Construction of Sewer network under TP Schemes Nos. 412A, 412B, 243, 109, 413 & 411 and construction of 3 Nos.Pumping Stations (MPS 01- 11.98 MLD, MPS-2 12.24 MLD, MPS-3 20.55 MLD & SPS-12.5 MLD) and Sewerage Treatment Plant of 30 MLD Capacity within AUDA TP Scheme areas. (Job-40/2025-26)
281109
Job-40/2025-26
Open
Miscellaneous Works
Works
Ahmedabad
3 documents required · 3 mandatory
₹18,000
Ahmedabad Urban Development Authority, Ahmedabad
₹1.1 Cr
26 Feb 2026
26 Feb 2026
26 Feb 2026
27 Mar 2026
26 Feb 2026
Bill of Quantities
Depth of excavation for inlet units
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Excavation for well including removing and spreading
the excavated stuffs directed with all lead.
1.A) In all sorts of soils & Soft Murrum
(100% in all sorts of soils & Soft Murrum)
(100% in all sorts of soils & Soft Murrum)
(100% in all sorts of soils & Soft Murrum)
(100% in all sorts of soils & Soft Murrum)
(100% in all sorts of soils & Soft Murrum)
(100% in all sorts of soils & Soft Murrum)
1.B) In Hard Murrum
(100% in Hard Murrum)
(100% in Hard Murrum)
Excavation for foundation upto 1.5 m depth including
sorting out and stacking of useful materials and disposing
off the excavated stuff upto 50 Meter lead.(A) Loose or
b) Dense or Hard soil 245.58 149.67 cmt
(C) Hard Murrum 18.58 256.12 cmt
(D) Soft rock not requiring Blasting 11.15 263.08 cmt
E) Hard Rock 7.43 597.60 cmt
Excavation for foundation 1.5 m to 3.0m depth including
sorting out and stacking of useful materials and disposing
off the excavated stuff upto 50 Meter lead.(A) Loose or
Filling available excavated earth (excluding rock) in
trenches. plinth, sides of foundations etc. in layers not
exceeding 20 cm. in depth consolidating each disposited
layer by ramming and watering.
Dewatering by pumping set of required capacity including
temporary platform carting pumping at site and fixing the
same in position including all accessories, and fuel and
labour etc . complete.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing and laying rubble for appron (each stone
6 weighting not less than 40Kg.) including and packing and
filing in the interestices with quarry-spalls.
230 mm rubble soling below footing 174.00 1041.05 CU.M.
Providing and casting in situ C.C. in grade M-15 (approx.
corresp. to prop. 1:2:4) (proportions as per mix design or
as per Table 9 of IS456 2000 in masses by weigh batching
) using granite, quartzite trap metal of size 6 mm to 20 mm
for RCC work, including scaffolding centering, form
work, needle vibrated consolidation, curing comp. up to
meter depth or height (excluding cost of reinforcement
and neat finishing) with centering and
shuttering/deshuttering etc. comp. for structure for other
than water retaining.
Footing (without form work)
Providing and cast in situ C.C. in grade M-30 proportions
of ingredients as per mix design by weigh batching using
granite, quartzite trap metal of size 12 mm to 20 mm and
or 6 mm to 12 mm including scaffolding centering
8 formwork, needle vibrated consolidation, curing and
hydraulic testing etc. complete (excluding cost of
reinforcement) with centering and shuttering/deshuttering
etc. camp. up to 6 meter height /depth Av. G.L.for all
water retaining structures
Flat bottom slab with shuttering 293.71 9444.95 CU.M.
Vertical Wall (Above 25 cm) 715.00 9295.45 CU.M.
Columns 16.00 10714.55 CU.M.
Floor slab/slab with shuttering 232.00 9444.95 CU.M.
Beams/ ring beams/girders 59.00 9758.90 CU.M.
Lintel/W.Shed/Chhajja 4.00 9444.95 CU.M.
Providing formwork of ordinary timber planking so as to
give a rough finish including centering shuttering strutting
and propping etc. Height of propping and centering below
9 supporting floor to ceiling not exceeding 4 M. and 82.56 173.40 sqm
removal of the same for in situ reinforced concrete and
plain concrete work in. Foundations Footings Bases of
Columns etc. and Mass concrete.
Providing and cast in situ C.C. in grade M-25 proportions
of ingredients as per mix design by weigh batching using
granite, quartzite trap metal of size 12 mm to 20 mm and
or 6 mm to 12 mm including scaffolding centering
formwork, needle vibrated consolidation, curing and
hydrulic testing etc. complete (excluding cost of
reinforcement) with centering & shuttering/ deshuttering
etc. for all water retaining structures.
a) R.C.C. footings & Raft 145.00 9288.55 cmt
b) R.C.C. Columns 32.00 10574.25 cmt
c) R.C.C. beams, lintels and bracket for gantry or chain
pully blocks, plinth beams, tie beams, weather shed etc.
d) R.C.C. slabs and platform 115.00 9288.55 cmt
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supplying cutting, bending, binding and placing in
position steel as per plan and design and as per ISS
including cost of steel and binding wire for
11 reservoirs/structures only including lift up to 6 meter 216.54 89129.60 M.Ton
height or depth below G.L. for all diameters Do -
deformed (TMT) bars confirming to relevant IS Fe -
grade for all diameters.
Supplying, cleaning, cutting, bending, welding,
fabricating, erecting, structural steel in position
irrespictive of location and levels as per drawings
including handling and transport, etc. complete including
applying two (2) coats of primer red oxide and two (2)
coats of approved quality paints
Brick work using common burnt clay building bricks
having crushing strength not less than 35kg./Sq.Cm. in
foundation and plinth in Cement Mortar 1 : 6 ( 1-Cement :
6-fine sand ) (B) Conventional (upto 10 ton)
Brick masonry in cement mortar (1:5) using common
burnt clay building bricks having crushing strength not
less than 35kg/csmt including scaffolding,curing, etc.
complete for walls, parapets, etc. in Foundation and Plinth
Brick masonry in cement mortar (1:5) using common
burnt clay building bricks having crushing strength not
less than 35kg/csmt including scaffolding,curing, etc.
complete for walls, parapets, etc. at all levels.
Brick work using common burnt clay building bricks
having crushing strength not less than 35 kg./Sq.Cm. in
foundation and plinth in Lime Mortar 1:1.5 (1- Lime putty
:1.5 -fine sand)(B) Conventional
Brick work using common burnt clay building bricks
having crushing strength not less than 35 kg./Sq.Cm. in
foundation and plinth in Lime Mortar 1: 2 (1- Lime putty :
2 -fine sand)(B) Conventional
Providing 15mm thick cement plaster in single coat on
Rough (Similar)side of single or half brick walls for
18 interior plastering upto floor two level and finished even 14772.60 224.79 Smt
and smooth in (i) Cement mortar 1:3 (1-cement:3-sand) &
Finishing with a floating coat of neat cement slurry.
Providing 10mm thick cement plaster in single coat on
brick/concrete walls for interior plastering upto floor two
level and finished even and smooth in (i)Cement mortar
1:3 (1-cement:3-sand)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
20 mm thick sand faced cement plaster on walls up to
height 10 metres above ground level consisting of 12 mm
20 thick backing coat of C.M. 1 : 3 ( 1-cement : 3-sand ) and 4746.72 300.66 SQ.M.
8 mm thick finishing coat of C.M. 1 : 1 ( 1-cement : 1-
sand ) etc. complete.
Providing and fixing window having extruded
aluminum Colour anodized section frame main
outer size 127mm x 38.10mm x 1.35mm @wt.
1.384kg/m, horizontal Four track member size
vertical member of size 122.20mm x 31.75mm x
1.50mm @1.398 kg/mt with sliding shutters of
horizontal member size 40mm x 18mm x 1.29mm@
0.456kg/mt ,vertical member of size 40mm x 18mm
x 1.29mm @ 0.456 kg/mt with 5 mm thick
transparent bronze colour tinted float glass with
powder coated aluminum fittings and fixtures and
transparent silicon sealant glass fixing to frame as
per details etc complete for window.
Providing and fixing M.S. grills of required pattern
to wooden frames of windows etc. with M.S. flats
22 at required spacings and frame alround, square or 432.00 145.08 Kg
round bars with round headed bolts and nuts or by
screws. (B) ORNAMENTAL GRILL
Providing and fixing rolling shutter of approved make
made of 80 mm. wide M.S. plates inter locked together
entire length and jointed together at the end by locks
mounted on specially designed pipe shafts with bracket
plates. Guide channels and arrangements for inside and
outside locking with push pull operation complete
including the cost of hood cover and spring complete. (B)
Shutters having width 3.5 M. and above
Providing & Refilling in sides of structure with sand
24 incuding watering, ramming, consolidation and dressing 3162.00 460.19 CU.M.
complete in layers not exceeding 20 CM. in depth.
Distempering two coats with oil bound washable
distemper of approved brand & manufacture & of required
shade on wall surface to give an even shade over and &
incl. a priming coat of alkali resistance primer of approved
brand after throughly brushing the surface to give an even
shade after throughly brushing the surface free from
mortar droppings and other foreign matter and also
including preparing the surface even and smooth.
Extra for ditempering with oil bound washable distemper
on ceiling and sloping roofs.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Applying two coats of putty & two coats of primer of
approved brand and manufacture on new wall surface to
26 give an even shade including thoroughly brushing the 1200.00 40.59 Smt
surface free from mortar dropping and other foreign matter
and sand papered smooth.
Finishing wall with weather proof exterior emulsion paint
on wall surface (two coats) to give an required shape even
27 shade after thouroughly brushing the surface to remove all 1996.72 114.53 SQ.M.
dirt, and remains of loose powdered materials. Etc
Providing and laying broken China Mosaic flooring for
terrace using 12 mm to 20 mm broken pieces of glazed
tiles to be laid over Cement mortar 1:3 to plain or slope
28 and to be tempered to bring mortar crème out upto surface 335.01 747.29 Smt
using white cement including rounding of junctions and
extending them upto 15 cm. along the wall, clearing with
water and oxalic acid etc. as directed.
Providing and laying polished Kota stone slab flooring
over 20 mm (average) thick base of cement mortar 1:6 (1
29 cement : 6 coarse sand) laid over and jointed with grey 320.00 1096.33 smt
cement slurry including rubbing and polishing etc.
complete . Avg - 30 mm thick
Providing and laying polished kota stone slab 25mm thick
in risers of steps,skirting Dedo and pillars laid on 10mm
thick cement mortar 1:3 (1-Cement : 3 coarse sand) and
jointed with gray cement slury mixed with pigment to
match the shade of slab including rubbing and polishing
Granite in Jams and Sills of the window and ventilation
31 and Door with one molding as directed by Engineer-in- 33.00 3282.50 smt
Filling in plinth with sand under floors incuding watering,
ramming, consolidation and dressing complete
Providing throating or plaster drip and moulding as
instructed by Engineer in charge.
Conveying, carting and removing of the surplus
excavated stuff from the site to any place within the
34 Municipal limit as directed by the Engineer-in-charge
including loading, unloading, carting, dumping and/or
spreading as directed etc. Comp
Carting from 50mt to 5 Km 468.00 103.26 Cmt
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing and Fixing 25 mm X 5.2 mm MS Railling with
three horizontal rows and posts of angle iron of Size
35 mm X 65 mm X 8 mm RCC 150 mm and 1.15 meter 4284.00 88.55 R.M.
height and placed at 1.85 mt/ C/C including painting two
coats and anchorage in CC etc. Complete.
Providing and laying cement concrete for IPS 1:2:4 (1-
cement : 2-coarse sand : 4-graded stone aggregate 20mm
nominal size) laid in one layer and finished with a floating
coat of neat cement. (B) 50mm thick.
Providing , laying and jointing in true line and level
diameter UPVC (Type B) conforming to IS 13592-1992
with one end plain and other end socketed with rubber ring
& fittings conforming to ISI 14735-1999 of approved
make for drainage system pipeline, pipe shall be jointed
with each other with rubber lubricant, pipe shall be fixed
37 on wall using of PVC clamp of the size 110 mm diameter 40.00 835.15 R.M.
x 149 mm lengthn x 145 mm height at every 2000 mm
centre to center or shall be concealed in walls as directed
including necessary fittings such as bends, shoes etc.
imcluding testing of pipes and joints and joined with
adhesive solvent cement including costof all materials.
Providing and laying marble stone slab flooring over
20mm (average) base of cement mortar 1:6 (1-
cement:6coarsesand) or L.M. 1:1.5 (1-lime putty :1.5-
coarse sand )laid and jointed with gray cement slurry
including rubbing and polishing complete. (A) Marble slab
25mm thick (up to 10 ton)
Providing and fixing copper lightning arrestor incl. copper
39 strip and earthling plate etc. complete (incl. cost of 200.00 1009.70 Kg
excavation for earthling plate etc. rate per kgs of copper).
Providing and fixing 50 cm wide M.S. Ladder fabricated
from M.S. Flats 10 mm x 75 mm with 20 mm dia steel bar
40 steps in double rows, @ 30 cm C/C. The include stays of
10 mm x 50 mm flats fixed at 3 meter C/C with welding
anchoring and 3 coats anticorrsive paint.
M.S. Ladder(Without safety cage) 190.74 3392.50 Kg
Providing and fixing PVC pipe of 6Kg./csmt of 140 mm
dia for rain water with shoe.
Providing and fixing depth gauge painted on TW plank
mm / MS plate 4 mm thick float, level indicator sliding
42 wire on standard pullies incl. necessary arrangement to 4.00 6348.00 Nos.
prevent the swinging etc. complete with calibration up to
43 Exhaust Fan 8.00 1949.65 Nos.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Steel work, welded in built up sections framed work
including cutting, hoisting, fixing in position and applying
a priming coat of red lead paint. (A)In beams and joists,
channels angles Tees, flats, with connecting plates or
angle cleats as in main and cross beams. Hip and jack
rafters, purlins conneted to common rafters and the like
8 mm thick Chequred plate
8 mm thick Chequred plate
Painting two coats (excluding priming coat) over new steel
and other metal surfaces with enamel paint, brushing,
interior to give an even shade including cleaning the
surface of all dirt, dust and other foreign matter.
Providing and constructing cofferdam in river basin
including excavation ,filling, middle portion with B.C.soil
(in empty Cement/Gunny bags) to the entire satisfaction of
EIC till completion of the work including dismantling
coffer dam after completion of the work as directed by
Painting Letters for "Capacity of Pumping Station" the
size of letters will be 45 cm height and 50 mm width.
Providing and laying cement concrete 1:3:6 ( 1: Cement :
3- Coarse Sand : 6- CRUSHED stone aggregates 40mm
nominal size) and curing complete excluding cost of
formwork in (A) Foundation & Plinth (more than 10 ton)
Providing and laying controlled cement concrete M.200
and curing complete including the cost of formwork (Only
fresh ply shall be use) but excluding cost of reinforcement
for reinforced concrete work in RCC SLAB
Providing Thermo Mechanically Treated bars (TMT bars)
Fe-415 reinforcement for R.C.C. work including bending,
50 binding amd placing in position complete up to floor two 626.48 67.26 kg
level (more than 10 ton)
Providing and fixing 35 mm thick shutters for
doors,windows and clear story windows including Indian
teak wood frames 12 cm x 7 cm size including anodized
alluminium fixtures and fastenings including primer coat
of approved quality and two coats of oil painting etc
complete. (ii) Fully Panelled
Providing and laying 24" x24" Vitrified 8mm thick tiles
flooring over 20mm base of cement mortar 1:6 on new
surface or fixing on existing flooring by adhesive
52 materials including dismantling existing flooring and 51.84 1397.83 Sq.m
jointed with coloured cement slury including finished with
flush pointing & cleaning the surface etc. complete for
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing erecting fixing double coated Syntex of
Equivalent PVC (ISI) Mark Water Tank of Required
Capacity eack with all necessary fittings & connection etc.
complete on Terrace.
Providing and fixing to wall, ceiling and floor CPVC
plumbing systms for hot and cold water( IS 15718, NSF
54 approved ) of the following nominal bore, tube fitting and
clamps including making good the wall ceiling and floor. -
Providing and fixing wsh down water closet (European
type, W.C. Pan) with integral P or S trap including jointing
55 the trap with soil pipe in Cement Mortar 1:1 (1-Cement : 1- 4.00 1303.71 Nos.
fine sand) (Seal and cover to be measured and paid for
separately)(A) vitreous China Pattern :(i) in white colour
Providing and fixing chromium plated brass half trun flush
56 cock of approved quality including fixing in pipe line etc. 4.00 314.97 Nos.
complete.(i) 20mm dia.
Providing and fixing 100mm size P or S trap for water
closet squatting pan including jointing the trap with the
pan and soil pipe in cement Mortar 1:1 (1-Cement : 1-Fine
sand)(A) Vitreous China.
Providing and fixing G.I. inlet connection for flush pipe
Providing and fixing plastic seat and cover for wash down
59 water closer with C.P. brass hinges and rubber buffers. (B) 4.00 291.33 Nos.
Black plastic seal and cover.
60 Bib cock 15 mm Heavy duty with cap 4.00 400.58 Nos.
Providing and fixing washbasin with single hole for pillar
tap with C.I. or M.S. brackets painted white including
61 sutting holes and making good the same but excluding 4.00 1414.18 Nos.
fittings.(A) Vitreous China:(ii) Flat Back washbasin
mm x v 400mm size. (i) In white colour.
Providing and fixing chromium plated, bottle trap with
necessary couplings of approved quality for wash basin.
Providing and fixing C.P. brass waste for washbasin or
sink. (B) 40mm dia.
64 Concealed cock 15 mm Heavy duty with cap 4.00 491.30 Nos.
65 C.P. Angle stop cock 15 mm Heavy duty with cap 4.00 407.42 Nos.
66 C.P. Pillar cock 15 mm Heavy duty swan neck 4.00 647.95 Nos.
Providing and fixing S.W. gully trap with C.I. grating
brick masonary chamber and water tight C.I. Cover with
frame of 300mm x 300mm size ( inside ) with standard
weight. Square mouth traps
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing and laying (to level or slope) and jointing with
stiff mixture of cement mortar in proportion 1:1 salt glazed
stoneware pipes incl. testing of pipes and joints complete.
Constructing brick masonary chamber for underground
C.I. Inspection chamber and bends with bricks having
crushing strength not less than 35 Kg./Sq.Cm. In C.M. 1:5
C.I.cover with frame ( Light duty ) 455 mm x 610 mm
internal dimensions. Total weight of cover with frame to
be not less than 38 Kg. ( Wt. Of cover 23 Kg. ) and wt. Of
69 frame 15 Kg. ) ( R.C.C. top slab with 1:2:4 mix ( 1-cement 8.00 7180.44 Nos.
: 2-coarse sand : 4-graded stone aggregate 20 mm size )
foundation concrete 1:5:10 inside plaster 15 mm thick
with cement mortar 1:3 finished smooth with a floating
coat of neat cement on walls and bed conc.etc. comp.( iii )
inside dimension 600mm x 850 mm x 450mm deep for
pipe line with three or more inlets.
70 PVC SWR pipes IS 13592 for Drain - 110 mmdia 20.00 265.34 Rmt
71 PVC SWR pipes IS 13592 for Drain - 75 mmdia 20.00 144.65 Rmt
72 PVC SWR Single T" -110 mm dia With Door" 8.00 109.55 Nos.
73 PVC SWR Single T" -75 mm dia With Door" 8.00 59.05 Nos.
PVC SWR Piipe Bend 87.5 degree with door for 75 mm
PVC SWR Piipe Bend 87.5 degree with door for 110 mm
76 PVC SWR Piipe clamp 75 mm 16.00 8.55 Nos.
77 PVC SWR Piipe clamp 110 mm 16.00 12.84 Nos.
PVC SWR Piipe Bend 87.5 degree with door for 75 mm
PVC SWR Piipe Bend 87.5 degree with door for 110 mm
80 PVC SWR WC Connector 110 mm 8.00 128.39 Nos.
81 PVC SWR Vent Cowl 75 mm dia 4.00 9.41 Nos.
82 PVC SWR Vent Cowl 110 mm dia 4.00 19.68 Nos.
83 PVC SWR Piipe Bend 45 degree 75 mm dia 16.00 31.67 Nos.
84 PVC SWR Piipe Bend 45 degree 110 mm dia 16.00 59.05 Nos.
85 PVC SWR Double Y" - 75 mm dia With Door" 16.00 106.99 Nos.
86 PVC SWR Double Y" -110 mm dia With Door" 16.00 174.61 Nos.
Ball Valve ,Gun Metal Wheel Valve 40mm dia. (A)
Copper Metal ,(i) 40 mm dia.
Non Return Valve , Providing and fixing Gun metal check
88 or non-return fullway wheel valve.(E) 40mm dia.(E) 40 4.00 663.43 Nos.
Earthwork in cutting in all sorts of soil and soft murrum
including conveying and spreading the stuff, embankment
89 as and where directed within the estate from the end of the 1359.00 127.74 Cum
cutting with all required lead and lift as directed by
engineer in charge within the estate.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing and laying cement concrete 1:2:4 (1Cement : 2-
Coarse sand : 4- graded stone aggregates 20 mm nominal
size) and curing complete excluding cost of formwork in
(A) Foundation and Plinth
Providing and fixing pre-cast concrete kerb stone of gray
cement based concrete block 30cm length,30cm height and
15cm thick of M250 grade concret OF Vyara, Kuber and
91 Asian or equvilaent make as per approved design and 500.00 361.64 Rmt
including excavation for fixing in proper line and
level,filling the joint with C:M 1:3 (1cement:3fine sand)
Graded Granular sub base (GSB)
Providing & laying of compacted thickness of 250 mm
Closed Graded Granular sub base (GSB) in Two equal
layers (each layer should be less than 200 mm)of graded
granular material consisting of river sand, graval, pabbles
and crushed stone aggregate, shingle as per grading - V
given in table 400-1 of the specification MORT&H and
compactor to the required density with 8 - 10 tonne
vibratory roller with plain drum or heavy pneumatic tyred
roller of minimum 200 to 300 KN weight in all seasons as
per MORT&H , maintaining the required slope & grade
during the operation as approved by the engineer in charge
& watering to the proper moisture content and sprinkled
with the help of truck mounted water tank fitted with
suitable arrangement. (fully saturated having CBR value
Wet Mix Macadam (WMM)
Providing, laying, spreading and compacting graded stone
aggregate to wet mix macadam 250 mm thick spacification
including trimix the materials with water at OMC in
mechanical mix plant carriage of mixed materials by tipper
to site laying in uniform layers (Layer should not be more
93 than 200 mm)with paver in sub base/base course on well 755.00 2146.84 Cum
prepared surface and camber with Sensor paver
consolidation by vibratory road roller to achieve the
desired density by using machine crushed chips as per
required gradation mixing with required optimum quantity
of water incl material, labour, plant and machinary and
equipment etc. complete.
Providing and fixing pre-cast Rubber Dye / steel Dye inter
locking concrete block 60mm thick with grade of concrete
M300 pnumatic compressed / vibrated mechanically and
as per approved design
Confirming to IS 15658 : 2006 including 35 mm Sand
layer for levelling and filling the joint with sand in proper
line and level as per guidlines of IRC: SP 63-2018 etc.
Providing cement vata (10cm. x 10 cm. size) quarter round
95 in cement mortar 1:1 including neat cement finishing, 520.00 23.68 Rmt
watering etc. complete.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Filling in Foundation and plinth with murrum or selected
96 soil in layers of 20cm . Thickness including watering , 6040.00 289.06 Cum
ramming and consolidating etc. complete
Providing and laying controlled cement concrete M.200
and curing complete including the cost of formwork '(Only
fresh ply shall be use) but excluding cost of reinforcement
for reinforced concrete work in a) RCC Footing
b)RCC column 48.00 8611.53 Cum
c)RCC Beam 45.00 6445.68 Cum
d)RCC coping 33.00 6057.54 Cum
Providing in line level plumb, fabricating and fixing three
row horizontal barbed wire fencing and punched tape
concertina coil of 9 turns per meter of 610 mm diameter
fixied with clips on top of the angle iron posts. The
punched tape concertina coil having sharp barbs at every
25 mm spacing shall be 0.5 mm thick and 19 mm width
98 and weighting 13 Kg./100 mtr. (Average) as per 550.00 468.00 Rmt.
manufacture's specification. The rate shall also include
providing and fixed 1.20 mt. total long MS angle 40 x
x 6 mm @ 3.00 mt. c/c spacing embedded in RCC column,
angle posts shall be painted with one coats of red oxide
and two coats of enamel paint of approved quality at top
of compound wall.
Labour charges for writing of capital letter "AUDA" in
green plaster of 30 cm height, 25 mm thick and 12 mm
embossed as per given detail in outside of compound wall
as instructed by Engineer in charge.
Fabricating and fixing in position MS structural section
such as flat, pipes, plates, hold fast, anchoring bolts / bars
of required size including fixing, welding and two coats of
100 approved anti corrosive paint over prime coat of red-oxide 650.00 90.00 Kg
including RCC gate column as per drawing etc. complete
as directed by Engineer-in-charge. a)2.2 m height and 6 m
wide main and wicket gate
Box cutting the road surface to proper slope and camber
for making a base in all sorts of soil strata for road work
including removing the excavated stuff and depositing as
directed by engineer in charge within the estate. The item
is including dismanteling of flexible road/ RCC structure
if any as per instruction of Engineer In charge.
Scarifying gravelled macadam or bitumen macadam
surface 6 cm to 10 cm.depth including stacking useful
materials on road side and disposing off remaining stuff.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Earth work for subgrade of 500mm thick having CBR not
less then 8 using yellow earth brought from outside having
PI value less than 15 including breaking clods dressing
with all lead and lift and including watering rolling and
103 consolidation of sub-grade in layers not exceeding 200 27956.50 164.10 Sqm.
mm thickness at O.M.C to required dry density
including filling the depressions which occur during the
process using Vibratory roller 8 to 10 tonne capacity (D)
From Borrow area within 2.0KM. lead
Construction of granular sub-base by providing & laying
of compacted thickness of 300 mm Grading 5th Granular
sub base (GSB) in two layers of graded granular material
consisting of machine cut black trap stone aggregate as
per grading - V given in table 400-1 of the specification
MORT&H and compactor to the required density with
104 vibratory roller in all seasons as per MORT&H , 24609.68 2162.65 CUM
maintaining the required slope & grade during the
operation as approved by the engineer in charge &
watering to the proper moisture content and sprinkled with
the help of truck mounted water tank fitted with suitable
arrangement. (fully saturated having CBR value minimum
Providing, laying, spreading and compacting graded stone
aggregate to wet mix macadam spacification including
premixing the materials with water at OMC in mechanical
mix plant carriage of mixed materials by tipper to site,
laying in uniform layers (Layer should not be more than
200 mm)with paver in sub base/base course on well
prepared surface and camber with Sensor paver
105 consolidation by vibratory road roller to achieve the 14553.00 2464.37 CUM
desired density by using machine crushed chips as per
required gradation mixing with required optimum quantity
of water incl material, labour, plant and machinary and
equipment etc. complete by plant mix method. ( Using
mechanical paver ). The rate is including
excavation/cutting and levelling the surface before laying
WMM as directed by engineer in charge.
Providing and applying primer coat with bitumen emulsion
SS1 on prepared surface of granular Base including
clearing of road surface and spraying primer at the rate of
0.70 kg/sqm using mechanical means.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing & laying compacted 50 mm thick dense graded
bituminous macadam (DBM) Grade-II in Single layer using 100-
120 TPH batch type HMP with tack coat at the rate of 2.5 kg /
10 m2 (VG10) in each using crushed aggregates of specified
grading premixed with bituminous binder @ 4.5% ( VG - 40)
bitumen by weight of total mix and filler , transporting the hot
mix to work site laying with a hydrostatic paver finisher with
sensor control with full road carpet width (Single screed) or as
directed by Engineer in charge to the required grade, level and
alignment, rolling with smooth wheeled roller, intermediate
rolling 8-10 tonnes dead weight or vibratory roller & pneumatic
tire roller of 12 to 15 tonnes weight having sufficient width and
pressure & the finishing rolling shall be done with 6 to 8 tonnes
smooth wheeled tendem rollers to acheive the desired
compaction as per MORT&H specification etc complete in all
respects. The agency shall have to get the mix design done from
approved laboratory and submit to the Engineer in charge for
approval.(Va = 3.5% & Vbe= 11.50% must be considered in
mix design ) If the asphalt (bituminous) content is more than
above, the agency shall have to bear the cost of additional
asphalt. The payment shall be done on the permissible field
density achieved on the site instead of density derieved in the
mix design. ( The density obtained by mix design above
MT/M3 shall be boarn by agency )
Providing and laying compacted 40 mm thick Bituminous
Concrete ( BC ) Grade -II in single layer using 100-120 TPH
batch type hot mix plant and using asphalt as a tack coat @
kg / 10 sq.m (VG 10) in each using crushed stone aggregateof
specified gradation and filler, Premix with VG-40 grade
bitumenous binder at 5.40 % by total weight of mix & filler
incl. transporting the hot mix to work site and laying with
hydrostatic paver finisher having sensor control with Full road
carpet width ( Single screed) or as directed by Engineer in
charge to the required grade, level and alignment, rolling with
smooth wheeled roller, intermediate rolling 8-10 tonnes dead
weight or vibratory roller & pneumatic tire roller of 12 to
tonnes weight having sufficient width and pressure & the
108 finishing rolling shall be done with 6 to 8 tonnes smooth 5054.00 4830.52 MT
wheeled tendem rollers to acheive the desired compaction as
per MORT&H specification etc complete in all respects. The
agency shall have to get the mix design done from approved
laboratory and submit to the Engineer in charge for approval
(Va = 3.5% & Vbe= 11.50% must be considered in mix design
). If the asphalt (bituminous) content is more than above, the
agency shall have to bear the cost of additional asphalt. The
payment shall be done on the permissible field density achieved
on the site instead of density derieved in the mix design. ( The
density obtained by mix design above 2.36 MT/M3 shall be
boarn by agency )
Providing and applying asphalt painting with bitumen of
VG 40 grade on bitumenous surface including clearing of
road surface and spraying Bitumen at the rate of 0.60 kg /
sqm using mechanical means.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Road Marking with Hot Applied Thermoplastic
Compound with Reflectorizing Glass Beads on
Bituminous Surface by Providing and laying of hot
applied thermoplastic compound 2.50 mm thick including
110 reflectorizing glass beads @ 250 gms per sqm area, 12377.00 367.72 Sqm
thickness of 2.5 mm is exclusive of surface applied glass
beads as per IRC:35 .The finished surface to be level,
uniform and free from streaks and holes etc. complete as
Construction of dry lean cement concrete Sub- base over a
prepared sub-grade with coarse and fine aggregate
conforming to IS: 383, the size of coarse aggregate not
exceeding 25 mm, aggregate cement ratio not to exceed
15:1, aggregate gradation after blending to be as per table
111 600-1, cement content not to be less than 150 kg/ cum, 393.80 2991.75 Cum
optimum moisture content to be determined during trial
length construction, concrete strength not to be less than
10 Mpa at 7 days, mixed in a batching plant, transported to
site, laid with a paver with electronic sensor, compacting
with 8-10 tonnes vibratory roller, finishing and curing.
Construction of un-reinforced, dowel jointed, plain cement
concrete pavement over a prepared sub base with approve
grade cement @ 400 kg per cum, coarse and fine
aggregate conforming to IS 383, maximum size of coarse
aggregate not exceeding 25 mm, mixed in a batching and
mixing plant as per approved mix design, transported to
site, laid with a fixed form or slip form paver, spread,
compacted and finished in a continuous operation
including provision of contraction, expansion,
construction and longitudinal joints, joint filler, separation
membrane, sealant primer, joint sealant, debonding strip,
dowel bar, tie rod, admixtures as approved, curing
compound, finishing to lines and grades as per
drawing.For M-350
Providing and laying cement concrete 1:5:10 (1- Cement :
5-Coarse sand : 10- hand broken stone aggregates 40 mm
nominal size) and curing complete excluding cost of
formwork in (A) Foundation and Plinth
RCC precast M.H. Frame & Cover Manufacture, supply &
Delivery at store or at site of work precast RCC M.200
Frame & cover suitable to drainage M.H. and as per type
design & Drawing including cost of reinforcement
M.S.Angles or Flat, curing mold work etc.
House Connection Chamber light duty A) Frame
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing and laying cement concrete work 1:2:4 (1-
Cement : 2- Coarse sand : 4- graded stone aggregates
mm nominal size) and curing complete excluding cost of
formwork and reinforcement for reinforced concrete work
in (B) Slabs, landing, shelves, Balconis , Lintels, Beams,
Girders and Cantilever upto floor two level.
Providing formwork of ordinary timber planking so as to
give a rough finish including centering shuttering strutting
and propping etc. height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and
removal of the same for in situ reinforced concrete and
plain concrete work in. (H) (1) Sides and soffits of Beams
Beam Haunchings cantilevers Girders Bressumers and
Lintels not exceeding 1 M. in Depth.
Providing and laying cement concrete work 1:2:4 (1-
Cement : 2- Coarse sand : 4- graded stone aggregates
mm nominal size) and curing complete excluding cost of
formwork and reinforcement for reinforced concrete work
in (A) Foundations, footings, Base or columns and Mass
concrete For Benching
Providing and casting in situ C.C. in grade M-20
(proportions as per mix design or as per table9 of IS456
2000 in masses by weigh batching ) using granite,
quartzite trap metal of size 6 mm to 20 mm for RCC work,
118 including scaffolding centering, formwork, needle vibrated 121.00 6085.80 Cum
consolidation, curing complete up to 6 meter depth or
height (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. complete
for structure other than water retaining (Below G.L)
Excavation for pipe line trenches for water supply,
sewerage line, manhole etc. all with shoring and struting if
required as per required gradient and line including safety
119 provisions using site rails and stacking excavated stuff
including up to all required lead cleaning the site etc.
complete for all lifts and strata as specified.
In all sorts of soil and soft murrum
(A) Upto 1.5 Mt. dpt.from G.L. 168658.16 102.35 Cu.M.
(C) 3.0 Mt TO 4.50 Mt depth 24920.00 118.45 Cu.M.
(D) 4.5 Mt. TO 6.00 Mt. Depth 6030.00 125.35 Cu.M.
(E) 6.0 Mt TO 7.50 Mt depth 640.00 129.95 Cu.M.
Providing and supplying D. I. pipes for following nominal
bore diameter with internal cement mortar lining
including all taxes, insurance, transportation, freight
charges, octroi, inspection charges, loading, unloading,
120 conveyance to departmental stores, stacking etc. complete.
(IS 8329-2000). For sewerage project cement mortor
lining shall be with sulphate resistance cement.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
500 mm Dia (DI PIPE K-9) 3733.00 7909.00 Rmt
600 mm Dia (DI PIPE K-9) 2641.00 10309.00 Rmt
250 mm Dia (DI PIPE K-9) 1869.00 2998.00 Rmt
(All type of fittings) Providing and supplying at store or
site of work incl. freight, loading, unloading, stacking,
121 insaurance & all taxes etc. complete
Rate for Specials Upto 300mm dia 2271.59 148.00 Kg
Rate for Specials Above 300mm dia 22549.81 151.00 Kg
Lowering, laying and jointing C. I. S & S Spun pipes
suitable for Tyton joints / Mortar lined D. I. Pipes of
various classes with CI / MS specials of following
122 diameters in proper position, grade and alignment as
directed by Engineer-in-charge including hydraulic testing
etc. comp. (tyton Joint)
500 mm Dia (DI PIPE K-9) 3695.00 358.80 Rmt
600 mm Dia (DI PIPE K-9) 2590.00 464.60 Rmt
250 mm Dia (DI PIPE K-9) 1850.00 146.05 Rmt
Providing and supplying ISI mark CI D/F Sluice Valves as
per IS:14846 (Latest Edition) of following class and
diameter including all taxes, insurance, transportation,
123 freight charges, octroi, inspection charges, loading,
unloading, conveyance to departmental stores, stacking
500 mm Dia PN-1 With gear operated (PD type short
body) Sluice valve
600 mm Dia PN-1 With gear operated (PD type short
body) Sluice valve
250 mm Dia PN-1 With gear operated (PD type short
body) Sluice valve
providing and supplying C. l. Air valves of approved
make & quality of following class and diameter including
all taxes, insurance, transportation, freight charges, octroi,
inspection charges, loading, unloading, conveyance to
departmental stores, stacking etc. complete.
100 mm Dia Air valves double acting (DS2) 6.00 5267.00 No
150 mm Dia Air valves double acting (DS2) 4.00 12384.00 No
80 mm Dia Air valves double acting (DS2) 3.00 3660.00 No
Lowering, laying and jointing in position following C. I. /
D/F Reflux valves, Butterfly valves, Sluice valves and Air
125 valves including cost of all labour, jointing material,
including nut bolts and giving satisfactory hydraulic
testing, etc. complete.
500 mm Dia PN-1 With gear operated (PD type short
body) Sluice valve
600 mm Dia PN-1 With gear operated (PD type short
body) Sluice valve
250 mm Dia PN-1 With gear operated (PD type short
body) Sluice valve
100 mm Dia Air valves double acting (DS2) 6.00 604.90 No
150 mm Dia Air valves double acting (DS2) 4.00 695.75 No
80 mm Dia Air valves double acting (DS2) 3.00 472.65 No
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Constriuction of Valves Chamber in Brick or bela stone
masonary,locally available in CM 1:6 foundation concrete
150mm thick in C.C 1:4:8 of trap metal size 25mm to
40mm thickk cement plaster in C.M. 1:3 and cement
pointing outside in CM 1:3 and top cover of precast RCC
slab 100 mm thick(with key hole in two parts with handels
or MS bar etc. comp. as given size) up to 1 meter depth
126 from Gl to pipe invert level including comp. civil work but
excluding cost of excavation & refilling with cast in situ
RCC slab in one single piece with fixing of CI -MH
frame & cover (excluding. cost of CI MH-frame & cover)
with 23 mm thick brick wall in C.M 1:6
Size of chamber 0.90 m x 0.90 m and 1.0 mt. deep With
precast slab in two parts 15 mm
Providing and supplying ISI Standard R.C.C. pipes(of
Sulphate Resisting Cement) in standard lengths of
following class and diameter suitable for either collar
127 joints or rubber ring joints including all taxes, insurance,
transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to departmental stores,
Note : One collar should be supplied with each full length
plain ended RCC pipe, cost included in rates below. One
rubber ring should be supplied with each full length
socketed pipe, cost included in rates below.
(D1) 300 mm dia (NP3 Class) 51570.00 755.00 Rmt.
(D2) 300 mm dia (NP4 Class) 10292.00 1087.00 Rmt.
(E1) 350 mm dia (NP3 Class) 787.00 879.00 Rmt.
(E2) 350 mm dia (NP4 Class) 1741.00 1379.00 Rmt.
(F1) 400 mm dia (NP3 Class) 759.00 1150.00 Rmt.
(F2) 400 mm dia (NP4 Class) 837.00 1873.00 Rmt.
(G1) 450 mm dia (NP3 Class) 380.00 1361.00 Rmt.
(G2) 450 mm dia (NP4 Class) 626.00 2179.00 Rmt.
(H1) 500 mm dia (NP3 Class) 354.00 1485.00 Rmt.
(H2) 500 mm dia (NP4 Class) 24.00 2337.00 Rmt.
(I1) 600 mm dia (NP3 Class) 1174.00 1946.00 Rmt.
(I2) 600 mm dia (NP4 Class) 1171.00 2994.00 Rmt.
(J1) 700 mm dia (NP3 Class) 551.00 2879.00 Rmt.
(J2) 700 mm dia (NP4 Class) 908.00 3900.00 Rmt.
(K1) 800 mm dia (NP3 Class) 25.00 3175.00 Rmt.
(K2) 800 mm dia (NP4 Class) 139.00 5575.00 Rmt.
(M1) 1000 mm dia (NP3 Class) 9.00 4821.00 Rmt.
(O1) 1200 mm dia (NP3 Class) 30.00 5899.00 Rmt.
(P1) 1400 mm dia (NP3 Class) 946.00 7587.00 Rmt.
(Q1) 1600 mm dia (NP3 Class) 387.00 11167.00 Rmt.
(R1) 1800 mm dia (NP3 Class) 1059.00 13608.00 Rmt.
Lowering, laying and jointing R. C. C. pipes in C. M. 1:1
1/2 of following diameters in proper position, grade and
alignment at all level as directed by Engineer-in-charge
128 including conveyance from stores to site of work, labour,
giving hydraulic testing as per ISI code.
(D1) 300 mm dia (NP3 Class) 51570.00 136.85 Rmt.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
(D2) 300 mm dia (NP4 Class) 10292.00 136.85 Rmt.
(E1) 350 mm dia (NP3 Class) 787.00 152.95 Rmt.
(E2) 350 mm dia (NP4 Class) 1741.00 152.95 Rmt.
(F1) 400 mm dia (NP3 Class) 759.00 174.80 Rmt.
(F2) 400 mm dia (NP4 Class) 837.00 174.80 Rmt.
(G1) 450 mm dia (NP3 Class) 380.00 196.65 Rmt.
(G2) 450 mm dia (NP4 Class) 626.00 196.65 Rmt.
(H1) 500 mm dia (NP3 Class) 354.00 217.35 Rmt.
(H2) 500 mm dia (NP4 Class) 24.00 217.35 Rmt.
(I1) 600 mm dia (NP3 Class) 1174.00 262.20 Rmt.
(I2) 600 mm dia (NP4 Class) 1171.00 262.20 Rmt.
(J1) 700 mm dia (NP3 Class) 551.00 308.20 Rmt.
(J2) 700 mm dia (NP4 Class) 908.00 308.20 Rmt.
(K2) 800 mm dia (NP4 Class) 164.00 347.30 Rmt.
(M1) 1000 mm dia (NP3 Class) 9.00 431.25 Rmt.
(O1) 1200 mm dia (NP3 Class) 30.00 506.00 Rmt.
(P1) 1400 mm dia (NP3 Class) 946.00 586.50 Rmt.
(Q1) 1600 mm dia (NP3 Class) 387.00 663.55 Rmt.
(R1) 1800 mm dia (NP3 Class) 1059.00 747.50 Rmt.
Providing & Constructing Precast RCC Manhole in RCC
M-40 grade Controlled concrete as per drawing, in OPC
including excavation, 80 mm thick P.C.C. in M-15,
129 Reinforcement in TMT-500, PVC Foot steps, Providing &
fixing FRC Manhole frame & cover including inside
epoxy paint complete etc.
For 250 mm to 600 mm Dia. Pipe ( Upto 4.0m Depth)
For 250 mm to 600 mm Dia. Pipe ( Above 4.0m Depth)
1.5 m Dia.- 4.01 m to 4.99 m Depth 59.10 9779.00 Rmt.
1.5 m Dia.- 5.01 m to 5.99 m Depth 30.40 11341 Rmt.
1.5 m Dia.- 6.01 m to 6.99 m Depth 12.40 11400 Rmt.
1.5 m Dia.- 7.01 m to 9.99 m Depth 0.50 15296 Rmt.
1.8 m Dia.- 5.01 m to 5.99 m Depth 3.70 14744.00 Rmt.
Providing and erecting C. I. and MS ventilating columns
15 cms. dia. with C.I. ornamental cap and Min 6.00 Mtr.
Height (Height may be varying as per site) base fixed
firmly with necessary foundation with one coat of red lead
oxide paint and one coat of any approved colour with
130 cms, dia.10 Mt.in length with 0.35mt*0.35mt* M100
Encasing, M.S pipe connection with M.H. including
excavation and jointing as required etc. complete. as per
drawing and Fixing inposition
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
For 6 Mtr. Height ( 6 Mt MS pipe) 225.00 38911.40 No.
Dewatering by pumping set of required capacity including
temporary platform carting pumping at site and fixing the
131 same in position including all accessories, and fuel and 9600.00 21.07 HP/Hr
labour etc. complete.
Shoring or timbering for trench with 50 mm thick planks
and suitable size struts etc. complete.
Refilling the pipeline trenches incl. ramming, watering,
consolidating desposal of surplus stuff as directed within a
radius of 3 km.do- with selected soil brought from outside
including all lead
do- with selected soil brought from outside including all
Drilling of 900mm dia Horizontal borehole for watermain
pipeline under the railway tracks incl all strata with
requried length incl fixing of 800mm dia M.S.casing pipe
of minimum 12mm thick Or IRS Casing Pipe with welding
pushing etc complete Providing & fixing various size of
pipe for 406.4 mm/457mm/508mm dia watermain of
G.I/M.S pipe of minimum 6.3mm thick for railway
permises as per instruction & regulations of Railway
authority & under supervision of Railway authority incl
Provinding & suppllying fixing of spacer at specified
interval if required between Casing pipe and water main,
ISI make sluice valve of required size at both side of
railway boundry with construction of brickedge pavement
incl C:C encasing 1:3:6 in 10mtr length of pipe at both
side. Incl Provinding & fixing of M.S/Iron Manhole frame
with cover for valve chamber with loacking arregment etc.
complete with all material labour fabrication,hydralic
testing of pipe & valve etc complete for 45 mt
Length.which includes horizontal pushing and with open
Without Water main & with MS Casing Pipe 100.00 29026.87 Rmt
Drilling of 900mm dia Horizontal borehole for watermain
pipeline crossing under the road incl in all strata with
135 requried length incl fixing of 800mm dia M.S/RCC casing
pipe with pushing etc complete various size of pipe for
406.4 to 508mm dia watermain
Without Water main & with MS Casing Pipe-800 thick:12 30.00 25712.67 Rmt
Drilling of 1300mm dia Horizontal borehole for
watermain pipeline crossing under the road incl in all
strata with requried length incl fixing of 1200mm dia
M.S/RCC casing pipe with pushing etc complete various
size of pipe for 559 to 711mm dia watermain. (for 45 Mtr.
Without Water main & with MS Casing Pipe-1200
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Drilling of 600mm dia Horizontal borehole for pipeline
crossing under the road incl in all strata with requried
length incl fixing of 400mm dia M.S/RCC casing pipe
137 with pushing etc complete various size of pipe for 273.1 to
355.6 mm dia (For 45 mt Length)
Without Water main & with MS Casing Pipe 1294.00 13344.78 Rmt
Drilling of Horizontal bore hole for water main pipeline
under the Railway / Road tracks in all strata with required
length including fixing of M.S.(or as specified by Railway
/ Road authority) casing pipe of suitable size and
Thickness. Rate includes the cost of Drilling of bore hole
Casing pipe & welding pushing etc complete but
excluding the cost of water main, valves and other items.
Entire work should be as per Approved Drawing and as
per instruction of Railway / Road authority for Following
diameter of Bore hole. for MS pipe
Horizontal Drilling-600:& MS Casing Pipe-500 thick:8 24.00 10540.90 Rmt
Drilling of Horizontal bore hole for water main pipeline
under the Railway / Road tracks in all strata with required
length including fixing of M.S.(or as specified by Railway
/ Road authority) casing pipe of suitable size and
Thickness. Rate includes the cost of Drilling of bore hole
Casing pipe & welding pushing etc complete but
excluding the cost of water main, valves and other items.
Entire work should be as per Approved Drawing and as
per instruction of Railway / Road authority for Following
diameter of Bore hole. for MS pipe
Horizontal Drilling-2100:& MS Casing Pipe-2000 thick: 36.00 81551.95 Rmt
Construction of cast in situ RCC manhole of 1500 mm
internal diameter and 3 m depth (upto invert of manhole)
140 in M 30 CC grade with opening of 1.2 m for MH cover. 1.00 258876.5 Rmt
Without MH cover
HDPE DWC Pipe : Providing and supplying of Class SN8
Structured Wall polyethelene Piping systems (Pipe with
online/offline coupler and elastomeric sealing ring) with
non-smooth External Annular Corrugated and Smooth
Internal Surfaces (Double Wall) for non-pressure
141 underground Sewerage & Drainage application as per
EN:13476-3 including all local and central taxes,
transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores
etc. complete.(ID Dia)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Lowering, laying and jointing of class SN 8 structured
wall ( External Annular Corrugated & Smooth Internal
surface) Polyethylene Piping and fittings with the help of
coupler ( on line / off line ) attached with one end of pipes,
sliding over the elastomeric sealing rubber ring placed on
the specified valley of the corrugation at the spigot end,
lowering the same into the trench at all level, laying on the
lower bedding (constructed at bottom of trenches) at
142 prescribed gradient,depth & alignment ,testing the water
tightness of the joints, ensuring the continuity tests of
specified pipe segments etc. complete as per
drawing,specifications & detailed engineering, including
carriage of pipes & fittings from site stacks to the place of
laying etc. as per direction of Engineer-in-charge.
Sequential Batch Reactor Technology (SBR
TECHNOLOGY) - 30 MLD
Designing, providing, constructing, hydraulic testing,
commissioning and giving satisfactorily trials of STP
consisting of Inlet Chamber, Screen
Chamber, Detritus Tanks, Distribution Chamber and SBR
Basins, Sludge Sump, Chlorine Contact Tank, Chlorinator
Room / Shed, Sludge
Dewatering Equipment, necessary piping work with
required valves, gates, drains, pathways, Administration
Block cum Laboratory,
Laboratory Equipments, Internal Roads, Pathways,
143 compound wall, Tools and Plants, complete as turnkey job
with all involved civil, electrical,
instrumentation and mechanical works inclusive of
following items, units as per detailed specifications for
civil, electrical and mechanical
components with all duties and taxes etc. complete to
achieve BOD < 10ppm, TSS < 10ppm,Biological TN <
10ppm & PO4 < 2ppm to get
recyclable quality of water for industrial / agricultural
purposes. The Coagulant Dosing System shall be provided
as an optional/ back up. All units shall be interconnected
with administration building by Suitable or RCC overhead
UNITS INCLUDED:
* PRIMARY TREATMENT
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Inlet Chamber :
Designing, providing, and constructing RCC (M:30) inlet
chamber for the peak flow as per CPHEEO Manual
including necessary excavation in
all types of strata including walkway all around the
periphery. Inlet chamber having minimum HRT of
seconds, each compartment will have
steel gates with extension rod, head stock operating
wheels. GI pipe railing etc. The work includes providing
and making necessary
arrangements to connect the flow to screen chamber by
approach channel as directed and as per specifications.
Screen Chamber :
Designing , providing, constructing, testing and
commissioning of Two approach channels (min 4.5 m
long), mechanically cleaned bar rack
screen (6 mm clear opening 10 mm the. flats), Escalator
screens, with 100% standby manual fine screen (10 mm
clear opening) MOC: SS316,
CI sluice gates (one before screen & one after screen)
designed fast per CPHEEO Manual in RCC (M -30),
including inlet pipe/ channel
from inlet chamber, outlet pipe / channel to detritus tank,
free board of 0.5 m minimum, RCC walkway 1.2 m wide
with GI pipe railing. RCC
stair case of 1.2 m width from GL to screen chamber. with
operating platform and belt conveyor system incl. panel &
push bottom switch at
local level as well as MCC room for two way control.
Designing, providing and constructing grit Chamber-
Detritus or vortex type or aerated type (100% standby),
mechanically operated in RCC (
M 30) capable of removing 100% of 0.2 mm size particle
and above, having specific gravity 2.40, HRT of 1 minute
at average flow (Detritus
Tank), horizontal velocity not exceeding 0.30 m/sec
(Detritus Tank) at peak flow with suitable arrangement of
separation of grit from
putrescible solids. Inlet and outlet channels of required
sizes as may be required to connect the flow to connecting
unit etc. Complete including
hydraulic testing for water tightness of structure having
minimum FB of 0.3 m, wash out arrangement to Grit
chamber and platform 1.2 m wide
RCC walkway with GI pipe handling shall be provided. A
pit for collecting grit conveyed by conveyor shall be
provided. It should be suitable to
handle the grit for carting. All arrangements shall be as
detailed specifications and as directed.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Parshall flume having head loss limited to 0.15 m with
necessary flow measuring devices/meter consisting of
digital indicator in LPS & MLD
SECONDARY TREATMENT
Designing, providing and constructing in RCC (M 300),
CASP basins for biological removal of BOD along with
built-in nitrification-denitrification,
Bio-P removal in compartments to handle combine flow of
1 DWF incoming flow and recirculation flow including
construction of
selector compartments and providing 1.2 m wide clear
approach walkways, expansion joints wherever necessary,
including foundations etc as
per specifications. Peak factor shall be 2, F/M ratio shall
be 0.15, complete with air blowers, fine diffused aeration
grid with Retrievable type
installation equipment and FB 0.5 m and SWD as
required. DO level in basin to be minimum 2 mg/l
complete with "Oxygen Uptake Rate"
control system and all related instruments, Stainless steel
decanters and automation works. MLSS concentrations
shall be 3000 - 5000 mg/l or
more, MLVSS to MLSS ratio to be 0.6-0.7. HRT shall be
min. 13.5 hrs and SRT suitable for fully digested sludge.
SBR process shall have
independent steps like Fill & aeration,
Settling(Sedimentation/clarification), Decanting without
overlapping each other. Since it is complete
batch process, filling will not be acceptable during settling
or Decanting. Minimum decanting depth shall not be less
than 2.20 m. The system
should work on a gravity influent condition. No
influent/effluent equalization tanks or flash filling is
accepted. It should have all other related
SRT shall be suitably provided to achieve N, P removal.
Since these are the technology driven plants, bidders has
to adopt well established,
well tested and proven, IIT/ NEERI evaluated/approved
SBR process /specifications and at least 50 % of the
tendered capacity has been in
successfully operating condition as per the outlet criteria
mentioned in above in Government organizations of India
since last two years
including one year of standard defect liability period.
Bidder has to tie-up with the well qualified technology
provider who having experience in
India at least 50 % of the tendered capacity with 1 year O
& M experience in government organizations of India.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Process Air Blowers or aeration Device
The Plant should be based on Dissolved Oxygen/Oxygen
Uptake Rate Control with VFD driven Aeration Device.
The Aeration System shall be
designed for 110 % Capacity of the design Air
requirement. The aeration Blower/Aeration Device shall
be having 100% installed standby unit.
Air diffuser shall be of disk/ tubular type, retrievable. The
wetted part of the aeration system of non-corrosive
materials such as UPVC.
Blowers shall be housed in process air blower building.
The minimum area of the building is 20 sq.m. and height
of 5m (min). Blowers shall be housed in process air
blower building. The minimum area of the building is
sq.m. and height of 5m (min).
Raw sludge pump house:
Raw Sludge Sump minimum HRT of 30 minutes & depth
of sludge limited to 2 m, 4.5 m minimum diameter,
separate panel room outside the
Chlorine Contact Tank:
Designing providing and constructing chlorine contact
chamber of adequate capacity to deal with 1 DWF average
flow. The chlorine contact
tank should be of 30 min capacity, during average flow to
achieve 99.99 % coliform reduction. Chlorine dose shall
be maintained as per
standard provisions, including designing, providing and
constructing water supply provision for chlorination,
including providing dewatering
and by pass arrangement jointing to final effluent mains
and outlet weir etc complete. The effluent quality should
match with the standards laid
down by Gujarat pollution control board and as per
obligatory provision and as detailed specification and as
directed by engineer in - charge.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Chlorinator and Chlorinator Room/Tonner Room:
Designing, providing and constructing chlorinators
vacuum type 2 Nos, (1 working+ 1 stand by) with auto
switchover facility and having
capacity for dosage of adequate chlorine to ensure
% coliform reduction as per obligatory provisions and
detailed specifications with
necessary provision of having chlorinator room of
adequate size. The chlorinator equipment shall include
cost of chlorine cylinders/tonner,
piping, valves, measuring and controlling equipment,
safety devices , lifting equipment, etc. complete as per IS -
10553 ( part II) 1982. The
tonner room should have minimum 3 MT capacity Hoist
for loading and unloading facility. Tonner storage should
be distinctly isolated and
should be for minimum storage space as directed in the
design specification and as per gas laws 1981 and factory
act shall be provided. All
other matching amenities shall be provided, Minimum
MT gantry rail shall be provided for full length of tonner
room at 6 m height from level
of tonner room, with outlet chamber and treated effluent
outlet channel etc complete as per detailed specification.
Sludge treatment
Sludge Thickner with equipments:
Solids loading rate of 25-35 kg/m2/day, Designing,
providing & constructing watertight of sludge thickener-
gravity type (picket fence) in RCC
(M-30) with inlet & outlet pipes, central feed well, sludge
it & sludge removal arrangement, grouting wherever
necessary with walkway all
around of 1.20m with GI pipe railing interconnecting CI
pipes all complete as per specifications, having bottom
slope 1:6 & min. 4.5m SWD
with necessary fixed bridge scraper arrangement as per
detailed specifications & necessary inlet & outlet
arrangement. All other arrangement
as per detailed specifications. (One unit upto 10 MLD and
two units for more than 10 MLD). Min sludge
concentration in thickened sludge shall
Sludge Holding Sump :
Designing, providing and constructing of sludge sump and
pump house of appropriate size with pumps, ceiling height
minimum 6 m over sump
for discharging sludge to centrifuge using CI pipe
complete as per detailed specification.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Sludge Dewatering Equipment Room with Centrifuge
or belt press or screw press or Filter Press or Combi-
machine or Bag Type:
Designing, providing constructing and installing including
foundation etc. Centrifuge or belt press or screw press or
Filter Press or Combimachine
or bag Type to handle the sludge flow as per
specifications, with appropriate inlet and outlet provision,
sludge dewatering unit drain
etc. Complete as per specifications.
Sludge/ filtrate Pumps
a) Capacity to pump sludge in 1 hour with 100% standby
(20-25% efficiency, "C" value to be adopted 50% than that
of water to calculate
b) Filtrate from thickening and dewatering to be conveyed
only by PVC 10 kg/sq.cm.
Inlet, outlet ,wash water inlet – only CI D/F and minimum
size of 200 mm as per approved make/brand.
All types gauges and meters required for O & M as per
design of specified make/brand.
Necessary Instrumentation and control as per
Designing, providing and constructing appropriate outfall
sewer of RCC NP2 pipe, to discharge treated effluent from
outlet chamber after
chlorination tank to the disposal point at outlet battery
limit of STP including necessary chambers for inspection
and cleaning including
necessary excavation, dewatering, refilling, concrete
encasing/bedding concrete steps to reach the disposal/
nallah bed level. pitching and
energy dissipation chamber in nallah portion etc. complete
up to 500 m length RCC NP2 pipe line and including all
By pass arrangements
RCC pipes with manholes and C.I. sluice gates (MH to be
raised above TWL of adjacent unit)
Piping work in CI-LA Class including Sluice valves,
Reflux Valves, MS Gates:
Providing laying and jointing pipes other than those
already included in the above items for interconnection by -
pass drains etc. of all units
including adequate numbers of manhole chambers. The
item includes excavations, refilling and hydraulic testing
of pipes, valves, gates,
accessories and cost of jointing materials. The items
includes required channels with gates for interconnection
of units by pass drains etc for
all units as directed etc complete as per detailed
specifications.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Administrative Building cum Laboratory (G+1):
Designing, providing and constructing administrative
building, office cum Laboratory including stores. This
shall be a building having
appropriate carpet area and ground floor and at first floor
complete as per specifications including necessary
excavation, foundation in RCC M
200 framed structure B. B masonry (11- class in C.M. 1:6)
20 mm cement plaster in C.M 1:3 inside and outside
painting. Aluminium door and
window with glass panels, mosaic tile flooring and skirting
and all other allied items, fixtures fastening electrification
arrangement water supply
arrangement etc complete.
a) Ground floor to accommodate administrative office &
b) First floor to accommodate Office of the Plant In
Charge, air monitoring equipments to
measure wind direction & speed, hydrogen sulphide
concentration etc.
Laboratory equipments
Laboratory equipment (as per specifications),
beautification, telephone and intercom arrangement
and wireless system.
Furniture and Office Equipments, Office furniture
(Make: Godrej/ or similar approved quality) as
per specifications
Ventilation and Safety equipments as per
Sanitary blocks
Carpet area – 15 square meter minimum up to 25 MLD
and 25 square meter above 25 MLD (or as
Maintenance Workshop of size as per specification
Air blower Building with Air Blowers:
Capable of delivering adequate free air for aeration device
with suitable pressure (100% standby).
MCC Room of minimum 9 m x 6 m clear inside with
safety measures, approval of various
statutory/ central/ foreign authority as applicable
Electric installation
Both internal and external including entire plant area (as
Electric installation - Sub Station Room as per
specifications.
DG room with DG sets, as per electric load and
specifications (50 % energy requirement).
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
General Infrastructure Development:
Scope also includes, Designing, providing and
constructing general infrastructure development such as
internal roads of minimum 6 mtr wide,
compound wall for STP site, internal street and building
lightings, pathways of minimum 1 m wide to access all
STP units and Entrance Gate in
MS fabrication, etc. all complete as per specifications and
directed by engineering in charge.
Asphalt road (Minimum 4.5 m) to connect all units from
main gate of plot.
Compound Wall as per the plant layout, long the boundary
of STP site (considering plant layout
for intermediate and ultimate build out capacity and 33%
landscaping area).
Green Belt (33% landscaping area) as per specification
Capacity of Plant (MLD)
Cost of 30 MLD treatment plant 1.00 252589450.00 No
1. Fine screens (SS 316) are of mechanically cleaned type for
working unit and manual bar screen type (SS 316) for standby
2. Upto 5 MLD Capacity STP chlorination may be done by
using sodium hypochlorite solution. Above 5 MLD capacity gas
chlorinator to be
3. Gravity sludge thickener is not provided upto 3 MLD
capacity STP. Sludge will be collected into sludge sump &
pumped directly to sludge
dewatering system.
4. Filter press or Bag Type dewatering can be provided for
STP's upto 5MLD capacity.
5. Chlorinator room not provided for STP upto 3 MLD.
6. Boundary wall, gate, Internal plant roads, storm water drains,
site clearance, landscaping is considered in scope. Plant road
7. All water retaining structures are in M-30 grade of concrete.
8. Lead for excavation is considered as 500m.
9. Grade of steel used is Fe
10. Peak factor considered for design for plants 2 to 5 MLD is
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
11. The rates mentioned above STP are considering sites
falling in Seismic Zone III.
12. Structural design criteria approved by technical
committee shall be applicable for design.
13. Hydraulic design of the plant shall be considered with
free fall discharge of treated sewage to local water body
(above HFL). Hydraulic loss
shall be worked out for peak flow condition and shall not
exceed 4.5m in any circumstances unless otherwise site
specific condition and
approved by technical committee.
14. The cost of sewage pumping station and rising main is
15. Makes of equipment shall be approved by
16. The rates includes excavation, refilling and throwing
away extra stuff as directed by the Engineer in Charge.
17. All other details shall be as per design criteria and
detail specifications.
Filling in Foundation and plinth with murrum or selected
soil in layers of 20cm . Thickness including watering
ramming and consolidating etc. complete as per instrcuted
by Engineer In Charege
SUBMERSIBLE SEWAGE NON-CLOG VERTICAL
Supply, Installation, Testing and Commissioning (SITC)
of Non-clog submersible pump of following duty
parameters along with LV AC submersible induction
motor air filled dry type pump-motor set shall be of
materials of construction and must have all required
accessories viz. automatic coupling device, double guide
pipes, chain with shackles, Submersible Power & control
cable (copper flexible & stranded type conductor of reqd.
cores & size for each pump motor set) & length of 20 m
long each run with necessary electrical termination
connection at junction box / starter panels, RCC
foundation with duck foot bend for auto coupling &
delivery bend and PMU etc. as per equipment data sheet
and detailed technical specifications and also including in
scope any other parts / accessories / fittings required to
complete the work in all respects & satisfactory operation
Capacity: 410 m3/hr,
Induction Motor rating mini. 75 kW or as per
For MPS-1 TO STP
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SUBMERSIBLE SEWAGE NON-CLOG VERTICAL
Supply, Installation, Testing and Commissioning (SITC)
of Non-clog submersible pump of following duty
parameters along with LV AC submersible induction
motor air filled dry type pump-motor set shall be of
materials of construction and must have all required
accessories viz. automatic coupling device, double guide
pipes, chain with shackles, Submersible Power & control
cable (copper flexible & stranded type conductor of reqd.
cores & size for each pump motor set) & length of 20 m
long each run with necessary electrical termination
connection at junction box / starter panels, RCC
foundation with duck foot bend for auto coupling &
delivery bend and PMU etc. as per equipment data sheet
and detailed technical specifications and also including in
scope any other parts / accessories / fittings required to
complete the work in all respects & satisfactory operation
Capacity: 419 m3/hr,
Induction Motor rating mini. 55 kW or as per
SUBMERSIBLE SEWAGE NON-CLOG VERTICAL
Supply, Installation, Testing and Commissioning (SITC)
of Non-clog submersible pump of following duty
parameters along with LV AC submersible induction
motor air filled dry type pump-motor set shall be of
materials of construction and must have all required
accessories viz. automatic coupling device, double guide
pipes, chain with shackles, Submersible Power & control
cable (copper flexible & stranded type conductor of reqd.
cores & size for each pump motor set) & length of 20 m
long each run with necessary electrical termination
connection at junction box / starter panels, RCC
foundation with duck foot bend for auto coupling &
delivery bend and PMU etc. as per equipment data sheet
and detailed technical specifications and also including in
scope any other parts / accessories / fittings required to
complete the work in all respects & satisfactory operation
Capacity: 469 m3/hr,
Induction Motor rating mini. 75 kW or as per
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SUBMERSIBLE SEWAGE NON-CLOG VERTICAL
Supply, Installation, Testing and Commissioning (SITC)
of Non-clog submersible pump of following duty
parameters along with LV AC submersible induction
motor air filled dry type pump-motor set shall be of
materials of construction and must have all required
accessories viz. automatic coupling device, double guide
pipes, chain with shackles, Submersible Power & control
cable (copper flexible & stranded type conductor of reqd.
cores & size for each pump motor set) & length of 20 m
long each run with necessary electrical termination
connection at junction box / starter panels, RCC
foundation with duck foot bend for auto coupling &
delivery bend and PMU etc. as per equipment data sheet
and detailed technical specifications and also including in
scope any other parts / accessories / fittings required to
complete the work in all respects & satisfactory operation
Capacity: 159 m3/hr,
Induction Motor rating mini. 30 kW or as per
MPS TO KARAI NETWORK
Supply, Installation, Testing and Commissioning of ISI
mark CI D/F Sluice Valve as per IS 14846 PN 1.0 with
Manually / Electrically Gear operated of following sizes
with SS 304 seat rings, SS rising spindle with all hot
dipped galvanised hardwares, bolts, nuts & washers,
gaskets including all taxes, insurance, transportation,
148 freight charges, Inspection Charges, loading unloading, 6.00 170535.00 No.
conveyence to pump house, stacking, security etc.
complete as per IS and Specification.
Size: 250 mm NB (Electrically Gear Operated - On
Delivery of each Pump)
Supply, Installation, Testing and Commissioning of ISI
mark CI D/F Sluice Valve as per IS 14846 PN 1.0 with
Manually / Electrically Gear operated of following sizes
with SS 304 seat rings, SS rising spindle with all hot
dipped galvanised hardwares, bolts, nuts & washers,
gaskets including all taxes, insurance, transportation,
freight charges, Inspection Charges, loading unloading,
conveyence to pump house, stacking, security etc.
complete as per IS and Specification.
Size: 300 mm NB (Electrically Gear Operated - On
Delivery of each Pump)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supply, Installation, Testing and Commissioning of ISI
mark CI D/F Sluice Valve as per IS 14846 PN 1.0 with
Manually / Electrically Gear operated of following sizes
with SS 304 seat rings, SS rising spindle with all hot
dipped galvanised hardwares, bolts, nuts & washers,
150 gaskets including all taxes, insurance, transportation, 2.00 137790.00 No.
freight charges, Inspection Charges, loading unloading,
conveyence to pump house, stacking, security etc.
complete as per IS and Specification.
Size: 150 mm NB (Electrically Gear Operated - On
Delivery of each Pump)
MPS TO KARAI NETWORK
Size: 100 mm NB (Manually Operated - On header for
MPS TO KARAI NETWORK
Supply, installation, testing and commissioning of double
flanged CI Dual Plate Check Valve conforming to API
594 Class 300 with CS dual door, hinge pin & stop pin of
SS 410 , springs of AISI 304 and seat of SS 304 , along
with all required accessories, gaskets and hardwares,etc.
and as per specification.
Size : 250 mm NB (On delivery of each Pump)
Supply, installation, testing and commissioning of double
flanged CI Dual Plate Check Valve conforming to API
594 Class 300 with CS dual door, hinge pin & stop pin of
SS 410 , springs of AISI 304 and seat of SS 304 , along
152 with all required accessories, gaskets and hardwares,etc. 5.00 36186.00 No.
and as per specification.
Size : 300 mm NB (On delivery of each Pump)
Supply, installation, testing and commissioning of double
flanged CI Dual Plate Check Valve conforming to API
594 Class 300 with CS dual door, hinge pin & stop pin of
SS 410 , springs of AISI 304 and seat of SS 304 , along
with all required accessories, gaskets and hardwares,etc.
and as per specification.
Size : 150 mm NB (On delivery of each Pump)
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SITC of Manually / Electrically Gear operated ISI mark
CI D/F Butterfly Valve as per IS 13095, PN 1.0 with
sleeve of EPDM & disc, shaft & internal parts of SS
410 along with gaskets and all other necessary
hardware etc. of following diameter including all taxes,
insurance, transportation, freight charges, Inspection
Charges loading unloading, conveyence to pump house
stacking, security etc. complete as per IS and
Size: 350 mm NB (Electrically Gear operated On pump
Header line after FM)
1 Nos at Header
SITC of Manually / Electrically Gear operated ISI mark
CI D/F Butterfly Valve as per IS 13095, PN 1.0 with
sleeve of EPDM & disc, shaft & internal parts of SS
410 along with gaskets and all other necessary
hardware etc. of following diameter including all taxes,
insurance, transportation, freight charges, Inspection
Charges loading unloading, conveyence to pump house
stacking, security etc. complete as per IS and
Size: 350 mm NB (Electrically Gear operated On pump
Header line after FM)
1 Nos at Header
SITC of Manually / Electrically Gear operated ISI mark
CI D/F Butterfly Valve as per IS 13095, PN 1.0 with
sleeve of EPDM & disc, shaft & internal parts of SS
410 along with gaskets and all other necessary
hardware etc. of following diameter including all taxes,
insurance, transportation, freight charges, Inspection
Charges loading unloading, conveyence to pump house
stacking, security etc. complete as per IS and
Size: 450 mm NB (Electrically Gear operated On pump
Header line after FM)
1 Nos at Header
SITC of Manually / Electrically Gear operated ISI mark
CI D/F Butterfly Valve as per IS 13095, PN 1.0 with
sleeve of EPDM & disc, shaft & internal parts of SS
410 along with gaskets and all other necessary
hardware etc. of following diameter including all taxes,
insurance, transportation, freight charges, Inspection
157 Charges loading unloading, conveyence to pump house 1.00 134674.00 No.
stacking, security etc. complete as per IS and
Size: 150 mm NB (Electrically Gear operated On pump
Header line after FM)
1 Nos at Header
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SITC of CI Temper Proof Air Valve with Isolation
Sluice Valve as per IS 14845 PN-1.0 & IS-14846 PN-1.0
respectively with SS304 float, gun metal nozzle, complete
hardware's, bolts, nuts & washers, gaskets etc. including
all taxes, Insurance, Transportation, freight charges,
Inspection charges, loading, unloading, conveyance to
departmental stores, stacking, security etc. as per IS and
Size: 100 mm NB - Pn 1.0 (On Header pipe O/S. the pump
house before interconnecting junction)
SITC of CI Temper Proof Air Valve with Isolation
Sluice Valve as per IS 14845 PN-1.0 & IS-14846 PN-1.0
respectively with SS304 float, gun metal nozzle, complete
hardware's, bolts, nuts & washers, gaskets etc. including
all taxes, Insurance, Transportation, freight charges,
159 Inspection charges, loading, unloading, conveyance to 1.00 11599.00 No.
departmental stores, stacking, security etc. as per IS and
Size: 50 mm NB - Pn 1.0 (On Header pipe O/S. the pump
house before interconnecting junction)
MPS TO KARAI NETWORK
Supply, installation, testing and commissioning of double
flanged Expansion Bellows confirming to EJMA/IS
standard with PN 1.0 rating & all necessary St.St.
160 Size : 250 mm x 300 mm ( L ) (On Delivery of Each 6.00 7745.00 No
Size : 350 mm x 300 mm ( L ) (On header Line near
MPS-1 TO STP 2.00 12840.00 No
Supply, installation, testing and commissioning of double
flanged Expansion Bellows confirming to EJMA/IS
standard with PN 1.0 rating & all necessary St.St.
161 hardware''s. 5.00 10200.00 No
Size : 300 mm x 300 mm ( L ) (On Delivery of Each
Size : 450 mm x 300 mm ( L ) (On header Line near
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supply, installation, testing and commissioning of double
flanged Expansion Bellows confirming to EJMA/IS
standard with PN 1.0 rating & all necessary St.St.
162 hardware''s. 2.00 4656.00 No
Size : 150 mm x 300 mm ( L ) (On Delivery of Each
MPS TO KARAI NETWORK
Size : 150 mm x 300 mm ( L ) (On header Line near
FlowMeter) 1.00 4656.00 No
MPS TO KARAI NETWORK
G.I. PIPES & FITTINGS:
Supply, installation, connection with equipments as
required, testing and commissioning of GI pipe
conforming to IS-1239 , Medium Duty with coupling, tee,
bend, union, elbow, flanges , etc as all required fittings for
connection complete with gaskets, hardware, and required
163 accessories as per IS & Specifications 80.00 898.00 RMT
Size: 100 mm NB (Header drain Pipe & for Air Valve
MPS TO KARAI NETWORK
Size: 50 mm NB (Air Valve Pipe)
MPS TO KARAI NETWORK
DI PIPES & SPECIALS
Providing and supplying D. I. D/F K-9 grade pipes for
following nominal bore diameter with internal cement
mortar lining including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading,
unloading, conveyance to departmental stores, stacking
etc. complete. (IS 8329-2000).
DI Pipe K-9 D/F
Size: 250 mm (For Delivery of Each Pump)
Size: 350 mm (Header pipe) Length is tentative and to be
considered as per actual site condition. 25.00 10071.00 RMT
Size: 350 mm (Header pipe) Length is tentative and to be
considered as per actual site condition.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
DI PIPES & SPECIALS
Providing and supplying D. I. D/F K-9 grade pipes for
following nominal bore diameter with internal cement
mortar lining including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading,
165 unloading, conveyance to departmental stores, stacking 75.00 7769.00 RMT
etc. complete. (IS 8329-2000).
DI Pipe K-9 D/F
Size: 300 mm (For Delivery of Each Pump)
Size: 450 mm (Header pipe) Length is tentative and to be
considered as per actual site condition.
DI PIPES & SPECIALS
Providing and supplying D. I. D/F K-9 grade pipes for
following nominal bore diameter with internal cement
mortar lining including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading,
unloading, conveyance to departmental stores, stacking
etc. complete. (IS 8329-2000).
DI Pipe K-9 D/F
Size: 150 mm (For Delivery of Each Pump)
MPS TO KARAI NETWORK
Size: 150 mm (Header pipe) Length is tentative and to be
considered as per actual site condition. 20.00 3597.00 RMT
MPS TO KARAI NETWORK
Manufacture, Supply & Delivery of Ductile Iron Flange
bends, tees, reducers or any other specials as per BS-EN-
545/1995 Class - A Series K12 Suitable for use with DI
pipes manufactured as per IS:8329 / 1994 delivery of
specials is to be made to site of works anywhere in gujarat
including all taxes, loading, unloading, carting, stacking,
insurance, inspection charges, octroi etc. complete. -
80 to 300 mm dia
MPS TO KARAI NETWORK
MPS-2 TO STP 1665.00 155.00 kg
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SITC of Electric Actuator Gear operated C.I. Sluice Gate
conforming to AWWA C 501 or IS : 13349 - 1992 Class -
1 with rising spindle, single faced, wall thimble mounted,
handwheel, flange back frame, head stock, Spindle with
supports brackets having length as specified or to suit site
168 condition, suitable for seating as well as unseating water 5.00 480250.00 Nos
head, complete in all respect.
Gate Size : 900 mm X 900 mm - approx. 12 m spindle
length (at inlet line) Conventional Bottom Closing or
suitable Closing
SITC of Electric Actuator Gear operated C.I. Sluice Gate
conforming to AWWA C 501 or IS : 13349 - 1992 Class -
1 with rising spindle, single faced, wall thimble mounted,
handwheel, flange back frame, head stock, Spindle with
supports brackets having length as specified or to suit site
condition, suitable for seating as well as unseating water
head, complete in all respect.
Gate Size : 1000 mm X 1000 mm - approx. 12 m spindle
length (at inlet line) Conventional Bottom Closing or
suitable Closing
SITC of Electric Actuator Gear operated C.I. Sluice Gate
conforming to AWWA C 501 or IS : 13349 - 1992 Class -
1 with rising spindle, single faced, wall thimble mounted,
handwheel, flange back frame, head stock, Spindle with
supports brackets having length as specified or to suit site
condition, suitable for seating as well as unseating water
head, complete in all respect.
Gate Size : 400 mm X 400 mm - approx. 9 m spindle
length (at inlet line) Conventional Bottom Closing or
suitable Closing
MPS TO KARAI NETWORK
BAR SCREEN - MANUAL
Supply, Installation, Testing and Commissioning of
Manuall Bar Screen having bar size of 10 mm x 50 mm
and clear spacing between bars of 25 mm, MOC SS-304
and lifting hook etc with all required accessories and
171 hardware. 3.00 186450.00 Nos
Size : 2000 mm (L) X 2000 mm (W)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
BAR SCREEN - MANUAL
Supply, Installation, Testing and Commissioning of
Manuall Bar Screen having bar size of 10 mm x 50 mm
and clear spacing between bars of 25 mm, MOC SS-304
and lifting hook etc with all required accessories and
Size : 1000 mm (L) X 1000 mm (W)
MPS TO KARAI NETWORK
BAR SCREEN - MECHANICAL
Supplying, installing, testing, and commissioning of
Mechanical Fine Screen suitable for sewage pumping
station inlet channel, designed to automatically remove
fine solids and floating debris from incoming raw sewage.
The screen shall be of robust construction in stainless steel
SS304/SS316, consisting of screen frame, fine bars,
automatic raking system, drive motor with gearbox,
control panel, and necessary supports and guide structures.
The system shall ensure uninterrupted screening with
automatic removal of screenings to a designated disposal
area, thereby protecting pumps and downstream
Size : 2000 mm (L) (or as per actual requirement) X
E.O.T. CRANE WITH HOIST
Supply, installation, testing & commissioning single girder
type fully electrically operated EOT crane with electrically
operated hoist, class II duty, geared travelling trolley with
seven meter lift complete with long travel rail track (40
mm sq. bar), moving or cross girder, all three motions
electrically operated by suitable rating motor IP 54, control
panel & down pendant control block, brake, safety device,
cables form motor to starter panel & other required
accessories & tested as per IS Specifications.
Note: Minimum as specified capacity or higher as per
requirement such that EOT crane capacity is min.1.25
times of the pump, motor OR single heaviest component to
be lifted within pump house.
Capacity : 5 Ton. (for Pump Room)
'Lift : 6-12 m (or as per actual site condition)
Span: 6-9 m (or as per actual site condition)
Bay length: 20 m (or as per actual site condition)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
E.O.T. CRANE WITH HOIST
Supply, installation, testing & commissioning single girder
type fully electrically operated EOT crane with electrically
operated hoist, class II duty, geared travelling trolley with
seven meter lift complete with long travel rail track (40
mm sq. bar), moving or cross girder, all three motions
electrically operated by suitable rating motor IP 54, control
panel & down pendant control block, brake, safety device,
cables form motor to starter panel & other required
175 accessories & tested as per IS Specifications. 1.00 416250.00 Nos
Note: Minimum as specified capacity or higher as per
requirement such that EOT crane capacity is min.1.25
times of the pump, motor OR single heaviest component to
be lifted within pump house.
Capacity : 2 Ton. (for Pump Room)
'Lift : 6-12 m (or as per actual site condition)
Span: 0-6 m (or as per actual site condition)
Bay length: 6 m (or as per actual site condition)
MPS TO KARAI NETWORK
SITC of Electrically Operated Chain Hoist & Electrically
operated Trolley, suitable to operate on Mono Rail Girder
having motorised motion in vertical lifting & cross travel,
manufactured as per IS:6547-1972-Class-II & IS-3177-
Class-II, complete with electrically operated chain hoist &
Electically operated geared trolley, brake, chain-gear,
motors, safety device, pendant push button, starter panel,
cables from motor to starter panel and all other required
accessories like limit switches, panel, power supply system
(Fastoon cable type), fasteners, epoxy painting, etc. tested
for over load as per IS complete as per specifications and
complete in all respect.
Capacity : 1 Ton. Min. (for Manual Screen-lifting)
'Lift : 12 m as mini. or as per site req.
(w/o MONORAIL GIRDER & MS supporting structure)
Note: (1) Minimum as specified capacity or higher as per
requirement such that ECH capacity is min.1.25 times of
the pump/motor OR single heaviest component to be lifted
within pump house.
Chain Pulley Block
Providing chain pulley block with triple gear arrangement,
lifting hook, laod chain & hand chain & locking device
Capacity : 1 Ton. Min. (for Manual Screen-lifting)
'Lift : 10 m as mini. or as per site req.
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Providing, Supplying at site of work with freight, loading,
unloading carting, etc. including all taxes and duties
complete such as joints, channels, angles, plates, iron rails,
etc. below 10 mm thickness as per relevant IS and as per
178 specification 8000.00 64.84 KG
MPS TO KARAI NETWORK
Labour Charges for lowering, laying, Fixing with
fabrication various size section of MS such as joints
channel, angles, plates, etc Complete as per relevant IS
and as per specification.
MPS TO KARAI NETWORK
INSTRUMENTATION WORK PRESSURE
MEASURMENT SYSTEM
Supply, installation, testing & commissioning of Bourden
type Pressure Guage glycerene filled having 150 mm dial
with necessary fittings / accessories (Manifold valve,
nipples, etc. shall be in SS 316 only) as per specifications
& complete in all respects.Pressure gauge shall be
provided only Pump delivery and on header line.
(On delivery of each pump & on Header line).
Range : 0 - 6 kg / sq.cm.
MPS TO KARAI NETWORK
Supply, installation, testing and commissioning of
Digital Pressure Transmitter along with, manifold valve,
required fittings, tubing (all valves, fittings, tubings, etc.
shall be in SS 316 only) all accessories, hardware, etc.
complete in all respects as per specifications and having
following measurement ranges:
Range : 0 - 6 Kg/cm2 (On Delivery of each pump and
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
LEVEL MEASURING SYSTEM
Ultrasonic Type Level Transmitter with Remote Display :
Design, Supply, Installation, Testing and Commissioning
of NOn Contact Ultrasonic Type Level Transmitter with
Remote Display.
The sensor should be non contact type, field mounting
type, housing shall have minimum IP65 protection, PP/
PVC Sensor MOC, with sensor to transmitter cable.
Remote Indicator cum Transmitter:
Microprocessor based indicator with LED / LCD digital
display,panel/ wall mounting type, power supply shall be
Accesories: Mounting bracket, nut, bolts etc as per system
requirement and Hook up diagram of the Instruments.
Meas. Range: upto 15 m at Wet well
MPS TO KARAI NETWORK
ELECTRO MAGNETIC FLOWMETER
Supply, installation, testing and commissioning of remote
type Full Bore Electromagnetic flow meter comprising of
IP-68 Sensor, IP-65/66 remote transmitter with 10m cable
between sensor and transmitter,Panel mounted flow
indicator cum Totalizer along with all mounting
accessories, hardware, etc. complete in all respect and as
per specs and shall have following size and measurement
range. The scope also includes necessary connection with
Meter Size : 350 mm (At Header)
Pipe size: 350 mm
Pipe Material : DI
ELECTRO MAGNETIC FLOWMETER
Supply, installation, testing and commissioning of remote
type Full Bore Electromagnetic flow meter comprising of
IP-68 Sensor, IP-65/66 remote transmitter with 10m cable
between sensor and transmitter,Panel mounted flow
indicator cum Totalizer along with all mounting
accessories, hardware, etc. complete in all respect and as
184 per specs and shall have following size and measurement 1.00 226181.00 Nos.
range. The scope also includes necessary connection with
Meter Size : 450 mm (At Header)
Pipe size: 450 mm
Pipe Material : DI
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
ELECTRO MAGNETIC FLOWMETER
Supply, installation, testing and commissioning of remote
type Full Bore Electromagnetic flow meter comprising of
IP-68 Sensor, IP-65/66 remote transmitter with 10m cable
between sensor and transmitter,Panel mounted flow
indicator cum Totalizer along with all mounting
accessories, hardware, etc. complete in all respect and as
per specs and shall have following size and measurement
range. The scope also includes necessary connection with
Meter Size : 150 mm (At Header)
Pipe size: 150 mm
Pipe Material : DI
MPS TO KARAI NETWORK
PLC BASED CONTROL PANEL FOR SPS
Supply, Installation, Testing & Commissioning of PLC
Based Instrument control Panel with panel mounted 10 "
colour touch screen HMI, 4G or Latest GPRS modem with
ethernet port / Such suitable port for Remote data
transmission to Existing Central as well as Zonal SCADA,
SIM card for remote data tranmission facility,
Communication port for MFM . Instrument Control Panel
'(PLC Enclosure / Panel ) with necessary PLC based logic
and wiring , Min. 1 kVA online UPS (with 30 min backup
alongwith filter for harmonic, suitable rating SMF inbuilt
batteries alongwith battery charger and all other
accessories as per standard), etc. complete in all respects
and as per specs with PLC having minimum I/O count of
64DI / 64DO / 16AI /12AO. These are the minimum IO
requirement if any other IO,s required to complete the
work contractor shall be provide the same without any
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
PLC BASED CONTROL PANEL FOR SPS
Supply, Installation, Testing & Commissioning of PLC
Based Instrument control Panel with panel mounted 10 "
colour touch screen HMI, 4G or Latest GPRS modem with
ethernet port / Such suitable port for Remote data
transmission to Existing Central as well as Zonal SCADA,
SIM card for remote data tranmission facility,
Communication port for MFM . Instrument Control Panel
'(PLC Enclosure / Panel ) with necessary PLC based logic
187 and wiring , Min. 1 kVA online UPS (with 30 min backup 1.00 1243000.00 No.
alongwith filter for harmonic, suitable rating SMF inbuilt
batteries alongwith battery charger and all other
accessories as per standard), etc. complete in all respects
and as per specs with PLC having minimum I/O count of
32DI / 32DO / 16AI /12AO. These are the minimum IO
requirement if any other IO,s required to complete the
work contractor shall be provide the same without any
MPS TO KARAI NETWORK
SITC of Licensed SCADA Software (Latest Version) for
Central Monitoring & Control System of Sewage Pumping
Stations (SPS) and Sewage Treatment Plant (STP),
including supply, installation, testing and commissioning
of SCADA software capable of real-time centralized
monitoring and control of all SPS and STP units from a
central control room, as well as local monitoring and
control from individual SPS and STP locations. The
software shall support seamless integration with
PLCs/RTUs over standard protocols (Modbus TCP/IP,
188 IEC 60870, etc.) and provide functionalities including 1.00 1200000.00 NOS.
graphical HMI, data logging, alarm management,
historical trends, and automated reporting. The license
shall support the required number of tags/nodes and
include configuration for both central and local HMIs.
Complete in all respects and with all required accessories
and hardware to run the software and system including one-
year warranty, operator training, OEM support, and
1) I5 PC with 8 GB RAM 1TB Hard Disk & 32” Monitor
2) 1 KVA UPS for 1 Hr. Backup
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
INSTRUMENT CABLE & ACCESSORIES
'Supply, Laying, Installation, Connection, Termination,
& Commissioning of Instrument Cables, along with
cable glands, lugs, cable trays, required junction boxes,
fittings and accessores as per specs.
The unit rate shall include
a. Supply, loading & unloading of the cable at site from
store. B. Shifitng of cable from site store to place of
c. Fixing of cable clamps, brackets, supports, route
markers etc. where ever required to fix the cables safely.
d. Excavation, back filling and levelling of ground
alongwith laying of fine sand, protection bricks and other
necessary civil material for laying cables outside the
e. Testing and submission of sketches & reports of all the
MPS TO KARAI NETWORK
MPS TO KARAI NETWORK
MPS TO KARAI NETWORK
INSTRUMENT CABLE TRAY
Supply & laying GI perforated type cable trays with
returned edge / flange, fabricated from 2.0 mm thk sheet
steel in the standard length of 2.5 mtrs, duly hot dipped
galvanized after fabrication as per IS 2629-1989 / IS 4759-
1984 including accessories such as coupler plates/ fish
plates, bends, tees, reducers, elbows, covers and electro-
galvanized hardware etc, erected on existing support as per
specification and instruction of Engineer-in-charge.
100 x 35 mm - Perforated type
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
CABLE END TERMINATION AND CONNECTION :
'Supply, fixing, connection, testing and commissioning
of double compression brass cable glands and crimping
type Bimetalic lugs / sockets with necessary tools and
equipments as specified in specifications and IS complete
in all respects. The glands and lugs / sockets shall be
suitable for cable size and type mentioned above. The job
also includes earthing the glands and armour of the cable
with common earth bar or flexible copper mesh as
MPS TO KARAI NETWORK
MPS TO KARAI NETWORK
MPS TO KARAI NETWORK
11 kV Two Pole Structure Assembly:
SITC of 11 kV double pole 9 meter high structure made of
6" X 3" 'I" section girder, 4" X 2" channels, clamps, nuts,
bolts, stay wires including earthing system with following
accessories duly connected with ACSR conductors as per
approved drawing & in compliance with requirement of
(a) 11 kV, 200 A drop out fuses with Synthetic Resin
Bonded Paper (SRBP) tubes: 1 Set (01 piece per phase).
192 (b) 11 kV, 400 A G.O.D. switch complete with earth 3.00 120663.00 Each
switch, insulators, operating handle with galvanised pipe,
square bar: 1 Set.
(c) 11 kV lightning arrestor with clamps: 3 Nos.
(d) 11 kV Disc Insulators (70KN): 3 Nos.
(e) 11 kV Pin Insulators (5KN): 3 Nos.
(f) 20 mm dia. GI Stay Sets Complete: 2 Set.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
HT SWITCHGEAR PANEL
Supply, installation, testing & commissioning both side
extensible, Indoor type HV Switchgear panel confirming
to IS-3427, IS-2516 (Part- I & II.sec.1 ) & IEC-60056 &
IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed
AC supply system and having breaking/ ruptuing capacity
of 500 MVA (26.3 kA for 3sec) complete with spring
charged mechanism, ON-OFF mechanical push button,
operation counters, Breaker TNC switch, Breaker L/R
switch, necessary auxiliary switches, closing coil, shunt
trip, protection relays & Indicators etc., complete. The
panel shall comprise of air insulated busbars provided with
heat shrinkable PVC sleeves. The VCB trolley shall
comprise of three vacuum interrupters with epoxy support
insulators and self aligning finger type isolating contacts
and necessary mechanical interlocks, safety shutters,
isolating plugs. Enclosure shall be openable from front as
well as rear end. The breaker shall be Manual cum
motorised mechanism with following accessories.
a) 96 x 96 mm square flush mounting type Ammeter &
Volt meter with selector switches b) Multi function meter
c) Double core, cast resin type current transofrmer having
ratio as per requirement, one core for metering & one core
for protection having required class of accuracy. d)
Instantaneous under voltage relay & Temperature rise
tripping Relay, e) Triple pole IDMTL two over current
and one earth fault relay with current setting range 50-
200% and 10-40% f) Electrical closing. coil & shunt trip
coil operating on 110 V DC. g) Auxiliary relay for anti
pumping device. h) Three limb, drawout type, feeder
connected, cast resin insulated, three phase Potential
transformer having ratio & burden as per reqirement &
Class 0.5 accuracy. i) Annunciator Windows, Common
Hooter / Alarm bell operating on 230 AC/ 110 V DC. j)
Cable boxes suitable to terminate 3 core XLPE cable of
required size (As per design). k) 230V AC to 110 V DC
power pack for closing & tripping circuit common. l)
Breaker ON-OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination lamps with plug
socket. n) Space Heater with Thermostat.
11 kV HV Switchgear Panel- Comprising of 630 A
Vacuum circuit breaker for 1 no. Incomer, 2no. O / G
feeders for 11/0.433 kV distribution transformers
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
11 kV (Earthed / Unearthed) Grade Cable- Aluminium
Supply, laying, testing & commissioning of 6.35 / 11 kV
(E) grade, XLPE insulated, stranded Aluminium
conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty
cable (to be laid on wall surface with necessary clamps / in
existing cable trench / cable trays / conduit / pipe sleeves
at road crossing or floor as per site requirement)
conforming to IS: 7098 (Part2)
& IEC: 60502 (Part-2) of following sizes:
3 Core x 240 Sqmm
From 2 Pole Structure to HT Panel & HT Panel to
Cable Terminations / Jointing Kits for 6.6 kV (UE) /
kV (E) grade XLPE Cable
Providing & fitting heat shrink cable termination / jointing
kits for 6.6 kV (UE) / 11 kV (E) grade XLPE insulated
cable including necessary earth connectivity connection,
material & consummables making the termination/ joint
complete ensuring the joint resistance is within
the permissble limit as per IS, of following types & sizes:
Outdoor Terminations Kit suitable for - 3 Core x
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
DISTRIBUTION TRANSFORMER
Providing, erecting, testing & commissioning approved
make oil immersed ONAN cooled, double wound, core
type indoor / outdoor copper wound 11KV/ 433V step
down transformer of following capacities operating on
phase, 50 Hz 4 wire & neutral earthed system
continuously rated for a full temperature rise in oil not
exceeding 45 Deg.C.at maximum ambient temp. of
Deg. C. complete with necessary radiator first filling of
new transformer oil & standard fitting as below
complying with IS 1180( Part 1 ):2014 standards with
energy efficiency level
Off load tap changing range steps +2.5% to -5% on H.V
for variation should be provided. The H.V. shall be
connected Delta & Secondary with star connection. The
transformer should have cable-end boxes on H.T. side
suitable for up to 3 core 150 sq.mm. XLPE cable & on
L.T. side suitable for bus duct or cables as per requirement
complete with test certificates from manufacturers
1. Oil conservator with filling Hole & Cap - One No.
Thermometer pocket with 6" dial type thermometer switch
alarm & trip contacts- Two nos. 3. Silica-gel breather
with charge- One No. 4. Plain oil level gauge - One
No. 5. Drain / Sampling / Filter valve- One No. 6. Top
196 Filter Valve - One No. 2.00 671787.02 Nos.
7. Explosion vent with Diaphragm - One No. 8. Rating
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
7. Explosion vent with Diaphragm - One No. 8. Rating
& Diagram plate - One No. 9. Additional neutral
bushing for earthing - One No. 10. Bi directional
Roller - Four Nos. 11. Earthing terminals - Two Nos.
Lifting lugs - Two Nos. 13. Air release plug. - One No.
Double float buchholz relay with Alarm and trip
contacts. 15. Control cable as required from Transformer
to VCB Panel is to be provided with necessary connection
to VCB relays for protection. as per IS 1180 level-1
(A) 250 KVA - Cat.III
Max. allowable loses at 50 % of rated load is 2.79 KW
and at full load is 7.77 KW
Note: Transformer shall be suitable for parallel operation.
Minimum requirement shall be as below:
Both transformer shall have " Identical X/R ratio, phase
angle shift, polarity, phase sequence, frequency, position
of tap changer. Turns ratio & voltage ratio"
DISTRIBUTION TRANSFORMER
Providing, erecting, testing & commissioning approved
make oil immersed ONAN cooled, double wound, core
type indoor / outdoor copper wound 11KV/ 433V step
down transformer of following capacities operating on
phase, 50 Hz 4 wire & neutral earthed system
continuously rated for a full temperature rise in oil not
exceeding 45 Deg.C.at maximum ambient temp. of
Deg. C. complete with necessary radiator first filling of
new transformer oil & standard fitting as below
complying with IS 1180( Part 1 ):2014 standards with
energy efficiency level
Off load tap changing range steps +2.5% to -5% on H.V
for variation should be provided. The H.V. shall be
connected Delta & Secondary with star connection. The
transformer should have cable-end boxes on H.T. side
suitable for up to 3 core 150 sq.mm. XLPE cable & on
L.T. side suitable for bus duct or cables as per requirement
complete with test certificates from manufacturers
1. Oil conservator with filling Hole & Cap - One No.
Thermometer pocket with 6" dial type thermometer switch
alarm & trip contacts- Two nos. 3. Silica-gel breather
with charge- One No. 4. Plain oil level gauge - One
197 No. 5. Drain / Sampling / Filter valve- One No. 6. Top 2.00 1606000.00 Nos.
Filter Valve - One No.
7. Explosion vent with Diaphragm - One No.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
7. Explosion vent with Diaphragm - One No.
Rating & Diagram plate - One No. 9. Additional
neutral bushing for earthing - One No. 10. Bi
directional Roller - Four Nos. 11. Earthing terminals -
Two Nos. 12. Lifting lugs - Two Nos. 13. Air release plug.
- One No. 14. Double float buchholz relay with Alarm
and trip contacts. 15. Control cable as required from
Transformer to VCB Panel is to be provided with
necessary connection to VCB relays for protection. as per
IS 1180 level-1
Note: Transformer shall be suitable for parallel operation.
Minimum requirement shall be as below:
Both transformer shall have " Identical X/R ratio, phase
angle shift, polarity, phase sequence, frequency, position
of tap changer. Turns ratio & voltage ratio"
DISTRIBUTION TRANSFORMER
SITC of outdoor type, three phase, oil immersed
distribution transformer of required KVA and voltage
ratio, copper double wound, vector group Dyn11, HV
delta connected and LV star connected with neutral
brought out to provide separate earthing terminals,
complete with bushing/cable box on HV side and cable
box on LV side suitable for cables or bus duct as per
requirement with standard fittings, conforming to IS:1180
(Part-1)/2014 with its latest amendments, including first
fill of transformer oil and accessories such as oil
conservator with filling holes, cap and prismatic oil level
gauge; silica gel dehydrating breather charged with silica
gel; oil drain cum sampling valve with plug; oil filter
valve; lifting eyes/hooks/lugs; two earthing terminals;
diagram and rating plate; air release plug; explosion vent
with diaphragm; thermometer pocket; four bi-directional
plain rollers with base channel with hauling holes;
fixed/separate type radiator banks; off-circuit externally
operated tapping switch (for rating <1000 kVA); 100 mm
stem type oil temperature indicator (for rating <500 kVA);
Buchholz relay with shut-off valve (for rating ≥500 kVA);
150 mm dial type oil temperature indicator with alarm/trip
contact (for rating ≥500 kVA); 150 mm dial type winding
temperature indicator with alarm/trip contact
(for rating ≥1000 kVA); marshalling box (for rating ≥500
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
(for rating ≥1000 kVA); marshalling box (for rating ≥500
kVA); 150 mm dia. magnetic type oil gauge (for rating
≥1600 kVA); inspection cover and jacking lugs (for rating
≥1600 kVA). For transformers having oil storage capacity
of 2000 liters and above, nitrogen injection fire protection
system (NIFPS) shall be provided.
(C) 400 KVA - Cat.III
Max. allowable loses at 50 % of rated load is 2.79 KW
and at full load is 7.77 KW
Note: Transformer shall be suitable for parallel operation.
Minimum requirement shall be as below:
Both transformer shall have " Identical X/R ratio, phase
angle shift, polarity, phase sequence, frequency, position
of tap changer. Turns ratio & voltage ratio"
Casting of transformer plinth / foundation including oil
soak pit (where required) in situ reinforced cement
concrete in M 20 using granite, quartzite trap metal of size
6 mm to 20 mm for RCC work including providing of
grade cement & Fe 415 grade TMT bars, scaffolding,
centering, form work, curing etc. complete.
Size:- 1250x1250x
Casting of transformer plinth / foundation including oil
soak pit (where required) in situ reinforced cement
concrete in M 20 using granite, quartzite trap metal of size
6 mm to 20 mm for RCC work including providing of
200 grade cement & Fe 415 grade TMT bars, scaffolding, 2.00 35000.00 Set
centering, form work, curing etc. complete.
Size:- 1500x1500x
Supply and levelling of Switch yard & transformer yard
using gravel, fine sand and other required filing material,
enmarked for the Switchyard & Transformer yard
including removing of trees or boulders etc. if any. The
general level of the yard shall be at a convenient level for
201 movement of man and material and it should match with 225.00 350.00 Sq.m.
FGL and as per Specification and Drg.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supply and Installation of GI Chain link fencing frames
with L angle/Channel post around Transformer yard etc. as
per Specification and Drg.
202 MPS-1 TO STP 180.00 1080.00 RMt.
SITC of 3.0 mtr wide gate with GI chain link as per
Specification and Drg.
MEDIUM VOLTAGE PANEL BOARD (PMCC)
SITC of PMCC Panel (50kA) complete in all respects as
per SLD / Specification / IS and including following as
(1) Two nos. FP 400A Microprocessor EDO ACB for I/C
with Digital Voltmeter with Voltmeter Selector Switch,
Digital Power Factor Meter, Digital Ammeter with
Ammeter selector switch, MFM with RS-485, R, Y, B, on,
off, trip Indicating lamps & ON, E-STOP, Reset
Pushbutton, etc.
(2) One no. FP 400A Thermal Magnetic EDO ACB for
(3) 400A TPN Main busbars. (Main & Auxilary bus-bars
size with current density 0.8A/Sq.mm)
(4) Three Nos. (2W + 1S) Soft Starter for min. 75 kW
Motor or higher as per pump Manufacturer reco. with
suitable derating and with 160A TPN Motor Duty MCCB,
160A AC3 duty line & external bypass contactor, Ten
channel temperature scanner with potential free contacts,
fast acting fuse, MFM with RS-485, door display key pad
& digital MPR+SPP with CBCT, on, off, trip Indicating
lamps & ON, E-STOP, Local/Remote, Auto/ Manual
selector switch & LCS for Pump- MOV Actuator with
Indication & push button etc.
204 (5) Tr. losses comp. fixed capacitor bank with Two 1.00 1881000.00 Set
nos. 5 kVAR capacitors bank each with capacitor duty
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
nos. 5 kVAR capacitors bank each with capacitor duty
contactor, timer & 'D' curve MCB, etc. for each
(6) Two nos. 160A FP Microprocessor MCCB feeder for
(7) Three nos. 63ATPN MCCB feeders (for 2 nos PDB -
Auxiliary accessories load, Spare)
(8) 2 no. 32A TPN MCCB spare.
(9) One no. Outdoor lighting LDB feeder with 32ATPN
'C' curve MCB with 32A contactor & Time switch.
(10) 4 nos. 32A 'C' curve MCB feeders (for Indoor LDB,
3nos. spare feeders)
(11) 4nos. 16A DP MCB feeders (for single phase supply
for 2nos. X'mer marshaling box, HT Panel & Spare.)
(12) 6nos. 400A/1A, Cl.-0.5 metering CT
(13) 2nos. 400A/1A, Cl.-1. APFC CT
(14) 2nos. Multiplication relay for dry run protection of
MEDIUM VOLTAGE PANEL BOARD (PMCC)
SITC of PMCC Panel (50kA) complete in all respects as
per SLD / Specification / IS and including following as
(1) Two nos. FP 400A Microprocessor EDO ACB for I/C
with Digital Voltmeter with Voltmeter Selector Switch,
Digital Power Factor Meter, Digital Ammeter with
Ammeter selector switch, MFM with RS-485, R, Y, B, on,
off, trip Indicating lamps & ON, E-STOP, Reset
Pushbutton, etc.
(2) One no. FP 400A Thermal Magnetic EDO ACB for
(3) 400A TPN Main busbars. (Main & Auxilary bus-bars
size with current density 0.8A/Sq.mm)
(4) Three Nos. (2W + 1S) Soft Starter for min. 55 kW
Motor or higher as per pump Manufacturer reco. with
suitable derating and with 160A TPN Motor Duty MCCB,
160A AC3 duty line & external bypass contactor, Ten
channel temperature scanner with potential free contacts,
fast acting fuse, MFM with RS-485, door display key pad
& digital MPR+SPP with CBCT, on, off, trip Indicating
lamps & ON, E-STOP, Local/Remote, Auto/ Manual
selector switch & LCS for Pump- MOV Actuator with
Indication & push button etc.
(5) Tr. losses comp. fixed capacitor bank with One nos.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
(5) Tr. losses comp. fixed capacitor bank with One nos.
kVAR Two nos. 5 kVAR capacitors bank each with
capacitor duty contactor, timer & 'D' curve MCB, etc. for
each transformer.
(6) Two nos. 160A FP Microprocessor MCCB feeder for
(7) Three nos. 63ATPN MCCB feeders (for 2 nos PDB -
Auxiliary accessories load, Spare)
(8) 2 no. 32A TPN MCCB spare.
(9) One no. Outdoor lighting LDB feeder with 32ATPN
'C' curve MCB with 32A contactor & Time switch.
(10) 4 nos. 32A 'C' curve MCB feeders (for Indoor LDB,
3nos. spare feeders)
(11) 4nos. 16A DP MCB feeders (for single phase supply
for 2nos. X'mer marshaling box, HT Panel & Spare.)
(12) 6nos. 400A/1A, Cl.-0.5 metering CT
(13) 2nos. 400A/1A, Cl.-1. APFC CT
(14) 2nos. Multiplication relay for dry run protection of
MEDIUM VOLTAGE PANEL BOARD (PMCC)
SITC of PMCC Panel (50kA) complete in all respects as
per SLD / Specification / IS and including following as
(1) Two nos. FP 800A Microprocessor EDO ACB for I/C
with Digital Voltmeter with Voltmeter Selector Switch,
Digital Power Factor Meter, Digital Ammeter with
Ammeter selector switch, MFM with RS-485, R, Y, B, on,
off, trip Indicating lamps & ON, E-STOP, Reset
Pushbutton, etc.
(2) One no. FP 400A Thermal Magnetic EDO ACB for
(3) 800A TPN Main busbars. (Main & Auxilary bus-bars
size with current density 0.8A/Sq.mm)
(4) Five Nos. (3W + 2S) Soft Starter for min. 75 kW
Motor or higher as per pump Manufacturer reco. with
suitable derating and with 160A TPN Motor Duty MCCB,
160A AC3 duty line & external bypass contactor, Ten
channel temperature scanner with potential free contacts,
fast acting fuse, MFM with RS-485, door display key pad
& digital MPR+SPP with CBCT, on, off, trip Indicating
lamps & ON, E-STOP, Local/Remote, Auto/ Manual
selector switch & LCS for Pump- MOV Actuator with
Indication & push button etc.
(5) Tr. losses comp. fixed capacitor bank with One
nos 20 kVAR, Two nos. 10 kVAR & Two nos. 5 kVAR
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
nos 20 kVAR, Two nos. 10 kVAR & Two nos. 5 kVAR
capacitors bank each with capacitor duty contactor, timer
& 'D' curve MCB, etc. for each transformer.
(6) Two nos. 200A FP Microprocessor MCCB feeder for
(7) Three nos. 63ATPN MCCB feeders (for 2 nos PDB -
Auxiliary accessories load, Spare)
(8) 2 no. 32A TPN MCCB spare.
(9) One no. Outdoor lighting LDB feeder with 32ATPN
'C' curve MCB with 32A contactor & Time switch.
(10) 4 nos. 32A 'C' curve MCB feeders (for Indoor LDB,
3nos. spare feeders)
(11) 4nos. 16A DP MCB feeders (for single phase supply
for 2nos. X'mer marshaling box, HT Panel & Spare.)
(12) 6nos. 800A/1A, Cl.-0.5 metering CT
(13) 2nos. 800A/1A, Cl.-1. APFC CT
(14) 2nos. Multiplication relay for dry run protection of
LV POWER CONTROL CENTER (PCC)
Supply, installation, testing and commissioning of LV
Distribution Board (LVDB), totally enclosed, dust- and
vermin-proof, indoor type, fabricated from CRCA sheet
steel with minimum thickness of 3.0 mm for base frame,
channels and gland plates, 2.0 mm for load-bearing
members and doors, and 1.6 mm for internal partitions,
with a minimum degree of protection of IP-52 as per IS:
2147. The LVDB shall be suitable for operation on 3-
phase, 4-wire, 415 V, 50 Hz system with effectively
grounded neutral. The panel shall be provided with
instrumentation compartments accommodating meters,
auxiliary and protective relays, LED type indicating lamps
and control MCBs conforming to IS: 13947. Current
transformers and voltage transformers shall conform to IS:
2705. The panel shall be provided with air-insulated
electrolytic grade aluminium / copper bus bars for three-
phase and neutral system, along with GI earth bus
extending throughout the entire length of the panel. Power
and control wiring shall be carried out using 1100 V
grade, FRLS insulated copper conductor wires conforming
to IS: 694 and IS: 8130, complete with all necessary
equipment fittings. The LVDB shall have a horizontally
running busbar compartment with a minimum height of
300 mm. Incoming and outgoing cable connections
shall be suitable for 1100 V grade aluminium / copper
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
shall be suitable for 1100 V grade aluminium / copper
conductor, XLPE / PVC insulated and PVC sheathed
armoured cables. The LVDB shall be provided with the
required incoming, bus coupler and outgoing modules of
the specified type and ratings.
Above 80 A, upto & including 250 A, 3 & 4 Pole, Air
Break Fixed MCCB conforms to IS / IEC 60947-2 with
trip free mechanism, current limiting type with Thermal-
Magnetic / Microprocessor release (O / C, S / C & E / F)
with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro-
Mechanical protections & interlocks etc. MCCB module,
when used as Incommer / Bus Coupler, shall have
enclosure dimensions- 1800(H) x 600(W) x 600 (D) &
following technical features:
4 Pole, 160A MCCB with Breaking Capacity of Icu=50
KA at 415V (Ics =100% of Icu), Microprocessor release
MPS TO KARAI NETWORK
MEDIUM VOLTAGE PANEL BOARD (PMCC)
SITC of PMCC Panel (50kA) complete in all respects as
per SLD / Specification / IS and including following as
(1) One nos. FP 160A Microprocessor EDO MCB for I/C
with Digital Voltmeter with Voltmeter Selector Switch,
Digital Power Factor Meter, Digital Ammeter with
Ammeter selector switch, MFM with RS-485, R, Y, B, on,
off, trip Indicating lamps & ON, E-STOP, Reset
Pushbutton, etc.
(2) 200A TPN Main busbars. (Main & Auxilary bus-bars
size with current density 0.8A/Sq.mm)
(3) Two Nos. (1W + 1S) Soft Starter for min. 30 kW
Motor or higher as per pump Manufacturer reco. with
suitable derating and with 80A TPN Motor Duty MCCB,
80A AC3 duty line & external bypass contactor, Ten
channel temperature scanner with potential free contacts,
fast acting fuse, MFM with RS-485, door display key pad
& digital MPR+SPP with CBCT, on, off, trip Indicating
208 lamps & ON, E-STOP, Local/Remote, Auto/ Manual 1.00 1122000.00 Set
selector switch & LCS for Pump- MOV Actuator with
Indication & push button etc.
(4) Two nos. 40A FP Microprocessor MCCB feeder for
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
(5) Two nos. 63ATPN MCCB feeders (for 1 nos PDB -
Auxiliary accessories load, Spare)
(6) 2 no. 32A TPN MCCB spare.
(7) One no. Outdoor lighting LDB feeder with 32ATPN
'C' curve MCB with 32A contactor & Time switch.
(8) 3 nos. 32A 'C' curve MCB feeders (for Indoor LDB,
2nos. spare feeders)
(9) 4nos. 16A DP MCB feeders (for Spare.)
(10) 3nos. 200A/1A, Cl.-0.5 metering CT
(11) 3nos. 200A/1A, Cl.-1. APFC CT
(12) 2nos. Multiplication relay for dry run protection of
MPS TO KARAI NETWORK
Design, supplying, installing, and testing of a factory-
fabricated, ready-made Three Phase APFC Panel. The
cubical panel fabrication shall be type-tested as per IEC
61921 and IEC 61439:1 & 2. Capacitor duty contactors
shall be provided for switching as per the required steps.
The incomer switch shall be of MCCB type with Icu = Ics
= 50 kA at 400/440 volts and shall include overcurrent
(OC), short-circuit (SC), and internal earth fault
protection. The panel shall include copper tinned insulated
busbars and shall be an indoor type cubical panel with
IP43 and IK10 protection. It shall be equipped with
metalized polypropylene film-type 3-phase 550-volt
capacitors and a detuning reactor for each capacitor. The
panel shall have short-circuit and overload protection, and
each capacitor step shall include a suitable MCB with SC,
OL, and internal earth fault relay. Each stage shall be
provided with a stage contactor (capacitor load rating).
The power factor (PF) regulator master controller shall
have suitable steps with an LCD display and an RS-485
communication port. Indication LED lamps shall be
provided for the main incomer and for ON/OFF status of
each capacitor bank. The panel shall include an MS
channel for floor mounting, cable entry as per site
conditions, and cooling fans for proper ventilation.
95 KVAR capacity: APFC panel consisting following
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
(1) 160 A FP Microprocessor MCCB I/C.
(2) 5 Steps Microprocessor APFC Relay with sensitivity
(3) 1 no. 30 kVAR capacitor bank with 63A 'D' curve
MCB & 30 kVAR Capacitor duty contactor with timer.
(4) 1 no. 20 kVAR capacitor bank with 40A 'D' curve
MCB & 20 kVAR Capacitor duty contactor with timer.
(5) 3 nos. 10 kVAR capacitor bank with 20A 'D' curve
MCB & 10 kVAR Capacitor duty contactor with timer.
(6) 3 nos. 5 kVAR capacitor bank with 16A 'D' curve
MCB & 5 kVAR Capacitor duty contactor with timer.
(7) All capacitors shall be Gas Filled type with dielectric
losses ≤ 0.2w/kVAR.
(Suitable for 0.95 or better Correction).
Design, supplying, installing, and testing of a factory-
fabricated, ready-made Three Phase APFC Panel. The
cubical panel fabrication shall be type-tested as per IEC
61921 and IEC 61439:1 & 2. Capacitor duty contactors
shall be provided for switching as per the required steps.
The incomer switch shall be of MCCB type with Icu = Ics
= 50 kA at 400/440 volts and shall include overcurrent
(OC), short-circuit (SC), and internal earth fault
protection. The panel shall include copper tinned insulated
busbars and shall be an indoor type cubical panel with
IP43 and IK10 protection. It shall be equipped with
metalized polypropylene film-type 3-phase 550-volt
capacitors and a detuning reactor for each capacitor. The
panel shall have short-circuit and overload protection, and
each capacitor step shall include a suitable MCB with SC,
OL, and internal earth fault relay. Each stage shall be
provided with a stage contactor (capacitor load rating).
The power factor (PF) regulator master controller shall
have suitable steps with an LCD display and an RS-485
communication port. Indication LED lamps shall be
provided for the main incomer and for ON/OFF status of
each capacitor bank. The panel shall include an MS
channel for floor mounting, cable entry as per site
conditions, and cooling fans for proper ventilation.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
75 KVAR capacity: APFC panel consisting following
(1) 160 A FP Microprocessor MCCB I/C.
(2) 8 Steps Microprocessor APFC Relay with sensitivity
(3) 1 no. 30 kVAR capacitor bank with 63A 'D' curve
MCB & 30 kVAR Capacitor duty contactor with timer.
(4) 1 no. 20 kVAR capacitor bank with 40A 'D' curve
MCB & 20 kVAR Capacitor duty contactor with timer.
(5) 1 nos. 10 kVAR capacitor bank with 20A 'D' curve
MCB & 10 kVAR Capacitor duty contactor with timer.
(6) 3 nos. 5 kVAR capacitor bank with 16A 'D' curve
MCB & 5 kVAR Capacitor duty contactor with timer.
(7) All capacitors shall be Gas Filled type with dielectric
losses ≤ 0.2w/kVAR.
(Suitable for 0.95 or better Correction).
Design, supplying, installing, and testing of a factory-
fabricated, ready-made Three Phase APFC Panel. The
cubical panel fabrication shall be type-tested as per IEC
61921 and IEC 61439:1 & 2. Capacitor duty contactors
shall be provided for switching as per the required steps.
The incomer switch shall be of MCCB type with Icu = Ics
= 50 kA at 400/440 volts and shall include overcurrent
(OC), short-circuit (SC), and internal earth fault
protection. The panel shall include copper tinned insulated
busbars and shall be an indoor type cubical panel with
IP43 and IK10 protection. It shall be equipped with
metalized polypropylene film-type 3-phase 550-volt
capacitors and a detuning reactor for each capacitor. The
panel shall have short-circuit and overload protection, and
each capacitor step shall include a suitable MCB with SC,
OL, and internal earth fault relay. Each stage shall be
provided with a stage contactor (capacitor load rating).
The power factor (PF) regulator master controller shall
have suitable steps with an LCD display and an RS-485
communication port. Indication LED lamps shall be
provided for the main incomer and for ON/OFF status of
each capacitor bank. The panel shall include an MS
channel for floor mounting, cable entry as per site
conditions, and cooling fans for proper ventilation.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
135 KVAR capacity: APFC panel consisting following
(1) 160 A FP Microprocessor MCCB I/C.
(2) 5 Steps Microprocessor APFC Relay with sensitivity
(3) 2 no. 30 kVAR capacitor bank with 63A 'D' curve
MCB & 30 kVAR Capacitor duty contactor with timer.
(4) 2 no. 20 kVAR capacitor bank with 40A 'D' curve
MCB & 20 kVAR Capacitor duty contactor with timer.
(5) 2 nos. 10 kVAR capacitor bank with 20A 'D' curve
MCB & 10 kVAR Capacitor duty contactor with timer.
(6) 3 nos. 5 kVAR capacitor bank with 16A 'D' curve
MCB & 5 kVAR Capacitor duty contactor with timer.
(7) All capacitors shall be Gas Filled type with dielectric
losses ≤ 0.2w/kVAR.
(Suitable for 0.95 or better Correction).
Design, supplying, installing, and testing of a factory-
fabricated, ready-made Three Phase APFC Panel. The
cubical panel fabrication shall be type-tested as per IEC
61921 and IEC 61439:1 & 2. Capacitor duty contactors
shall be provided for switching as per the required steps.
The incomer switch shall be of MCCB type with Icu = Ics
= 50 kA at 400/440 volts and shall include overcurrent
(OC), short-circuit (SC), and internal earth fault
protection. The panel shall include copper tinned insulated
busbars and shall be an indoor type cubical panel with
IP43 and IK10 protection. It shall be equipped with
metalized polypropylene film-type 3-phase 550-volt
capacitors and a detuning reactor for each capacitor. The
panel shall have short-circuit and overload protection, and
each capacitor step shall include a suitable MCB with SC,
OL, and internal earth fault relay. Each stage shall be
provided with a stage contactor (capacitor load rating).
The power factor (PF) regulator master controller shall
have suitable steps with an LCD display and an RS-485
212 communication port. Indication LED lamps shall be 2.00 141586.33 Set
provided for the main incomer and for ON/OFF status of
each capacitor bank. The panel shall include an MS
channel for floor mounting, cable entry as per site
conditions, and cooling fans for proper ventilation.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
25 KVAR capacity: APFC panel consisting following
(1) 40 A FP Microprocessor MCCB I/C.
(2) 5 Steps Microprocessor APFC Relay with sensitivity
(3) 5 nos. 5 kVAR capacitor bank with 16A 'D' curve
MCB & 5 kVAR Capacitor duty contactor with timer.
(4) All capacitors shall be Gas Filled type with dielectric
losses ≤ 0.2w/kVAR.
(Suitable for 0.95 or better Correction).
MPS TO KARAI NETWORK
SITC of Power Distribution Board (PDB) for MOV as
3 Phase 4 Wire TPN, 8 way Prewired LDB cum PDB for
Actuators and EOT and Aux. load.
Incoming: 63A TPN, MCB 'C' Curve
Outgoing: 6 nos. 6-32A TP MCB 'C' Curve
MPS TO KARAI NETWORK
SITC of Light Distribution Board (LDB) as under: (For
Indoor Lighting & Outdoor Lighting)
3 Phase 4 Wire TPN, 8 way Prewired LDB for Lighting
Incoming: 63A TPN, MCB 'C' Curve
Outgoing: 6 nos. 6-32A TP MCB 'B' Curve
MPS TO KARAI NETWORK
MEDIUM VOLTAGE CABLES
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured
cable multistrand Aluminium / Copper conductor for
KV. to be laid on wall with necessary clamps or in existing
trench / pipe of following size of cables
3.5C x 185 sq. mm. A2XFY Cable (2Run for Transformer-
1 & 2 to LT Panel)
3.5C x 70 sq. mm. A2XFY Cable (1Run for APFC)
3C x 95 sq. mm. A2XFY Cable (1Run each for each
Motor) 180.00 420.28 Mtr.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
MEDIUM VOLTAGE CABLES
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured
cable multistrand Aluminium / Copper conductor for
KV. to be laid on wall with necessary clamps or in existing
trench / pipe of following size of cables
3.5C x 120 sq. mm. A2XFY Cable (2Run for Transformer-
1 & 2 to LT Panel)
3.5C x 70 sq. mm. A2XFY Cable (1Run for APFC)
3C x 95 sq. mm. A2XFY Cable (1Run each for each
Motor) 180.00 420.28 Mtr.
MEDIUM VOLTAGE CABLES
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured
cable multistrand Aluminium / Copper conductor for
KV. to be laid on wall with necessary clamps or in existing
trench / pipe of following size of cables
3.5C x 300 sq. mm. A2XFY Cable (3Run for Transformer-
1 & 2 to LT Panel)
3.5C x 185 sq. mm. A2XFY Cable (1Run for APFC
3C x 95 sq. mm. A2XFY Cable (1Run each for each
Motor) 300.00 420.28 Mtr.
MEDIUM VOLTAGE CABLES
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured
cable multistrand Aluminium / Copper conductor for
KV. to be laid on wall with necessary clamps or in existing
trench / pipe of following size of cables
3.5C x 95 sq. mm. A2XFY Cable (1 Run Incomer Panel to
MPS TO KARAI NETWORK
4C x 16 sq. mm. A2XFY Cable (1Run for APFC)
MPS TO KARAI NETWORK
3C x 35 sq. mm. A2XFY Cable (1Run each for each
Motor) 60.00 189.14 Mtr.
MPS TO KARAI NETWORK
4C x 6 sq. mm. A2XFY Cable (For Outdoor LDB, Indoor
MPS TO KARAI NETWORK
4C x 2.5 sq. mm. 2XWY/2XFY Cu Cable (For Motor
Operated Valves)
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
3C x 2.5 sq. mm. 2XWY/2XFY Cable (For Outdoor light /
MPS TO KARAI NETWORK
2C x 2.5 sq. mm. 2XWY/2XFY Cu Cable (For 5 Nos.
Motor space heater (as required)), HT Panel, for 2nos.
APFC CT & X'mer marshaling box Single Phase Supply,
for level switch)
MPS TO KARAI NETWORK
10C x 1.5 sq.mm. 2XWY/2XFY Cable (2Run Tr. to HT
Panel control cable)
MPS-1 TO STP 360.00 393.20 Mtr.
12C x 1.5 sq.mm. 2XWY/2XFY Cable (For Actuator LCS
of 5 nos. Pump and Header)
MPS TO KARAI NETWORK
10Tride x 1.0 sq.mm. individual triad and overall shielded
with aluminum mylar tape Signal Cable for RTD & BTD
of motor (1Run Motor to VFD Panel)
CABLE END TERMINATION AND CONNECTION:
Providing and, fixing heavy duty flange type brass double
compression type cable gland with rubber ring for PVC
insulated armoured cable complete with out going tails,
insulating tape etc for following size of cables.
Solder less crimping type Aluminium lugs conforming to
IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals
with brass / cadmium plated nut bolts in an approved
1) Earthing the glands and arm ouring with earthing
219 clamp and jumper and also connecting to common earth 12.00 558.30 Nos.
bar. 2) The job also includes, if necessary, supply & fixing
of extension busbar of same material on MCCB or panel
board terminal / connector to connect more than one no. of
parallel cables or to connect higher size cable to lower size
unit. The job also includes earthing the glands and armour
of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site
3.5C x 185 sq. mm. A2XFY Cable (2Run for Transformer-
1 & 2 to LT Panel)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
3.5C x 50 sq. mm. A2XFY Cable (1Run for APFC)
3C x 95 sq. mm. A2XFY Cable (1Run each for each
Motor) 6.00 254.53 Nos.
CABLE END TERMINATION AND CONNECTION:
Providing and, fixing heavy duty flange type brass double
compression type cable gland with rubber ring for PVC
insulated armoured cable complete with out going tails,
insulating tape etc for following size of cables.
Solder less crimping type Aluminium lugs conforming to
IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals
with brass / cadmium plated nut bolts in an approved
1) Earthing the glands and arm ouring with earthing
220 clamp and jumper and also connecting to common earth 12.00 319.64 Nos.
bar. 2) The job also includes, if necessary, supply & fixing
of extension busbar of same material on MCCB or panel
board terminal / connector to connect more than one no. of
parallel cables or to connect higher size cable to lower size
unit. The job also includes earthing the glands and armour
of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site
3.5C x 120 sq. mm. A2XFY Cable (2Run for Transformer-
1 & 2 to LT Panel)
3.5C x 95 sq. mm. A2XFY Cable (1Run for APFC)
3C x 95 sq. mm. A2XFY Cable (1Run each for each
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
CABLE END TERMINATION AND CONNECTION:
Providing and, fixing heavy duty flange type brass double
compression type cable gland with rubber ring for PVC
insulated armoured cable complete with out going tails,
insulating tape etc for following size of cables.
Solder less crimping type Aluminium lugs conforming to
IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals
with brass / cadmium plated nut bolts in an approved
1) Earthing the glands and arm ouring with earthing
221 clamp and jumper and also connecting to common earth 18.00 671.19 Nos.
bar. 2) The job also includes, if necessary, supply & fixing
of extension busbar of same material on MCCB or panel
board terminal / connector to connect more than one no. of
parallel cables or to connect higher size cable to lower size
unit. The job also includes earthing the glands and armour
of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site
3.5C x 300 sq. mm. A2XFY Cable (3Run for Transformer-
1 & 2 to LT Panel)
3.5C x 185 sq. mm. A2XFY Cable (1Run for APFC)
3C x 95 sq. mm. A2XFY Cable (1Run each for each
Motor) 10.00 254.53 Nos.
CABLE END TERMINATION AND CONNECTION:
Providing and, fixing heavy duty flange type brass double
compression type cable gland with rubber ring for PVC
insulated armoured cable complete with out going tails,
insulating tape etc for following size of cables.
Solder less crimping type Aluminium lugs conforming to
IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals
with brass / cadmium plated nut bolts in an approved
1) Earthing the glands and arm ouring with earthing
222 clamp and jumper and also connecting to common earth 2.00 290.64 Nos.
bar. 2) The job also includes, if necessary, supply & fixing
of extension busbar of same material on MCCB or panel
board terminal / connector to connect more than one no. of
parallel cables or to connect higher size cable to lower size
unit. The job also includes earthing the glands and armour
of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site
3.5C x 95 sq. mm. A2XFY Cable (1 Run Incomer Panel to
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
4C x 16 sq. mm. A2XFY Cable (1Run for APFC)
MPS TO KARAI NETWORK
3C x 35 sq. mm. A2XFY Cable (1Run each for each
Motor) 4.00 126.20 Nos.
MPS TO KARAI NETWORK
4C x 6 sq. mm. A2XFY Cable (For Outdoor LDB, Indoor
MPS TO KARAI NETWORK
4C x 2.5 sq. mm. 2XWY/2XFY Cable (For Motor
Operated Valves)
MPS TO KARAI NETWORK
3C x 2.5 sq. mm. 2XWY/2XFY Cable (For Outdoor light /
MPS TO KARAI NETWORK
2C x 2.5 sq. mm. 2XWY/2XFY Cable (For 5 Nos. Motor
space heater (as required))
MPS TO KARAI NETWORK
10C x 1.5 sq.mm. 2XWY/2XFY Cable (2Run Tr. to HT
Panel control cable)
MPS-1 TO STP 24.00 83.00 Nos.
12C x 1.5 sq.mm. 2XWY/2XFY Cable (For Actuator LCS
of 5 nos. Pump and Header) HT Panel, for 2nos. APFC
CT & X'mer marshaling box Single Phase Supply, for
MPS TO KARAI NETWORK
10Tride x 1.0 sq.mm. individual triad and overall shielded
with aluminum mylar tape Signal Cable for RTD & BTD
of motor (1Run Motor to VFD Panel)
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supply & laying GI ladder type cable trays with side
channels of size - 75 x 15 x 15 mm / 100 x 15 x 15 mm &
rungs of size - 35 x15 x 15 mm spaced at 250 mm apart,
fabricated from 2 mm thick sheet steel in standard length
of 2.5 meter, duly hot dipped galvanized after fabrication
as per IS 2629-1989/ IS 4759-1984 including accessories
223 such as coupler plates/ fish plates, bends, tees, reducers, 240.00 558.00 Mtr.
elbows, covers and electro-galvanized hardware etc,
erected on existing support as per specification and
instruction of Engineer-in-charge.
Size:- 600(W) x 100(H) x 2.0 mm Thick - Ladder type
Size:- 300(W) x 100(H) x 2.0 mm Thick - Ladder type
MPS-2 TO STP 680.00 456.00 Mtr.
MPS TO KARAI NETWORK
Size:- 150(W) x 75(H) x 2.0 mm Thick - Ladder type
MPS-2 TO STP 1050.00 336.00 Mtr.
MPS TO KARAI NETWORK
CHEMICAL EARTHING SYSTEM
SITC of Maintenance free chemical earthing (copper) with
earthpit of minimum bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in Pipe Technology as per IS-
3043:1987 /Tech spec. made of corrosion free Pipes
having Outer pipe dia of 48 mm having 250 Micron
copper plating,
Inner corrosion free Hot dip galvanised (80 to 100 micron)
pipe dia of 26 mm with copper flat strip type connection
terminal 14mm dia with constant ohmic value surrounded
224 by highly conductive corrosion resistant chemical 30.00 10494.73 Nos
compound with high charge dissipation suitable for
electrical installation & of 3Mtr. length of Pipe with two
nos. 25Kg. bag of Back filling compound.
(2 Nos Each for HT Panel, Transformer Neutral - TR-1 &
2, 2 pole structure)
NOTE: Earthing Resistance value & date shall be painted
on the chamber cover.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
CHEMICAL EARTHING SYSTEM
SITC of chemical earthing with earthpit of minimum bore
size dia. 225mm Safe Earthing Electrode consisting Pipe-
in-Pipe Technology as per IS-3043:1987 made of
corrosion free G.I. Pipes having Outer pipe dia of 80 mm
having 80-200 Micron galvanising, Inner pipe dia of
mm having 200-250 Micron galvanising or copper coated
solid steel road / flat strip type connection terminal 14mm
dia with constant ohmic value surrounded by highly
conductive corrosion resistant chemical compound with
225 high charge dissipation suitable for electrical installation 66.00 7028.82 Nos
of 11 kV & 440V of 2Mtr. length of Pipe with one no.
25Kg. bag of Back filling compound. (2 Nos Each for
Transformer Body - TR-1 & 2, LT Panel, APFC Panel,
Nos Each for Motor and all elec. equipments)
NOTE: Earthing Resistance value & date shall be painted
on the chamber cover.
MPS TO KARAI NETWORK
SITC of 50mm(w) x 6mm(T) etc. sizes as required, HOT
deep GI Strip including supply & fixing using GI spacers,
saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the
building & interconnection with earth pit & all electro-
226 mechanical equipments. 2160.00 77.17 Kg
(50X6 G.I Strip wt.2.4 kg/m, 2.4x250Mt.=600kg.)
MPS TO KARAI NETWORK
Supply, laying and erection of 25mm(w) x 3mm(T) etc.
sizes as required, HOT deep GI Strip including supply &
fixing using GI spacers, saddles when laid inside the
building and inclusive of excavation & refilling of earth
when laid outside the building & interconnection with
227 earth pit & all electro-mechanical equipments. 450.00 77.17 Kg
(25X3 G.I Strip, 0.6 Kg/m, 0.6x200Mt.=120Kg.)
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supply, laying and erection of 40mm(w) x 6mm(T) etc.
sizes Copper Strip including supply & fixing of bolts,
saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the
building & interconnection with earth pit & Tr. nutral.
MPS TO KARAI NETWORK
SITC of HOT Dip Galvanized iron strip wire 8 SWG (For
LDB cum PDB etc.)
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 100Mt.= 10 Kg)
229 MPS-1 TO STP 35.00 77.17 Kg
MPS TO KARAI NETWORK
INTERNAL WIRING
SITC of Mains & outlet points wiring with 1.1 kV grade
FRLS PVC insulated ISI marked flexible stranded copper
conductor wires with medium class min. 25mm. dia.
Rigid PVC pipe and accessories to be erected
concealed in / to be run on surface / wall / ceiling with
following sizes as mentioned below. The unit rate wirings
shall be with connector, PVC junction box, wires, holder,
ceiling rose, angle holder, switch, sockets, switch
board, brass chromium / cadmium plated machine screws,
phase and neutral wires, green Earth continuity wires etc.
as required to complete wiring from LDB panel to the
final outlet termination points. The wiring shall be as
per IS:732, IS:4648 and as per tender specification /
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
MPS TO KARAI NETWORK
As per Sr. No.-8.1 (b) SITC of Mains wiring with 3 wire
2.5 sq.mm as per tender specification & IS.
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SITC of Point wiring for Light / fan / Bell / Primary Point
with 2nos. 1.5 sq. mm & earth wire of 1.5 sq. mm (green)
both are of ISI marked 1.1 kv grade FRLS PVC insulated
multistrand copper wires, pipe to be erected concealed
in flushed on wall / ceiling, complete with 6A Tissino
Type ISI marked flush type switch / bell push &
accessories erected on metal / PVC Box covered with
mm thick PC (Polycarbonate) / Acrylic sheet with
necessary lamp holder / ceiling Rose / H. D. connector as
directed with medium class Rigid PVC pipe & accessories.
MPS TO KARAI NETWORK
SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu.
Mains size wiring & earthwire of 1.5 sq.mm (green) both
are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC
pipe and accessories to be erected on wall / ceiling,
complete with ISI marked 3 / 5 Pin socket and tissino type
233 switch erected with earth continuity connection erected on 21.00 310.60 Nos
Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet. (6 Nos for Pump House)
MPS TO KARAI NETWORK
SITC of One 300/380 mm dia. Ex fan 16A independent
Plug point near Ex. Fan with 2nos. 4 sq.mm Cu.
Mains size wiring & earthwire of 1.5 sq.mm (green)
both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC
pipe and accessories to be erected on wall / ceiling,
complete with ISI marked 3Pin socket and tissino type
234 switch erected with earth continuity connection erected on 16.00 704.60 Nos
Metal / PVC box covered with 3 mm thick PC
(Polycarbonet) / Acrylic sheet. Plug point shall be near
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu.
Mains size wiring & earthwire of 1.5 sq.mm (green) both
are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC
pipe and accessories to be erected on wall / ceiling,
complete with ISI marked 3 / 5 Pin socket and tissino type
235 switch erected with earth continuity connection erected on 21.00 489.47 Nos
Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet. (6 nos. at Pump House)
MPS TO KARAI NETWORK
LED LIGHT FIXTURES:
SITC of LED indoor fittings with LEDs of wattage
Watt to 0.5 Watt assembled on single MCPCB, with
housing used as a heat sink shall be made of thick sheet
Steel conforming to IS: 513/CRCA/ aluminium die cast
powder coated and high U.V. & corrosion resistance with
diffuser with company mark/name 160V to 270V, Power
Factor more than 0.9, THD < 15%,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt ,LED
LED driver efficiency > 85 %
236 (fitting required LM-79 & LM-80 Certificates)(NOTE: 40.00 293.26 Nos
Below description have shown ranges of Wattage capacity
of LED fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.)
18-20 Watts, Surge - 2KV,IP-20, conventional 4 feet CAT-
(For 8 nos. Pump House, 3 Nos HT Room)
MPS TO KARAI NETWORK
Providing & erecting Approved make Power Saving
Watt Ceiling Fan with double ball bearing ISI mark with
Condenser 230 volt A.C. 50 Hz 1200 mm sweep complete
having 3blades with aluminium blades with , canopy &
cm. down rod erected with earthing.(Make shall be
approved by Engineer in charge)) Fan shall be painted
with white colour.
1 Nos for Operator room
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supplying and erecting 19 / 20 mm. nominal bore Medium
Class M.S. Pipe down rod erected duly painted for fan
complete with proper insulation without leakage and
1 Meter Down Road or as per instruction given by
engineer Incharge.
MPS TO KARAI NETWORK
Supplying & erecting Fan Hook of 10 mm M.S. Round bar
grouted in RCC slab with Making the site as original.
MPS TO KARAI NETWORK
Supplying & erecting fan hook box of 10 mm M.S. round
bar bounded to the RCC bars up to 50mm length each side
and pierced through a 16 Gauge M.S. box / Heavy Duty
PVC box complete erected concealed in Ceiling with
240 necessary finishing. 4.00 107.13 Each
MPS TO KARAI NETWORK
Providing Fan clamp of 30 x 5 mm flat of required length
& 10 mm M.S. Bolt & Nuts erected with necessary hook
of 10 mm M.S. Round Bar.
241 MPS-1 TO STP 4.00 98.13 Each
MPS TO KARAI NETWORK
Providing 2.5mm.thick laminated acrylic sheet to cover the
fan hook or Fan box.
MPS TO KARAI NETWORK
380mm sweep 1400 R.P.M exhaust fan, capacitor type,
having double ball bearing, M.S.blades, mounting
frame, forearms, suitable to operate on 230V,50 HZ AC
supply conforming to IS: 2312.Fan shall be painted with
epoxy grey colour controlled by one 6 A flush type switch
243 on board and 6A plug point near Ex. fan. 16.00 3052.47 Nos.
(2 nos. Wet Well)
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
LED LIGHT FIXTURES & LIGHTING:
SITC of 40W LED Surface / Wall mounted LED Flood
Light fittings with High power White LEDs wattage of
1Watt and above assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free High pressure die
cast aluminum housing with smooth finish powder coated
and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name
engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %,
CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy>
lumens/watt . LED driver efficiency > 85 %.
(Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: (2 nos. at Pump House)
MPS TO KARAI NETWORK
EXTERNAL LIGHTING (Flood LIGHT):
SITC of 70W LED Wall mounted LED Flood Light
fittings with High power White LEDs wattage of 1Watt
and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast
aluminum housing with smooth finish powder coated and
heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name
engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %,
CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy>
lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (12 nos. for area lighting)
MPS TO KARAI NETWORK
SITC of 'B' class galvanised iron pipe 32 mm outside dia
45 cms long duly welded on 20 cms x 20 cms x 3 mm
thick M.S. base plate, erected on wall or corner for
mounting luminaire with necessary hardware materials
duly painted for wall mounting indoor & outdoor flood
light fixtures on Wall of Buildings.
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
SAFETY ACCESSORIES
SITC of following safety accessories complete with
necessary fixing brackets, other accessories and tools
etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher
of 6.5kg capacity with necessary clamps made from 50 x
247 mm M.S. Flat with nut & bolts grouted in wall complete. 26.00 8586.26 Nos
(For 2 Nos for HT Room, 2 nos. for X'mer-1 & 2, 4 no.
MPS TO KARAI NETWORK
Supplying stand first AID box with anticeptic cream,
medicine for use on wounds due burn, crepe bandage,
guage bandage, medicated ready to use bandage (Band-
aid) adhesive tape for medicinal user, scissors, anticeptic
solution (Savlon or similar) etc. (All above contents shall
248 be of standard makes) (1 no. for HT Room, 1 no. for Pump 7.00 297.00 Nos.
MPS TO KARAI NETWORK
Providing printed instruction (First Aid) Chart both in
English and Gujarati and duly framed with front glasses,
for treatment of person suffering from electric shock.
(1no. For Pump Room)
MPS TO KARAI NETWORK
Supplying and erecting floor mounting stand for keeping
four nos. of FIRE buckets comprising 1500 mm in length,
900 mm height frame made out of 30mm X30 mm X
mm angle iron with cross supports for legs, welded with
hooks and duly painted with one coat of red lead and two
250 coats of approved enamelled silver paint. 7.00 933.43 Nos
For HT Panel, Tr. 1 &
MPS TO KARAI NETWORK
Supply and laying of 12 mm thickness, Rubber Matting as
per as per IS:15652/IEC 61111. (for Torrent HT, AMC
251 MPS-1 TO STP 18.00 3051.00 Sqmtr
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Supply and laying of 4 mm thickness, Rubber Matting as
per as per IS:15652/IEC 61111. (for Torrent HT, AMC
HT, LT & APFC etc. Panels)
252 MPS-1 TO STP 74.00 1017.00 Sqmtr
MPS TO KARAI NETWORK
Providing pair of rubber hand gloves suitable for working
on 11 KV/22 KV supply.
MPS TO KARAI NETWORK
Providing, Supply of Structure Steel at site of work with
freight, loading, unloading carting, etc. including all taxes
and duties complete such as joints, channels, angles, Iron
Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates
(below 10mm thickness) etc. required for support structure
of Elecrto-Mechanical equipments etc. for support on
floor / wall / beam / brackets etc. as per tender and IS.
MPS TO KARAI NETWORK
Labour Charges for lowering, laying, Fixing with
fabrication various size section of MS such as joints,
channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat,
Plates, Chequered plates etc Complete with two coats of
red oxide and two coats of approved colour shade of
epoxy paint as per relevant IS and as per specification.
MPS TO KARAI NETWORK
Supplying & fixing Steel Chequered Plate having 7 mm
thickness, duly painted with two coats of black Japan
colour. (Average Wt 61.1 kg / Sq.Mtr)
256 MPS-1 TO STP 68.00 3498.84 Sq. Mtr
MPS TO KARAI NETWORK
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
Operation and maintenance and repairing of U/G Drainage
Scheme in all respect i.e. all the civil components executed
under this tender mainly sewer collecting line, house
connections , rising main, pumping station , Area
Development Works including all materials on repairing
257 of pipe line and other civil works and pumping machinery
as per detailed specification & obligatory requirement for
satisfactory maintaining the record for same including all
supply of suitable equipment and machinery, consumable,
labour, tools, power cost to operate & maintenance of the
project as per specifications and directions of Engineer-in-
O & M for 1st year Rs. 12.00 2,75,302.62 Months
O & M for 2nd year Rs. 12.00 2,75,302.62 Months
O & M for 3rd year Rs. 12.00 2,75,302.62 Months
O & M for 4th year Rs. 12.00 2,75,302.62 Months
O & M for 5th year Rs. 12.00 2,75,302.62 Months
Electro-mechanical works – Operation, Maintenance and
Repair of all electro-mechanical equipments including but
not limited to pumps, motors, pump house piping, all types
of valves, expansion bellows, flow meters, pressure
gauges, specials, MS structures, lighting arrangements,
cranes, switch yard works, all types of HT & LT cables
with termination kits, lugs/glands including cable trays and
258 trenches, transformers, HT & LT panels, starter panels,
capacitor panels, battery chargers, earthing works and all
other allied miscellaneous items such as instruction charts,
rubber mats, fire extinguishers, etc., complete as per
specifications and directions of Engineer-in-Charge.
O & M for 1st year Rs. 12.00 98,990.78 Months
O & M for 2nd year Rs. 12.00 98,990.78 Months
O & M for 3rd year Rs. 12.00 98,990.78 Months
O & M for 4th year Rs. 12.00 98,990.78 Months
O & M for 5th year Rs. 12.00 98,990.78 Months
Comprehensive Operation and Maintenance (O&M) of the
complete 30.00 MLD Sewage Treatment Plant and all
components executed under this tender, including
breakdown/emergency maintenance, day-to-day operation,
preventive and periodic maintenance, and major
maintenance, special repairs and replacements, including
training of AUDA O&M staff and maintenance of all
O&M records as per tender specifications.
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
The scope includes operation, maintenance and repair of
all civil, mechanical and electro-mechanical works such as
pumping machinery, pumping stations, rising mains,
pipelines and allied civil works.
The work shall include operation, maintenance and repair
of all electro-mechanical equipments including pumps,
motors, pump house piping, valves, expansion bellows,
flow meters, pressure gauges, specials, MS structures,
259 lighting systems, cranes, switchyard, transformers, HT &
LT panels, starter panels, capacitor panels, battery
chargers, cables with termination kits, lugs, glands, cable
trays/trenches, earthing systems and other miscellaneous
items such as instruction charts, rubber mats and fire
extinguishers, complete.
The quoted rate shall be inclusive of all fixed charges,
consumables, flow-dependent charges, maintenance and
repair charges, replacement charges, insurance,
establishment charges and manpower deployment,
including all materials required for repairs of pipelines,
civil works and pumping machinery, but excluding the
cost of electrical power.
O & M for 1st year Rs. 12.00 8,23,479.50 Months
O & M for 2nd year Rs. 12.00 8,80,765.52 Months
O & M for 3rd year Rs. 12.00 9,42,527.03 Months
O & M for 4th year Rs. 12.00 10,09,148.95 Months
Sr. No. Description Qty. Rate (Rs.) Unit Amount (Rs.)
O & M for 5th year Rs. 12.00 10,81,051.52 Months
I/We am/are willing to carry out the work at ________% above/below percent (should be written in figures and words) of the
Estimated amount put to tender Estimated amount put to tender
Deduct____% below Add____% Above
In words In words
1. All work shall be carried out as per Public Works Department Handbook and other specifications of Division or as directed.
2All columns in the Schedule should be filled in ink and the total of the entire in the last columns should be struck by the contractor
under his signature.
3 Rates quoted include clearance of site (prior commencement of work and at its close) in all respects and hold
good for work under all conditions, site, moisture, weather etc.
4. To be continued on additional sheets, if found necessary.
5. The Labour Cess will be deducted as per prevailing rules i.e.1% of the work done.
6. GST is applicable seperatly for all type of works by the Client (Total Tender Cost is without GST).
7. The bituminous work shall be carried out by the contractor or as under by utilizing.
8. For abnormal high or law rates payment of such items shall be regulated as per Govt. Circular letter No.
Parach-102008-61-S dated 27-11-2008 attached with tender papers.
9.From dt. 1-7-2017 GST is applicable hence Agency should quote price accoringly. Any dispute regarding this
will not be considered by AUDA
10. The Contractor shall exhibit a board with detailed specification and details of work as directed by the EngineerIn-Charge for
which no extra payment shall be made.
11. GST and Income tax TDS will be deducted at a source while making payments of bills.
12 In all R.C.C. Items in Rate Analysis Standard Cement Consumption has been taken as per Govt. G.R.: PRC10/2017
Cement Consumption/16/C Date:11/05/2017 as stated in
S.O.R. therefore in R.C.C. items where there is a change as per
actual mix design the cost of difference of cement consumption have been deducted from th rate of original item at the rate of input
rate mentioned in SOR used for preparation of Estimate.
Signature of Contractor
Executive Engineer
Ahmedabad Urban Development Authority (AUDA)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
BOQ.pdf
Extra Condition Gujarati.pdf
Item wise Specification.pdf
SBD.pdf
Road Specification.pdf
Special Condition of Contract.pdf
Standards for cement consumption.pdf
STP Item Wise Specification_compressed.pdf
GAD Pumping Station.pdf
Mechanical Electrical.pdf
Rising Main Network Drawing for TP-411.pdf
RISING MAIN NETWORK DRAWING.pdf
Storm Network.pdf
STP.pdf
TYPICAL DRAWING OF STEEL BRIDGE DWG.pdf
Typical Drawings.pdf
Network Drawing for All TP Zone Wise 1.pdf
Network Drawing for All TP Zone Wise 2.pdf
Network Drawing for All TP Zone Wise 3.pdf
Network Drawing for All TP Zone Wise 4.pdf
Network Drawing for All TP Zone Wise 5.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .