Loading…
Loading…
Tender Value
₹174.3 Cr
EMD Value
₹3.5 Cr
Closing Date
15 Jul 2026, 4:00 pm
Chief Engineer (T&O)
Site survey including underground utility verification using (GPR & EPL), Engineering, Procurement, Supply, Loading, Transportation, Unloading, Insurance, Delivery at Site, Handling, Storage, Installation, Testing, Commissioning Including Documentation of All Items/Material required to complete works for Turnkey Based Contract For Conversion of Existing LT Line Network Including Consumer Service Lines Into Under Ground Cable Network using FSP/MSP & Ring Main System at VasanaSub Divion of Vishwamitri West Division of Baroda City Circle and any where in baroda DistrictUnder MGVCL with GIS Mapping / Geo Urja Mapping (Developed by GUVNL) and Asset Tagging under under Gujarat Wire Free City Mission.
316316
MGVCL/TECH/LT UG/BCC/VASANA/26-27
Open
Electrical and Maintenance Works
Vadodara
20 documents required · 20 mandatory
₹11,800
Madhya Gujarat Vij Company Ltd Vadodara
₹3.5 Cr
21 Jun 2026
21 Jun 2026
21 Jun 2026
15 Jul 2026
21 Jun 2026
SCHEDULE-B: CONVERSION OF OVERHEAD TO UNDERGROUND
“Site survey including underground utility verification using (GPR & EPL), Engineering, Procurement, Supply, Loading, Transportation, Unloading, Insurance, Delivery
at Site, Handling, Storage, Installation, Testing, Commissioning Including Documentation of All Items/Material required to complete works for Turnkey Based
Contract For Conversion of Existing LT Line Network Including Consumer Service Lines Into Under Ground Cable Network using FSP/MSP & Ring Main System at
Vasana Sub Division Under Vishwamitri West Division Baroda City and any where in vadodara Disctrict under MGVCL with GIS Mapping / Geo Urja Mapping
(Developed by GUVNL) and Asset Tagging under Gujarat Wire Free City Mission ”.
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
1 LT NETWORK(LT XLPE Cable Supply of XLPE (IS:7098) (I) -88 ISI marked Armoured cable multistrand aluminium conductor for 1.1 KV of following Size of Cable)
A 1C X 400 Sqmm LT Cable (TC TO FSP) Meter 18550 851.7 15799035
B 1C X 300 Sqmm LT Cable (TC TO FSP) Meter 2500 670.95 1677375
C 3.5 CX 400 mm2 Aluminium Meter 0 2097 0
D 3.5 CX 300 mm2 Aluminium Meter 2500 1886.85 4717125
E 3.5 CX 240 mm2 Aluminium Meter 148768 1524.6 226811692.8
F 3.5 C X 185 mm2 Aluminium Meter 2500 1206.45 3016125
G 3.5 C X 150 mm2 Aluminium Meter 152572 978.6 149306959.2
H 3.5 C X 120 mm2 Aluminium Meter 270 827.4 223398
I 3.5 C X 95 mm2 Aluminium Meter 480 641.55 307944
J 3.5 C X 70 mm2 Aluminium Meter 690 478.8 330372
K 3.5 C X 50 mm2 Aluminium Meter 2580 367.5 948150
L 4 C X 25 mm2 Aluminium Meter 10770 228.9 2465253
M 4 C X 16 mm2 Aluminium Meter 804150 161.7 130031055
N 4 C X 10 mm2 Aluminium Meter 0 124.95 0
O 4 C X 6 mm2 Aluminium Meter 0 99.75 0
P 2 Core, 4 Sq.mm Meter 69 0
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
LT Cable Termination:
Supply of Cable Termination on LT Pole, FSP, LT Distribution Trasformer Box of pole mounted trasformer of LT cable grade as pecified below. LT CABLE including cutting,stripping of
cable,insulations,providing compression type terminals,suitable cable glands,crimping lugs with necessary connections.Work carried out up to consumer premises with meter shifting, and
provide load side cable as per site conditions and as per EIC. All the accessories in the scope of biddier.
A 1C X 400 Sqmm LT Cable (TC TO FSP) Nos 2300 1245 2863500 2300 45
B 1C X 300 Sqmm LT Cable (TC TO FSP) Nos 250 1245 311250 250 45
C 3.5 CX 400 mm2 Aluminium (FSP TO MSP) Nos 0 1245 0 0 45
D 3.5 CX 300 mm2 Aluminium (FSP TO MSP) Nos 250 1245 311250 250 45
E 3.5 CX 240 mm2 Aluminium (FSP TO MSP) Nos 3084 1245 3839580 3084 45
F 3.5 C X 185 mm2 Aluminium (FSP TO MSP) Nos 250 940 235000 250 45
G 3.5 C X 150 mm2 Aluminium Nos 8915 940 8380100 8915 45
H 3.5 C X 120 mm2 Aluminium Nos 9 889 8001 9 45
I 3.5 C X 95 mm2 Aluminium Nos 16 889 14224 16 45
J 3.5 C X 70 mm2 Aluminium Nos 23 889 20447 23 45
K 3.5 C X 50 mm2 Aluminium Nos 86 889 76454 86 45
L 4 C X 25 mm2 Aluminium Nos 359 804 288636 359 45
M 4 C X 16 mm2 Aluminium Nos 26793 788 21112884 26793 25
N 4 C X 10 mm2 Aluminium Nos 0 788 0 0 25
O 4 C X 6 mm2 Aluminium Nos 0 679 0 0 25
P 2 Core, 4 Sq.mm Nos 0 679 0 0 25
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
FSP (FUSE SECTION PILLER): 4 Way
Supplying and erecting 120x100x40 cms. Fuse section pillar fabricated from 4 mm Thermosetting Plastic ( moulded in a single piece ) i.e Glass Reinforced Polyester sheet Moulding
Compound (SMC ) or metal body(As per Specification and drawings) with cable clamps to be burried in ground to have appropriate erection on look unifrom unit erected with cement
3 concrete foundation and 45 cms high brick masonry internal supported on both side with intrnal and outer side locking arrangement with lock and keys in duplicate .Incoming switchgear
SFU of 800A TPN and outgoing HRC SMC fuse base and knife type links 32 Amp to 630 Amp capacity fuse base fitted on 630 Amp current capacity copper Busbar with RYB colour coding
and insulated strip with all internal connections and entry for incomming up to 1 core 300/400 sq mm 4 nos and outgoing 3 nos. 31/2 core cables of suitable sizes. (As per Technical
specification of FSP ) (Erection shall be carried out as per approved drawing and site condition)
FSP (FUSE SECTION PILLER): 6 Way
Supplying and erecting 120x100x40 cms.Fuse section pillar fabricated from 4 mm Thermosetting Plastic ( moulded in a single piece ) i.e Glass Reinforced Polyester sheet Moulding
Compound (SMC ) or metal body(As per Specification and drawings) with cable clamps to be burried in ground to have appropriate erection on look unifrom unit erected with cement
4 concrete foundation and 45 cms high brick masonry internal supported on both side with intrnal and outer side locking arrangement with lock and keys in duplicate .Incoming switchgear
SFU of Suitable TPN and outgoing HRC SMC fuse base and knife type links 32 Amp to 630 Amp capacity fuse base fitted on 630 Amp current capacity copper Busbar with RYB colour
coding and insulated strip with all internal connections and entry for incomming 1 core 300/400 sq mm 4 nos and outgoing 5 nos. 31/2 core cables of suitable sizes. (As per Technical
specification of FSP ) (Erection shall be carried out as per approved drawing and site condition)(SFU Amp Capcity is as under)
MSP(Mini Section Piller) : 4 Way
Supplying and erecting 120x100x40 cms. Mini section pillar fabricated from 4 mm thick Thermosetting Plastic(moulded in a single piece) i.e. Glass Reinforced Polyester Sheet Moulding
Compound (SMC) or Metal Body Type Enclouser(As per Specification) with cable clamps to be burried in ground to have appropriate erection on look uniform unit erected with cement
concrete foundation and 45 cms high brick masonary internal supported on both side with internal and outer side locking arrangement with lock and keys in duplicate. Incoming HRC SMC
fuse base and kinfe type links 32 Amp to 250 Amp. capacity, fuse base fitted on 250 Amp. current capacity copper Busbar with RYB colour coding and insulated strip with all internal
connections and entry for incoming up to 3.5 Core 300 Sq.mm 1 Nos. and outgoing 3 nos. 3.5 core cables of suitable sizes.( As per Technical specification of MSP)
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
MSP(Mini Section Piller) : 6 Way
Supplying and erecting 120x100x40 cms. Mini section pillar fabricated from 4 mm thick Thermosetting Plastic(moulded in a single piece) i.e. Glass Reinforced Polyester Sheet Moulding
Compound (SMC) or Metal Body Type Enclouser(As per Specification) with cable clamps to be burried in ground to have appropriate erection on look uniform unit erected with cement
concrete foundation and 45 cms high brick masonary internal supported on both side with internal and outer side locking arrangement with lock and keys in duplicate. Incoming HRC SMC
fuse base and kinfe type links 32 Amp to 250 Amp. capacity, fuse base fitted on 250 Amp. current capacity copper Busbar with RYB colour coding and insulated strip with all internal
connections and entry for incoming up to 3.5 Core 300 Sq.mm 1 Nos. and outgoing 5 nos. 3.5 core cables of suitable sizes.( As per Technical specification of MSP)
MSP(Mini Section Piller) : 8 Way
Supplying and erecting 120x100x40 cms. Mini section pillar fabricated from 4 mm thick Thermosetting Plastic(moulded in a single piece) i.e. Glass Reinforced Polyester Sheet Moulding
Compound (SMC) with cable clamps to be burried in ground to have appropriate erection on look uniform unit erected with cement concrete foundation and 45 cms high brick masonary
internal supported on both side with internal and outer side locking arrangement with lock and keys in duplicate. Incoming HRC SMC fuse base and kinfe type links 32 Amp to 250 Amp.
capacity, fuse base fitted on 250 Amp. current capacity copper Busbar with RYB colour coding and insulated strip with all internal connections and entry for incoming up to 3.5 Core
Sq.mm 1 Nos. and outgoing 7 nos. 3.5 core cables of suitable sizes.( As per Technical specification of MSP)
Supply, Instalation, Testing, Commissioning switch fuse unit made by SMC Box and capacity
A of 125 A, Mostaly used in flat/Socity area. Installation worked caried out with instruction of Nos 250 12087 3021750 250 1150
EIC. And as per the drawing approved by CA- Minimum 16 Nos. of CKT
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
Supply, Instalation, Testing, Commissioning switch fuse unit made by SMC box and capacity
of 200 A, Mostaly used in flat/Socity area. Installation worked caried out with instruction of
EIC. And as per the drawing approved by CA - Minimum 16 Nos. Of Circuit
Supply, Instalation, Testing, Commissioning switch fuse unit made by SMC box and capacity
of 400 A, Mostaly used in flat area. Installation worked caried out with instruction of EIC. And
as per the drawing approved by CA- Minimum 16 Nos. Of Circuit
EARTHING ELECTRODS: Supplying & erecting of maintained free earthing system comprising of
Minimum 17 mm dia 3 mtr Long Earthing Electrode of low carbon steel electrode with 250 microns
copper coating + carbon based conductive concrete back fill safe Compound(resistivity of less than
0.10 ohm mtr) & copper clamp. (FSP)
EARTHING ELECTRODS: Supplying & erecting of maintained free earthing system comprising of
Minimum 17 mm dia 2 mtr Long Earthing Electrode of low carbon steel electrode with 250 microns
copper coating + carbon based conductive concrete back fill safe compound(resistivity of less than
0.10 ohm mtr) & copper clamp.(MSP+SFU)
EARTHING STRIP: Supply installation & commissioning of earthing conductor 25 x 3mm G.I. strip for
C pole mounted transformer and up to FSP,RMU as well as connection to be made to the earth pit. Mtr 87280 91 7942480 87280 52
Rates inclusive of hot dipped hard wares.
PRE BONDING TAP: For laying on trench after laying cable on trench to provide indication cable route
10 below land surface in underground trench to protect cable for mechanical injuries.LDPE Material Mtr 562640 14 7876960 562640 7
having 250 mm Width (Yellow Color is preferable)
CABLE TAG: The PVC tag for identification of feeder/PSS/FSP/RMU name of HT/LT cables shall be
provided at every 10 MTR LT Feeder : PSS/Transformer/FSP/MSP/SFU
CABLE ROUTE MARKER: Providing and erecting RCC cable route marker as per drawing duly marked
with "DANGER" mark, "discom POWER CABLE" and arrow of route of cable.
CABLE TERMINAL FERRULS: The PVC Cable terminal ferruls for identification of phase sequence and
13 feeder/PSS/FSP name of HT/LT cables shall be provided at every termination of all cables stating Nos 17176 24 412224 17176 8
detail as under. HT Cable :Feeder name/Phase(R/Y/B) LT Cable : TC/FSP name/Phase(R/Y/B/N)
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
Supply of HDPE/DWC pipe confirming to IS 4984:1955 having diameter 110/100mm or
appropriate pipe size of cable and minimum thickness 5mm at a minimum depth 1200mm
below the road surface by PUSH through method by drilling the road with HDD
machine/manually without breaking the road surface and with laying of any size of LT XLPE
insulated aluminium armoured cable through the duct as per the instruction of EIC and
specifications. (For LT XLPE Cable above 3.5C/4C* 185 SQMM )
Supply & Laying of HDPE/DWC pipe confirming to IS 4984:1955 having diameter 90mm or
appropriate pipe size of cable with laying of various size of LT XLPE (3.5 Core 95 sq. mm to
3.5 core 150 Sq.mm) PUSH through method by drilling the road with HDD machine/manually
without breaking the road surface and with laying of any size of LT XLPE insulated aluminium
armoured cable through the duct as per the instruction of EIC and specifications
(Single/Double/Bunched)
Supply & Laying of HDPE/DWC pipe confirming to IS 4984:1955 having diameter 50/63 mm
with laying of various size of LT XLPE (2C 4SQmm to and upto 3.5/4 core 70 Sq.mm) PUSH
through method by drilling the road with HDD machine/manually without breaking the road
surface and with laying of any size of LT XLPE insulated aluminium armoured cable through
the duct as per the instruction of EIC and specifications insulated Aluminium armoured Cable
(Single/Double/Bunched)
Laying (including installation, testing and commissioning) of various size of LT XLPE insulated
Aluminium armoured Cable in ground 1200mm deep, 300mm wide trench, providing sand
cushioning below (75mm thick layer of sand) and above (75mm thick layer of sand) of the
cable and covering it with RCC half round hum pipe (150mm inner dia with thickness of
30mm, 1meter in legnth) before refilling pre warning tap/bonding tap should provide below
700mm from ground level and back filling the same to make the ground level as original. As
per specification and drawing of MGVCL. (RCC half round hum pipe should be provided
throughout on cable without gap).
Providing, supplying, laying, fixing and commissioning of Green color Hose Pipe for LT armored service cable protection/saddling work in consumer premises where digging is not possible
15 up to energy meter location, including all accessories such as saddles, clamps, clips, bends, fastening materials etc. complete in all respect as per technical specification.(Saddleing with
wall and etc, for this work GI type saddle and nail shall be used)
A Hose Pipe of Size 40mm/32mm Mtr 39200 118.64 4650847.458 39200 17.80
B Hose Pipe of Size 77mm/63mm Mtr 5600 364.41 2040677.966 5600 17.80
C Hose Pipe of Size 90mm/75mm Mtr 5600 406.78 2277966.102 5600 17.80
D Green color Hose Pipe of Size 120mm/103.5 mm Mtr 5600 805.08 4508474.576 5600 17.80
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
DRAWING: Preparing complete drawing of entire network as well as individual feeder map
showing joints also in AutoCad and providing the same to MGVCL in AutoCad copy as ell as
pdf copy and hard copy in six sets. The drawing should be geographical indicating all
Paint Pointed Letter 2 inchsize (Markingon FSP,MSP,SFU Etc Inany palce). As per directive of
Engineer Incharge) with supply of color
Dismentallling PSC Pole 8 Mtr with cross arm,insulators,hardwares etc.and return it to MGVCL
A store.While dismentalling utmost care shall be taken so that the material so that the same can be Nos 0 562
reused by MGVCL.
Dismentallling PSC 10 Mtr/Rail/RSJ pole with cross arm,insulators,hardwares etc.and return it to
B MGVCL store.While dismentalling utmost care shall be taken so that the material so that the same Nos 0 1131
can be reused by MGVCL.
Dismentalling of existing HT/LT line of 34SQMM to 55SQMM conductor and after making coil and
C stacking the same at MGVCL store.Conductor has to dismantal from shackel to shackel pole with 175.56 715
minimum nos of cut piese as per instruction of EIC
Disment of of single phase AB Cable(3.5 core) including fittings of All Accessories and stacking the
D same at MGVCL store.Cable has to dismantal from shackel to shackel pole with minimum nos of cut KM 51.44 8089
piese as per instruction of EIC
Disment of of single phase AB Cable(LT 1P2W) including fittings of All Accessories and stacking the
E same at MGVCL store.Cable has to dismantal from shackel to shackel pole with minimum nos of cut KM 0 3235
piese as per instruction of EIC
COMPREHENSIVE MAINTENANCE WORK FOR LT UNDERGROUND NETWORK AFTER SUCESSFUL COMPLETION OF PROJECT,
For Five years after completion of project,For further detail bidder advice to Read the chapter in STANDARD BIDDING DOCUMENT
Locating Underground Cable Fault of Underground Cable including digging,pin pointing with
cable route tracker by using cable fault location equipment like cable fault Van/Vehicle with
supportive meters and accessories & doing high pressure testing of cable for checking
A Per Job 2500 6780
healthiness of cable with suitable equipment after jointing of the faulty cable (excluding
jointing kit) backfilling, and submission of fault location with report of showing distance
from main source approx.. Including required manpower.
Supply of unskilled/skilled man power to perform day to day activity of maintenance work of
B LT Under ground Network and all Associated activity etc.These man power deployment MND 16425 650
meant for activities other than above 19 (A)
Amount in Rupees (without GST) 843261935
SUPPLY PORTION ERECTION PORTION
Sr No Particulars of Item Unit
Quantity Total in Rs Quantity Unit Rate in Rs Total in Rs
TOTAL Amount (WITH GST) 995049083
TOTAL Amount (WITH GST) 995049083
GRAND TOTAL (WITH GST)
GRAND TOTAL (WITH GST)
TOTAL COST IN CR 174.33 Crore
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
FINAL SBD VASNA.pdf
FINAL SCHEDULE-B VASNA.pdf
1. 1.1 KV CABLES PV.pdf
2. Reference Bid Drawing.pdf
3. Cables Tags and Markers.pdf
4. Erection Specification of LT Cabling Works.pdf
5. Final _LT Feeder Pillar-GPRD 567 WAY.pdf
6. GI Earthing Pipe.pdf
7. Sample Survey Report of SUE through GPR and EPL.pdf
8. Triple Pole Switch Fuse Units with Neutral Links.pdf
9. TS FOR 1.1kV XLPE INSULATED POWER CABLES.pdf
10. TS FOR CIVIL WORKS.pdf
11. TS FOR FRP FENCING.pdf
12. TS FOR FUSE SECTION PILLAR (FSP).pdf
13. TS FOR HDPE PIPES.pdf
14. TS FOR MAINTENANCE FREE EARTH FOR ELECTRICAL INSTALLATION.pdf
15. TS FOR MINI SECTION PILLAR (MSP).pdf
16. TS M.S. CHANNEL-ANGLE AND FLAT ETC.pdf
17. TS OF GI EARTHING STRIPS.pdf
18. TS of HDPE DWC Pipe.pdf
19. TS OF JOINTS FOR 1.1kV XLPE ALUMINIUM OR COPPER POWER CABLES.pdf
20. TS OF MATERIALS USED FOR CIVIL WORKS.pdf
Download all tender documents and submit your bid