 (3.28%)Rejected-Finance | L3 | Rejected-Finance Higher Side | |
| 4 | L4₹19.5 L+₹3.7 L (23.7%)Rejected-Finance NEAR SHIV SHAKTI DHARAM KANTA SHIV PURAM FULSUNGA RUDRAPUR U S NAGAR UTTARAKHAND | UDAM SINGH NAGAR | UTTARAKHAND | 244712 | L4 | Rejected-Finance Higher Side |
Tender Value
₹22.5 L
EMD Value
₹45,000
Closing Date
26 May 2020, 6:00 pmClosed
GE Pithoragarh
GE Pithoragarh Post Bharkatia Pithoragarh ( UK)PIN-262520
REPAIR / REPLACEMENT OF OLD US INTERNAL ELECTRIC WIRING, TUBE LIGHT FITTING AND BLDG SECURITY LIGHT FITTING, EARTHING SWITCH SOCKET AT 7E AREA (OTM AND MD ACCN) UNDER AT GE PITHORAGARH
2020_MES_341861_1
8291/PGH/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Pithoragarh
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE Pithoragarh
₹45,000
Yes
23 Jun 2020
30 Apr 2020
28 May 2020
30 Apr 2020
26 May 2020
14 May 2020
30 Apr 2020 - 14 May 2020
Amount
DESCRIPTION OF ITEMS
Taking down carefully old us point wiring (Light fan socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators, sockets etc), removing materials from site and making good disturbed surface of walls, floors etc, complete all as specified and directed.
M & L for point wiring surface type with 1.5 Sqmm, single core (FRLS), PVC insulated with multistranded unsheathed copper conductor cable including rigid non metallic PVC surface conduit 20 mm or higher dia, ISI marked complete with all PVC conduit accessories / fittings and sunk switch boxes with 3 mm thick plastic laminated hard glossy surface sheet (white) top cover, including continuous earth wire of PVC insulated, unsheathed, 1.5 Sqmm multistrand copper conductor (FRLS) connected to all fittings, sunken boxes and common earth and connected to earth dolly , screwed with screws, cup washers complete all as specified and directed for the following :-
(a) One light point/ fan/ exhaust fan point/bell point controlled by one, one way switch of 5/6 Amps.
(b)one socket outlet three pin 5 amps control by one switch on the same board
(c)one socket outlet three pin 5 amps control by one switch on independent board
(d) One light point controlled by two, two way switch of 5/6 amps
All as per Item No 3 above but with 2.5 Sq mm cable (FRLS) for one 15 Amp socket outlet controlled by one switch on independent board and 2.5 Sqmm PVC insulated unsheathed multi stranded copper conductor cable as continuous earth wire complete.
M & L for point wiring concealed type with 1.5 Sqmm, single core (FRLS), PVC insulated with multistranded unsheathed copper conductor cable including rigid non- metallic exhusting PVC concealed conduit 20 mm or higher dia, heavy grade ISI marked complete with all PVC conduit accessories / fittings and sunk switch boxes with 3 mm thick plastic laminated hard glossy surface sheet (white) top cover, including continuous earth wire of PVC insulated, unsheathed, 1.5 Sqmm multistrand copper conductor (FRLS) connected to all fittings, sunken boxes and common earth and connected to earth dolly ,screwed, cup washers complete all as specified and directed for the following :- Note: Cost of cutting chasing and making good of surface shall be deemed included in quoted unit rate.
(a) One light point/ fan/ exhaust fan point/bell point controlled by one, one way switch of 5/6 Amps.
(b)one socket outlet three pin 5 amps control by one switch on the same board
(c)one socket outlet three pin 5 amps control by one switch on independent board
(d) One light point controlled by two, two way switch of 5/6 amps
All as per Item No 5 above but with 2.5 Sq mm cable (FRLS) for one 15 Amp socket outlet controlled by one switch on independent board and 2.5 Sqmm PVC insulated unsheathed multi stranded copper conductor cable as continuous earth wire complete.
Supply and Fix Switch piano, flush type, white finish, 5/6 amps, single pole, one way complete all as specified and directed.
Supply and Fix Socket outlet 5 pin, 5/6 amps and flush type, non shutters, non inter locking type, complete all as specified and directed.
Supply and Fix Switch piano, flush type, white finish, 5/6 amps, single pole, two way complete all as specified and directed.
Supply and Fix Switch piano flush type, white finish, 15/16 amps, single pole, one way, complete all as specified and directed.
Supply and Fix Socket outlet 2 in 1, 5/6 pin, 5 and 15 amp flush type, complete all as specified and directed.
Supply and Fix in repair of bell push AC SP 240 volts flush type 5/6 Amps, single pole one way complete as all specified and directed.
Supply and Fix in repair of bell electric Ding Dong type/multi music type, AC, SP 240 volts, complete as all specified and directed.
Supply and Fix in repair Switch piano, flush type, white finish, 5/6 amps, 230 volt grade single pole, one way complete all as specified and directed.
Supply and Fix in repair Switch piano flush type, white finish, 15/16 amps, single pole, 230 volt grade single pole, one way complete all as specified and directed.
Supply and Fix in repair Socket outlet 5 pin, 5/6 amps flush type, non shutters, non inter locking type, complete all as specified and directed.
Supply and Fix in repair Socket outlet two in one 2 pin 5/6 amps and 3 pin 15/16 amps (multipurpose), flush type, non shutters, non inter locking type, complete all as specified and directed.
S&F in repair Electronic fan regulator flush type, 300 W Step type, 230 volts ISI marked. icomplete all as specified and directed.
Supply and Fix ceiling rose, surface bakelite, AC, 220/240 volts, 3 terminals, complete all as specified and directed.
S & F in replacement Florecent tube rod 36/40 Watt,complete all as specified and directed. Make- Bajaj / Surya / Philips
S & F in replacement Electronic Balast 36/40 Watt, complete all as specified and directed. Make- Havells/Philips/crompton
Supply and Fix in repair lamp holder, insulated body with back plate suitable for batten /angular fittings and making connection etc complete all as specified and directed.
Supply and fix in repair Single pole and neutral enclosure with a two pin and earth plug and socket complete with onesingle pole MCB of 20 amp all as specified and directed.
Supply and Fix in repair MCB DB sheet metal enclosure TPN, 4 way having protection with 200 amps rated bus bar, 440 volts, double door, including grauting suitable for housing MCB's and isolators, complete all as specified and directed.
Supply and Fix in repair MCB DB sheet metal enclosure , SPN, 8 way having protection with 200 amps rated bus bar, 440 volts, double door, including grauting suitable for housing MCB's and isolators, complete all as specified and directed.
Supply and Fix in repair MCB DB sheet metal enclosure for DB, SPN, 4 way having protection with 200 amps rated bus bar, 440 volts, double door, including grauting suitable for housing MCB's and isolators, complete all as specified and directed.
Supply and Fix in repair MCB single pole, 240 volts, 6-32 Amps of 10 KA ‘C’ series 240 Volts complete all as specified and directed.
Supply and Fix in repair MCB single pole & Neutral ‘C’ series 240 Volts, 6-32 amps, of 10 KA complete all as specified and directed.
Supply and Fix in repair MCB Triple pole & Neutral ‘C’ series 240 Volts, 63 amps, of 10 KA
Supply and Fix in repair MCB Triple pole & Neutral ‘C’ series 240 Volts, 100 amps, of 10 KA
Supply, instalation and teasting in replacement of electric temper proof energy meter ,ISI marked, single PH 230V 2 wire 10-60 Amp with optical poat facility including sealing wire and sealing bits , Accuaracy-class complete all as specified and directed.(Note: Old unsv meter shall be deposited by contractor in MES store yard.) Make- L & T / HPL / Havells / Delhi Control Devices Pvt Ltd
Supply, instalation and teasting in replacement of electric temper proof energy meter, ISI marked, Three PH 230V 4 wire 10-60A LCD display, Energy meter with optical poat facility including sealing wire and sealing bits , Accuaracy-class complete all as specified and directed. (Note: Old unsv meter shall be deposited by contractor in MES store yard.) Make-L & T / HPL / HPL / Havells / Delhi Control Devices Pvt Ltd
M & L for factory made sheet metal box made out of 2mm thick MS sheet size 30x30x15cm with single door hinged shutter and locking arrangement for fixing Electric meter flashed/grouting on wall including necessary powder coated(Siemence gray) painting with after necessary preparation of surface ,including providing sutable glass vision panel of meter in the door shutter for easy meter reading complete all as spacified and as directed.
Supply and fix in replacement of LED Integrated Batten with Polycarbonate housing, surface mounted, (1x9 Watt) prewired including electric electrical connection with PVC insulated twin twisted copper wire of size 0.75 Sqmm from ceiling rose to tube light fitting and including taking down old fitting complete all as specified and directed. Make:- Havells / Philips / Bajaj as approved.
Supply and Fix in repair of 1x20 watt LED security light fitting, pressure die-cast aluminium including fixing the same of GI pipe 25 mm dia bore light grade bracket, 1.5 mtr long including necessary cutting / bending /welding and fixed the same with two Nos FI clamps of 40x4mm duly painted and suitable size of nut & bolts etc. and making electric connection with two core copper flexible wire of 0.50 Sqmm complete and including taking down old fitting all as specified and directed. Make:- C&S / Bajaj / Philips / Wipro / Havells
S & F in repair recess mounting LED 2x2 luminaire 34W, slim ceiling light with extruded aluminium housing and milky diffuser complete and including taking down old fitting all as specified and directed. Make-Havells / Philips / Bajaj / CG
S & F in repair LED bulk head 10 Watt with PDC aluminium housing and milky diffuser complete and including taking down old fitting all as specified and directed. Make:- C&S / Philips / Havells / Wipro
Supply and Fix in replacement of LED Linner & compact 9W mirror lightwith decorative grey end caps, polycarbonate body and ribbed opal diffuser,9W 6000K complete all as specified and directed. Make-Havells / Philips / Bajaj as approved.
Supply and fix in repair of LED Integrated Batten T5 box type surface mouted, (1x18 Watt) prewired including electric electrical connection with PVC insulated twin twisted copper wire of size 0.75 Sqmm from ceiling rose to tube light fitting and including taking down old fitting complete all as specified and directed. Make:- Havells/ Philips / wipro/Crompton as approved.
S & F in repair integral EDGEPRO ROUND of 6W, slim fit low profile downlights are engineered to diliver superior light output and uniformity utillsing the latest edge-lit LED tecnologe. An ideal solution where ceilling voids are limited but high lumine required complete and including taking down old fitting all as specified and directed. Make:- Havells / Philips / BAJAJ as approved.
S & F in replacement 11 W ballast of CFL fitting including connection complete all as specified and directed. Make:- CG / Philips / BAJAJ as approved.
S & F in replacement CFL 11 W, 2/4 pin type 230V fitting complete all as specified and directed. Make:- CG / Philips / BAJAJ as approved.
S & F in replacement CFL 36 W, 4 pin type 230V fitting complete all as specified and directed. Make:- CG / Philips / BAJAJ as approved.
S&F in repair modular 5 step fan regulator, high speed with mounted on surface mounting plastic box 1/2 module and including 01 module cover plate complete all as specified and directed.
Material & Labour for sub main wiring with 1100 volts grade PVC insulated and unsheathed cable with stranded copper conductor 2x4 Sqmm, of code Red for Phase,Black For Neutral & Green For Earth concealed in wall and drawn in including PVC conduit along with 4 Sqmm single core copper conductor multi stranded cable as earth continuity conductor including taking down existing submain wiring complete all as specified and as directed. Note: 1. Three runs of 4 Sqmm and one run of PVC conduit shall be measured as one unit. 2. Cost of cutting chasing and making good of surface shall be deemed included in quoted unit rate.
Material & Labour for sub main wiring with 1100 volts grade PVC insulated and unsheathed cable with stranded copper conductor 2x6 Sqmm, of code Red for Phase,Black For Neutral & Green For Earth concealed in wall and drawn in including PVC conduit along with 6 Sqmm single core copper conductor multi stranded cable as earth continuity conductor including taking down existing submain wiring complete all as specified and as directed. Note: 1. Three runs of 6 Sqmm and one run of PVC conduit shall be measured as one unit. 2. Cost of cutting chasing and making good of surface shall be deemed included in quoted unit rate.
Supply & fixing in replacement of 1100 volts grade heavy duty round cable with PVC insulated aluminiuum conductor served with an inner sheating of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 mtr apart including 4mm suspention wire one twin core 10sqmm solid conductor complete all as specified and directed.
Supply and laying in replacement XLPE LT 1100 volts underground earthed cable, PVC bedded, galvanized steel strip or wire armoured, electric power cable heavy duty 1100V with multi stranded, aluminum conductor of cross sectional area 16 Sqmm, 4 Core including laying, testing and commissioning complete all as specified and directed. NOTE:- Excavation & eartwork shall be measured and paid separately under respective items
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/dense soil for foundation of poles, structures, stay rods, laying of underground cable etc like such work but not exc 10 Sqm on plan complete all as specified and directed.
Returning, filling in soils including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M & L for dry sand cushioning to underground cables in layer (8 cm thick before laying of cables and 15 cm thick after laying and stretching of cable) as in trenches for cable protection or under floor or in foundation and gentally hand ramming and consolidation complete all as specified and directed. Note:- Sand thickness shall be measured only 18 cm after punning
M & L for brick protection cover of UG cable by using old size sub class 'B''common burnt clay building bricks, laid dry and flat abutting each other with width equal to length of the brick and gap between adjacent brick not exc 10 mm complete all as specified and directed.
M & L in replacement for GI tubing 40 mm dia light grade for cable protection complete all as specified and directed.
M & L for repair of exhaust fan AC single phase 230/240V of size 400/450 mm sweep with rewinding super enameled copper winding wire of suitable size and proving with suitable insulation including repalcement of wornout nut bolt washer blade split pin etc reassembling and testing on completion and refix in position complete all as specified and directed
M & L for repair of PVC / metalic exhaust fan AC single phase 230/240V of size 250/300 mm sweep with rewinding super enameled copper winding wire of suitable size and proving with suitable insulation including repalcement of wornout nut bolt washer blade split pin etc reassembling and testing on completion and refix in position complete all as specified and directed
M & L for earthing in replacement complete with galvanized steel earth plate electrode 600x600x6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level, connected to galvanized earth lead wire 4.0mm dia by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 5 of MES schedule 1991 part – I connected to earthing test point including earth continuity conductor and loop earthing etc. as required 4 mm dia galvanized iron or steel wire including necessary excavation and earth work, concrete pit & chamber in PCC 1:2:4 type B1 & pit cover 75mm thck in RCC 1:2:4 type B1 dully reinforced with 6mm dia bar @ 150 c/c both ways including with lifting handle and Earth lead and GI protection pipe light grade 15 mm dia beyond 7.5 mtr from electrode to earth terminal point /main switch board and 20mm bore GI watering pipe medium grade etc. complete all as specified and directed.
shivam builders
M/S Shahjee Fridge Service
Perfect Electricals and Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .