| 1 | L1₹24.6 LAccepted-AOC MIG 2B 65 VINAYAKA NAGAR VUDA COLONY VISAKHAPATNAM 530044 | VISAKHAPATANAM | ANDHRA PRADESH | 530044 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹26.5 L+₹68,722 (2.66%)Rejected-Finance | L2 | Rejected-Finance Being not L1 | |
| 3 | L3₹26.8 L+₹1.0 L (4.01%)Rejected-Finance | L3 | Rejected-Finance Being not L1 | |
| 4 | L4₹27.5 L+₹1.7 L (6.40%)Rejected-Finance | L4 | Rejected-Finance Being not L1 | |
| 5 | L5₹30.3 L+₹4.5 L (17.6%)Rejected-Finance SITE NO 29 30 1ST CROSS NAGAPPA REDDY LAYOUT KAGGADASAPURA CV RAMAN NAGAR PO BANGALORE 560 093 | BANGALORE | BANGALORE | KARNATAKA | 560093 | L5 | Rejected-Finance Being not L1 |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
13 Jan 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer Utility-I Visakhapatnam
Garrison Engineer Utility-I Near Samudrika Naval Base Post Visakhapatnam -530 014
REPAIR/MAINTENANCE OF HT/LT DISRTIBUTION SYSTEM AND OTHER CONNECTED WORKS AT NAVAL PARK, AMZARI PARK, NAUSENABAUGH, NCS, MMT (E) AND OTHER MISC WORKS UNDER AGE E/M-I OF GE (UTILITY-I) VISAKHAPATNAM
2021_MES_495642_1
8378/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer Utility-I Near Samudrika Naval
CLASS D
8 documents required · 8 mandatory
₹500
Garrison Engineer Utility-I
₹96,000
Yes
8 Mar 2022
17 Dec 2021
14 Jan 2022
17 Dec 2021
13 Jan 2022
31 Dec 2021
60 days
Amount
M&L for disconnecting carefully electrical connection from both HT/ LT (primary & secondary) sides of the transformer, keeping them at safe side the transformer indoor/ outdoor type of capacity from 63 KVA to 800 KVA , 11 KV/ 0.433 KV, step down of any make for carrying out refixing after completion of minor repairs like maintenance / replacement of HT/LT bush, metal rods, lugs, replacement of rusted nutbolts etc incl cheking the continuty of HT/LT windings , top cover opening, prevent the all oil leakages, provn of new insulated gaskets / cork sheet for HT/LT supply etc complete all as specefied and directed. Note: Porcelain bushings, gun metal rods, cable end joint kit, transformer oil etc shall be measured and paid separatly.
M&L for lifting, transporting, handling of the transformer from work site to the workshop / factory incl necessary tools , plants and bringing back to work site / MES yard / MES store including lifting, handling safely after rectifying faults viz rewinding / repair / maintenance etc complete all as specefied and directed by Engr-in-charge.
M&L for re-windings of HT distribution transformers of any capacity/ size/ type by strip opening of HT coils (i.e. Primary coils) from core assembly safely, unwinding the HT (i.e. Primary coils) complete, removing the old defective insulation paper, rewindingwith new copper wire of same gauge and existing size together with new DPC insulation to the copper conductor, varnishing of the windings including heating/ drying/ backing complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc. all as directed by Engr-in- charge.
M&L for re-insulating of LT strip of transformers of any capacity/ type by insulating with copper strip as per same gauge and existing size together with new insulated materials/ bracings before placing in to the transformer and assembling the coil with new insulation and fitting the coils in the chamber, testing and commissioning the transformer complete all as directed.
Filtration of transformer oil of transformers installed at various locations to achieve di-electric strength not less than 60 KV at 2.5 mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration complete all as directed by the Engineer-in-Charge.
Supply and topping up of transformer oil with di-electric strength not less than 50 KV in to the conservator tank/ body tank of the transformer/ OCB/ FRMUs etc at various locations complete all as directed by the Engineer-in-Charge. [Make: Poweroil/ Transol/ Sabitha Chemicals]
M&L for replacement of the LT porcelain bushings complete of following capacity distribution transformers of existing transformer make/ size/ type all as directed including dismantling old one.
Above 300 KVA to 700 KVA
Up to 300 KVA
M&L for replacement of the HT porcelain bushings complete of following capacity distribution transformers of existing transformer make/ size/ type all as directed including dismantling old one.
Above 300 KVA to 700 KVA
Up to 300 KVA
M&L for replacement of the HT bushing with gun metal rod with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc. complete of following capacity distribution transformers of any make/ size/ type all as directed including dismantling old one.
Above 500 KVA to 1250 KVA
Up to 500 KVA
M&L for replacement of the LT bushing with gun metal rod with threading & of suitable length / size all as per existing including metal rings/ bolts/ washers/ rubber rings etc. complete of following capacity distribution transformers of any make/ size/ type all as directed including dismantling old one.
Up to 300 KVA
Above 300 KVA to 700 KVA
M&L for preparation of old painted surfaces of transformers with coarse cloth/ brush and painting throughout externally on exposed surfaces with two coats of smoke grey colour synthetic enamel paint complete including one coat of white wash for base foundation all as specified and directed by Engineer-in-charge for the following capacity in-door/ out-door type transformer:-
Upto 300 KVA
Above 300 KVA to 700 KVA
M&L for replacement of Silica gel breather assembly complete with breather unit and silicagel including connecting with proper necessary gaskets if necessary, including removing the unserviceable breather assembly.
500 kVA to 630 kVA
250 kVA to 400 kVA
Up to 200 KVA
Supply and filling Silica gel breather to the transformer including removing the unserveiceable silica gel complete all as directed.
Supply and fix in repairs off load tap changer assembly suitable for any make with 7 tapping position including opening top cover, conservator etc. complete all as directed.
500 kVA to 630 kVA
Up to 400 KVA
Taking down HT VCB of any make/ capacity, 11 KV, 630A for servicing/ repairs, replacement of defective/ worn out components and refixing back including testing comprising the following:-
(i) Disconneted the vacuum interrupter assembly from VCB panel along with all connections, adjustment of contact gap as required.
(ii) Disconnected socket contacts, cleaning and adjustment of gap, replacement of rings etc.
(iii) Checking the breaker bushing of bus bar and circuit side, inspection/ servicing of internal surface for any arcing/ tracks.
(iv) Checking the epoxy body completely for any cracks, any sign of arcs/ tracks, cleaning thoroughly with CTC including applying Bectrol red varnish.
(v) Checking the drive insulator assembly and inspect for chocking/ tracks/ arcing.
(vi) Taking the IR value of all components,confirm satisfactory results before refixing in VCB panel.
Dismantling the spring charging mechanism of the VCB, checking the entire mechanism for any worn/ crack/ bent/ block/ loose parts etc. for the following:-
(i) Checking the condition of the spring charging motor along with gear box including servicing the motor & replacement of motor bearings if required.
(ii) Checking/ servicing of ratchet wheel assembly, driving and charging parts.
(iii) Checking the auxiliary switch, its contacts for proper functional operation.
(iv) Checking & servicing of raising/ lowering mechanism and its locking system for proper functioning.
(v) Checking & servicing of shutter assembly for its automatic opening/ closing.
Note :- The items like nuts, bolts, spring washers, petroleum jelly, CTC etc required to put the breaker in serviceable condition shall be supplied by the contractor and unit rate quoted shall be deemed to be include the same.
M&L for de-carbonising / cleaning of 11KV cubicle type VCB panels consisting of bus bar and circuit chamber, metering chamber, CTs, PTs and relay chamber all as specified below:-
(i) Checking the bus bar and circuit spouts, cleaning with CTC and applying bectrol red varnish to the surface of the bus bar and circuit spouts.
(ii) Checking the CTs/ PTs for any arcing/ tracks, cleaning and applying one coat of varnish.
(iii) Cleaning of metering and relay chamber, checking/ replacement of burnt wires if any, tightening of all connections to arrest the loose contacts.
(iv) Applying mono-plast compound at bus bar joints after tightening all joints/ connections.
M&L for Disconnecting IED of any type/Make from 11kV HT panel, cleaning the contacts , IED configuration , Calibration & Testing of all the measuring & protection devices viz., CTs, Relays and Meters at site. Testing of all the trip functions of the relays after final current settings by simulating fault current by CT secondary injection test set , checking of current transformer , rectification of defects in control wiring for proper tripping of CB during actual system fault conduction through relay & Tripping coil. Adjustment / setting to plug and time multiplier settings of IED to achieve the discrimination in tripping , tune/synchronies upstream breaker relay settings-installation of relay, testing & commissioning etc complete all as specified and as directed.
M&L for Collecting necessary required data & peak load details from IED of any type/Make from 11kV HT panel , Transformer full load details during peak hours. Relay Setting Calculations & Co-Ordination Study. Unit Protection Setting of Transformers. Feeder wise settings has to be furnished & Report with Firm Recommendations to be submitted Down Stream Power distribution (Complete 11 KV system) overall co-ordinations of time need to be achieved. Adjustment / setting to plug and time multiplier settings of IED complete in all as specified and as directed.
Supply of CT's epoxy cast resin , with primary Current 100A - 50A / 1 A - 1A , Secondary current 1A , Dual core , Dual Ratio. Protection core -Class 5P10 & Metering core - Class 0.5 , 2.5 VA complete in all as specified and as directed.
Dismantling of existing CT's , Installation of supplied CT's & Commissioning by checking of current transformer by primary injection up to 100A complete in all as specified and as directed.
Supply only following spares :-
LED Indication Lamps
LED type push button actuators
Shunt trip coil 110 V DC / 220 V DC
Breaker Control Switch
Control Circuit fuses 2A to 63A
HRC fuses for PT primary side
Spring Charging motor with gear assembly
Multi function meter , Digital type
Panel Space Heater
Digital Temperature Indicator along with thermostat.
Busbar Support Insulator - 25KA
Finger Type ARMS ASSEMBLY
Main Bus Bar shroud (11kV Grade)
Vaccume Interupter
Contact Spring
Supply of 11kV /√3 / 110v/√3 Potential Transformers
Trpping coil 110 V DC
Closing coil 110 V DC
Battery of 2 Volts
M&L for rectification of faults and retrofit of electrical circuit of 11 KV VCB with suitable IED's by checking CT/PT healthiness , proper programming of multifunctional meters and replacement of defective components & wiring with FRLSH multistrand PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed Note :- Required new components will be measured and paid separately under relevant items.
M&L for servicing of SF6 insulated outdoor type compact Ring main unit HT 400/ 630 Amps, 11KV, 50 Hz with incomer and outgoings to transformers with PT chamber and line CT by removing both the sources of supply power cable switch modules, interlocking mechanism with earth switch carefully, checking its cable ends; removing the body cover of RMU; opening its covers, moving and fixed contacts, repair of moving / fixed parts, repair of its drive mechanism,moving & fixed contact, refixing its body covers, refixing the RMU with both ends of cables; necessary testing and charging the RMU all as specified and directed. Note: Each RMU of any no of Incomers & Outgoings will be measured as for One Job
Control Wiring up to Control Chamber with 1 Core , 2.5Sq mm Copper cable with proper ferules & appropriate Lugs all as directed.
S&F of PU foam insulation sealant spray for sealing HT Cable entry bottom side gaps to arrest rat / insetcs/ reptiles entry to HT/LT panels complete all as directed . (NOTE: Each panel will be measured as one Job)
Supply & replacement, calibrating, testing, commissioning of Micro processor feeder protection relay, range - 0.01In – 8In, protection setting- 2 set, protecting circuit correct – 1Amps & 5Amps sets, records history- 5Nos, Min 6 Analog out put, with following protections feeder protection 50/ 51N (3 Phase current), 50/ 51N (Earth Over current), 67 P (3 Phase directional Over current), 6/N (Earth fault directional over current), 51V (Voltage controlled over current) 37 (3 phase under current), 46(Negative phase sequence over current), 59N (Residual over voltage), 49 (Thermal over load), 79(Auto reclose), 50BF( Circuit breaker failure detection), Cold Load pickup, Inrush blocking, Relay will be on MODBUS protocol with LCD display, trip, circuit healthy, alarm, other assignable indication, Auxlary suppy : 110V DC etc complete all as directed. Make :- Schnieder, Model.P-VAP57
Supply and laying or fixing or passing through pipe or in cable ducts, 11000 volts grade XLPE(FRLS) insulated Heavy duty (earthed),screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor 185 sq mm 3 core size including dismantling old one complete all as specified and directed by Engineer-in-Charge. MAKE: Havells / Gloster / KEI Industries Ltd / Polycab / Asian Cables / Finolex
Supply and laying or fixing or passing through pipe or in cable ducts, 11000 volts grade XLPE(FRLS) insulated Heavy duty (earthed),screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor 240 sq mm 3 core size including dismantling old one complete all as specified and directed by Engineer-in-Charge. MAKE: Havells / Gloster / KEI Industries Ltd / Polycab / Asian Cables / Finolex
Supply and fix cable jointing kit for 11 KV grade cable for outdoor terimination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conducter cable of size 240 sq mm including testing after jointing complete all as directed . Make: Birla 3M/ Raychem/ Denson
Supply and fix cable jointing kit for 11 KV grade cable for indoor terimination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conducter cable of size 240 sq mm including testing after jointing complete all as directed . Make: Birla 3M/ Raychem/ Denson
Supply and fix cable jointing kit for 11 KV grade cable for outdoor terimination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conducter cable of size 185 sq mm including testing after jointing complete all as directed . Make: Birla 3M/ Raychem/ Denson
Supply and fix cable jointing kit for 11 KV grade cable for indoor terimination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conducter cable of size 185 sq mm including testing after jointing complete all as directed . Make: Birla 3M/ Raychem/ Denson
Supply and fix of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 240 sqmm including testing after jointing complete all as directed . Make: Birla 3M/ Raychem/ Denson
M&L for GI pipe light grade 80 mm dia laid along road crossings / plinth protection with suitable fittings for cable protection or fixed to the pole/ Wall complete all as specified and directed by Engineer-in-Charge . Make : Surya Roshni Ltd / Tata / Jindal steel / Prakash
M&L for GI pipe light grade 50 mm dia laid along road crossings / plinth protection with suitable fittings for cable protection or fixed to the pole/ Wall complete all as specified and directed by Engineer-in-Charge . Make : Surya Roshni Ltd / Tata / Jindal steel / Prakash
Cutting trench through road/ wall to a width of 20cm and depth of 30cm for inserting GI protection pipe for drawing cable and filling back the trench with PCC 1:3:6 type C1 complete all as directed. ( NOTE : GI pipe will be measured and paid separately )
Supplying, laying, testing and commissioning LT XLPE insulated , armoured heavy duty electric cable of following sizes, 1100 volts grade with stranded aluminium conductor laid in trenches / passing through pipe / duct/ road crossing /fixed on poles / walls Complete all as specified and directed. MAKE: Havells / Gloster / KEI Industries Ltd / Polycab / Asian Cables / Finolex [Note: The rate quoted shall inclusive of termination at ends with suitable aluminium lugs where required]
25 sqmm 4 core
50 sqmm 3.5 core
70 sqmm 3.5 core
95 sqmm 4 core
120 sqmm 3.5 core
185 sqmm 3.5 core
240 sqmm 3.5 core
Excavation in trenches n.exc 1.5 m wide and not exc 1.5 m depth and getting out in soft / loose soil complete all as specified and directed.
Removal of surplus excavated material of any type to a distance not exceeding 50 m and depositing where directed at a level not exc. 1.5 m bove the starting point complete all as specified and directed.
Returning and filling in of excavated material any type including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each complete all as specified and directed.
M&L for sand cushioning / sand covering for underground cable protection complete all as specified. Note: Punned thickness shall only be measured and paid.
Supply and laying sub class 'B' bricks of old size (approved size locally available) laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge.
Supply and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180 mm x 40 mm all as specified and directed by Engineer-in-Charge.
Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade and including taking out cable from faulty portion in any situation/position complete all as directed for the following sizes :- Make: 3M / Denson / M-Seal / Raychem
3.5 core of 240 sq mm
3.5 core of 150 / 185 sq mm
3.5 core of 90 to 120 sq mm
M&L for detecting HT/LT UG cable faults located in any stretch / depth with cable fault locator consisting of microprocessor based, identification instrument, cable tracer for exact location of under ground cable routes complete all as specified and directed. Note:- The rate quoted deemed to be inclusive of rental charges for T&P like entire cable fault locating instrument, charges for operator and transportation etc.
Supply and replace MCCB 4 pole, 415 V, adjustable type 400 Amps with breaking capacity 35 KA including necessary modification in the panel as per site requirment complete all as specified and as directed. Make: L&T/Seimens/Schneider/Legrand/ IndoAsian
Supply and replace MCCB 4 pole, 415 V, adjustable type 250 Amps with breaking capacity 25 KA including necessary modification in the panel as per site requirment complete all as specified and as directed. Make: L&T/Seimens/Schneider/Legrand/ IndoAsian
Supply and replace MCCB 4 pole, 415 V, adjustable type 200 Amps with breaking capacity 25 KA including necessary modification in the panel as per site requirment complete all as specified and as directed. Make: L&T/Seimens/Schneider/Legrand/ IndoAsian
Supply and replace MCCB 3 pole, 415 V, fixed type upto 63 to 100 Amps with breaking capacity 25 KA including necessary modification in the panel as per site requirment complete all as specified and as directed. Make: L&T/Seimens/Schneider/Legrand/ IndoAsian
Earthing complete with galvanised steel earth plate electrode 60 cm × 60 cm × 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32X6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion (Rates inclusive of necessary earth work in any type of soil, PCC pit, CI cover , funnel in watering pipe, 40 mm dia light grade GI protection pipe for earth strip in ground etc, all as required at site for complete earthing.)
UV POWER TECH
M/s NATIONAL ENGINEERING CONSTRUCTIONS CO
THE VENKATESWARA SUPPLIERS
B5BUILDING SOLUTIONS
Jessica Engineering Works
MONITOR ENGINEERING WORKS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .