Loading…
Loading…
Tender ID
Tender Value
₹1.2 Cr
EMD Value
₹1.2 L
Closing Date
23 Mar 2026, 6:00 pmClosed
Municipal Commissioner, AMC
Upgradation/Refurbishment of 6.6 KV HT Panel, FCMA Starter, Capacitor panel and related Electrical works with Buyback at Clear Water Pump House (CWPH) at 200 MLD Raska Water Treatment Plant of AMC.
284416
19 /2025-26
Open
Miscellaneous Works
Works
Ahmedabad
3 documents required · 3 mandatory
₹3,600
Municipal Commissioner, Ahmedabad
₹1.2 L
9 Mar 2026
9 Mar 2026
9 Mar 2026
23 Mar 2026
9 Mar 2026
Name of Work : Upgradation/Refurbishment of 6.6 KV HT Panel, FCMA Starter, Capacitor panel and related Electrical works
with Buyback at Clear Water Pump House (CWPH) at 200 MLD Raska Water Treatment Plant of AMC.
Earnest Money Rs. : Rs. 1,15,700/-
Date of Opening of Tender :
Total Estimated Project Cost : Rs. 1,15,60,508/-
1) I / We am / are willing to carry out work at _________ % above/below percent (in figures) (should be written in figures and words) of the
estimated cost, as mentioned above. Amount of my / our tender works out for Rs. ________________ (in figures)
Estimated amount put to tender Rs. Estimated amount put to tender Rs.
2) Lump Sump Amount Quoted for Buy Back Items (as per Annexure-I) in Scope of Work (Section A-4, A.4.1-C), Rs. _______________
Signature of Contractor
Company’s seal :
1. Bidder has to quote % Above (Premium) or % Below (Discount) or As par of total Job, Rs. 1,15,60,508/- (i.e. Total Estimated Project Cost w/o
to carry out work at Ordered Value with any Excess -Less Qty. mentiioned in above items as per site requirement and instruction of Engineer-in-charge.
2. Bidder shall quote for buyback items as per Annexure-1 in Scope of Work, Section A-4, A.4.1(C) separately online at Sr.
as indicated above. Bidder to note that net amount quoted by the bidder shall be determined by deducting the total amount
as indicated above. Bidder to note that net amount quoted by the bidder shall be determined by deducting the total amount
of buyback quoted by bidder from the amount quoted for works as above at Sr. No. 1 and the net amount so derived shall
be considered for price evaluaiton purpose to determine lowest bid.
UPGRADATION / REFURBISHMENT WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT
CLEAR WATER PUMP HOUSE (CWPH) AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION, AHMEDABAD.
SUMMARY OF WORK
Sr. No. DESCRIPTION AMT. IN RS.
A Electrical Works
Total SITC Work Amount without GST in Rs.
Vol-II BOQ for UPGRADATION / REFURBISHMENT WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE (CWPH) AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION,
AHMEDABAD. of WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION, AHMEDABAD.
Unit Supply Unit ITC Rates in
Qty Unit SITC Rates in Total Amt in Rs
S.N. Item Description Rs
1 ELECTRICAL WORKS:
6.6 KV H.T. INDOOR PANEL : SITC of 6.6 kV, 26.3KA, 800A, Indoor, Extensible type, Horizontal drawout,
EDO, Motorised spring charging mechanism, 11 Breaker VCB feeder panel complete in all respects as per
IS, Tender SLD & Tender Specification.:
(a) 800A EDO, VCB feeder: 2 nos. as Incomer
(b) 800A EDO, VCB feeder: 1 no. as Buscoupler.
(c) 800A EDO, VCB feeder: 6 nos.outgoing Motor feeder (FCMA starter) for min. 600kW along with
Breaker trolly for each feeder and 1 no. extra trolly / as per OEM Design (d) 2 nos. Bus PT. (e) 6.6KV
Earthing truck (Bus side & cable side- 1 each). Panel shall be with Auto/Manual operation; SCADA/PLC
compatible, with EC grade copper busbars along with PT (dual secondary) Cl:0.5/3P, 200VA for metering
and protection in incomers and Bus PT on both buses; required Resin cast CT Cl: 0.5/5P10/PS as per SLD,
Load sensing CT for APFC, 15 VA ; Annunciator, Hooter, Indicating lamps, Numerical Protection relay
(current & Voltage Based) with RS 485 with combined protection for 3O/C+1E/F, S/C, Reverse power, 1 No. 4,306,884.00 28,634.00 4,335,518
Under & Over Voltage, Tfr. Protection Aux. relay, Thermal overload, etc. High speed tripping relay, Trip ckt
supervision relay, Differential protection relay, Motor protection relay as per technical specification for
Motor feeders, Temprature scanner, KWH Meter, Digital Power factor meter, Ammeter, Voltmeter (Only
I/C), Digital MFM with RS 485, Class-0.5s with 3 Line Display,A/M switch, L/R switch suitable for
Local(from panel) as well as Remote operation (from LCS) & in Auto mode through PLC/SCADA etc.
complete in all respects as per Tender Specification/ SLD & OEM requirement.
Note: 1. 110V DC supply from DCDB.
2. Required interchanging of various protection features between
concerned HT / 6.6KV VCB panel and Motor Starter panels as per
actual design requirement of equipment vendor of FCMA.
3. HT panel feeder for FCMA panel shall be with Transformer protection relay.
2 FCMA BASED SOFT STARTER PANEL for 6.6 KV, 10KA 600KW VT pump motor rating (Neutral side)
SITC of 6.6 kV, FCMA starter panel, min. 600KW, 3ph 50HZ with HT FCMA copper busbar with design
Ambient Temp @ 50°C , external by-pass Vacuum contactor , Control ON & Soft starter healthy Indication,
Push button, Run hour Meter and HMI with inbuilt PLC with communication port to integrate with 6 Nos. 594,090.00 18,635.00 612,725
Pumping station SCADA/PLC complete in all respects as per IS/IEC standard, SLD & Tender specification.
3 6.6 KV HT CAPACITOR PANEL
SITC of Capacitor Panel for 6.6 kV HV Motor Capacitor panel HV fuse, Off load Isolator, CBCT with ELR,
0.2% series reactor & capacitor unit with comprehensive protection, internal discharge resistor, Copper
busbar etc. 230 KVAr capacitor bank minimum or higher for continuous duty to improve power factor with
bus-bar chamber having 2 mm thick sheet steel enclosure with copper earthing strip & all necessary
protective equipments and accessories with IP 42 protection etc. complete in all respects as per IS/IEC
standard, SLD & Tender specification.
Vol-II BOQ for UPGRADATION / REFURBISHMENT WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE (CWPH) AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION,
AHMEDABAD. of WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION, AHMEDABAD.
Unit Supply Unit ITC Rates in
Qty Unit SITC Rates in Total Amt in Rs
S.N. Item Description Rs
4 Supply of 4.0kW VFD Starter and Accessories:
Supply an 4.0kW VFD Starter (Allen Bradley, Model: 22B-D010N104) For FD in calrifoculator with all
required accessories. The supply must include a detachable, door-mounted keypad that is interchangeable
and replaceable with the keypads on the existing working VFD starters at the site. The vendor/contractor
must ascertain all existing VFD starter data prior to supply to ensure feasibility and compatibility. 4 Nos. 16,499.00 - 16,499
(Supply at Store or as directed by Engg-in-charge of AMC. Take permission of Engg-in-chrge of Client
prior to Place order)
5 SITC of the Indoor Heat shrinkable Termination:
SITC of Indoor H.T. cable end terminations Kit for 6.6KV / 11 kV (E), 3C x 300 sq.mm. XLPE armoured 36 Sets 4,223.00 575.00 4,798.00
6 LOW VOLTAGE (LT) CABLES
Supply, laying , testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE insulated (IS 7098) AL / Cu stranded
conductor, Extruded inner sheath cables as per specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick & sand protection/in DWC 50 Mtr. 112.11 12.12 124
pipes as per specified method and shall be laid in prepared trench/ on cable tray when laid inside the building.
Size :- 4C x 6 sq. mm. A2XFY (X) Cable (For Hoist at CWPH)
7 CABLE END TERMINATION AND CONNECTION:
SITC of Double compression weather proof type Ni-plated brass cable glands and crimping type Bimetalic lugs /
sockets with necessary tools and equipments as specified in specifications and IS. The glands and lugs / sockets
shall be suitable for cable size and type mentioned below & as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar.
2) The job also includes, if necessary, supply & fixing of extension busbar of same material on MCCB or panel
board terminal / connector to connect more than one no. of parallel cables or to connect higher size cable to lower 2 Nos. 111.00 0.00 111
size unit. The job also includes earthing the glands and armour of the cable with common earth bar or flexible
copper mesh.(Cable termination qty. shall be as per site requirement)
Size :- 4C x 6 sq. mm. A2XFY (X) Cable (For Hoist at CWPH)
8 SITC of 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, 12 Set 1,545.30 51.51 1,597
canopies, shackle, rubber bush, blades, electronic speed regulator, suitable to operate on 230V,50Hz AC
supply conforming to IS: 374/1979 complete in all respect as per IS and Specification.
9 Supply of Pedestal Circulatory Industrial fan A.C. 230V. 50 Cy/s. 600 mm sweep and adjustable height 3 Set 4,014.75 4,015
complete with guard, & standard lead flexible wires and plug top complete in all respect as per -
IS/Specification.
10 Supply of All-in-One PC of HP/ DELL make with the following configuration:
13th Gen Intel i7, 16GB DDR4 Ram, 1TB SSD, 23" or above FHD Screen, Wireless Keyboard & mouse, Windows 1 No. 98,500.00 - 98,500
11, Office 2021, License version of Antivirus.
Vol-II BOQ for UPGRADATION / REFURBISHMENT WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE (CWPH) AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION,
AHMEDABAD. of WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION, AHMEDABAD.
Unit Supply Unit ITC Rates in
Qty Unit SITC Rates in Total Amt in Rs
S.N. Item Description Rs
11 Supply of HP Laser jet printer (Scaner cum Printer) - with Scanner and wifi (HP) MFPM128FN PRINTER
WITH 10 PACK OF A4 PAPER WITH 75 GSM 1 REAM 1 No. 21,500.00 - 21,500
12 Supply of a Digital BOD Incubator- PID Control from Nova Instrument Pvt. Ltd. (Model NV-8901),
complete in all respects.
13 Supply of Offline UPS with a 600W / 1000VA load capacity with 20-30 minutes of backup time complete
in all respect. 1 No. 4,998.00 - 4,998
14 CHEMICAL EARTHING SYSTEM
SITC of Maintenance free chemical earthing (copper) with earthpit of minimum bore size dia. 225mm Safe
Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of corrosion
free Pipes having Outer pipe dia of 48 mm having 250 Micron copper plating, Inner corrosion free Hot
dip galvanised (80 to 100 micron) pipe dia of 26 mm with copper flat strip type connection terminal
14mm dia with constant ohmic value surrounded by highly conductive corrosion resistant chemical 2 Set 10,015.16 578.73 10,593.89
compound with high charge dissipation suitable for electrical installation & of 3Mtr. length of Pipe with
two nos. 25Kg. bag of Back filling compound.. (2 nos. for 11KV DP structure)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
15 SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of corrosion free Hot
dip Galvanised (min 150 Microns) Pipes having Outer pipe dia of 76 mm , Inner corrosion free Hot dip
galvanised pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia with constant
ohmic value surrounded by highly conductive corrosion resistant chemical compound with high charge
dissipation suitable for electrical installation & 3Mtr. length of Pipe with two nos. 25Kg. bag of Back filling
compound. (2 nos. Each for 2nos. for pump house, 2nos. for Panels, 2nos. for elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
16 SITC of 75mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip including supply & fixing
using GI spacers, saddles when laid inside the building and inclusive of excavation & refilling of earth when
laid outside the building & interconnection with earth pit & all electro-mechanical equipments. 468 Kg. 60.60 17.17 77.77
(75X8 G.I Strip wt.4.68 kg/m, 4.68x100Mt.=468 kg.)
17 SITC of 50mm(w) x 6mm(T) etc. sizes as required, HOT dip galvanized GI Strip including supply & fixing
using GI spacers, saddles when laid inside the building and inclusive of excavation & refilling of earth when
laid outside the building & interconnection with earth pit & all electro-mechanical equipments. 345 Kg. 60.60 17.17 77.77
(50X6 G.I Strip wt.2.3 kg/m, 2.3x150Mt.=345kg.)
Vol-II BOQ for UPGRADATION / REFURBISHMENT WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE (CWPH) AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION,
AHMEDABAD. of WORK OF EXISTING INSTALLED HT/LT ELECTRICAL EQUIPMENTS AT CLEAR WATER PUMP HOUSE AT RASKA OF AHMEDABAD MUNICIPAL CORPORATION, AHMEDABAD.
Unit Supply Unit ITC Rates in
Qty Unit SITC Rates in Total Amt in Rs
S.N. Item Description Rs
18 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip galvanized GI Strip
including supply & fixing using GI spacers, saddles when laid inside the building and inclusive of excavation
& refilling of earth when laid outside the building & interconnection with earth pit & all electro- 90 Kg. 60.60 17.17 77.77
mechanical equipments. (25X3 G.I Strip, 0.6 Kg/m, 0.6x150Mt.=90Kg.)
19 Supply, laying and erection of 40mm(w) x 6mm(T) etc. sizes Copper Strip including supply & fixing of bolts,
saddles when laid inside the building and inclusive of excavation & refilling of earth when laid outside the
building & interconnection with earth pit & Tr. nutral. (40X6 Cu. Strip, 1.88 Kg/m, 1.88 x 20mtr.=37.6Kg.)
Copper Bolt,Nuts ,Washers shall be used for Connecting Earth electrode to individual eqp. Bitumen shall 37.6 Kg. 760.53 34.34 794.87
be used at the place of joint/welding.
20 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB, LCS etc.)
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 100Mt.=10.3)
21 SAFETY ACCESSORIES
SITC of following safety accessories complete with necessary fixing brackets, other accessories and tools
etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with necessary clamps made 10 Nos. 8,645.60 26.26 8,671.86
from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.
22 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds due burn, crepe
bandage, guage bandage, medicated ready to use bandage (Band-aid) adhesive tape for medicinal user,
scissors, antiseptic solution (Savlon or similar) etc. (All above contents shall be of standard makes)
(pump house) 2 Nos. 299.97 - 299.97
23 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and duly framed with
front glasses, for treatment of person suffering from electric shock.
24 Supplying & fixing of floor mounting stand for keeping four nos. of FIRE buckets comprising 1500 mm in
length, 900 mm height frame made out of 30mm X30 mm X 4 mm angle iron with cross supports for legs,
welded with 4 hooks and duly painted with one coat of red lead and two coats of approved enamelled
25 Supply and laying of Synthetic Insulating Mat of Class - B of min. thickness 12mm as per IS:15652 / IEC
61111 and with good electrical insulation property for 11kV/22KV as per site requirement. (for6.6KV HT 25 Mtr. 3,081.51 - 3,082
Panel, FCMA Starter & Capacitor Panel)
26 Supply and fixing of 20 W LED operated emergency light with maintenance free battery for 4 hours
operation during mains power failure. 6 Nos. 2,470.00 123.50 2,593.50
(2 nos. for LT Room cum PH.)
27 Supply and laying of Synthetic Insulating Mat of Class - B of min. thickness 2.5mm as per IS:15652 and
with good electrical insulation property for 11kV/22KV as per site requirement. (for HT Panel) 20 Sq.mtr. 3,081.51 - 3,081.51
28 Providing pair of rubber hand gloves ISI make suitable for working on 22 KV supply 2 No. 214.12 - 214.12
Total Amount of Electrical & Misc.Works
Total Amount of Electrical & Misc.Works
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Vol-I Clear Water Pump House-07.03.2026.pdf
Volume-II_Financial Bid-CWPH-Part-II-07.03.2026.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .