Line Intractive UPS with AVR Average Turn Over of Last 3 Years 8 Lakh (s) Experience with Gov. Required 10 Year (s) Line Intractive UPS With AVR ( 46 ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Allowed Values GENERIC Rating in KVA/min VAH capacity of battery (KVA/VAH) 1.0/168 * Technology MOSFET-PWM MOSFET-PWM
IGBT- PWM Type of battery SMF-VRLA confirming to JISC-8702 Pt 1
2 &3 SMF-VRLA confirming to JISC-8702 Pt 1
2 &3 Rated Output (Volt) Single phase sinewave 230v AC
50Hz Single phase sinewave 230v AC
50Hz
Single Phase Quasi-Sin-wave 230 V AC
50 Hz Degree of protection IP-21 IP-21
IP 20 Inverter Efficiency (%) >/= 70% >/= 60%
>/= 70% Warranty for the battery from the 1 year 1 year
3 Years 1/4 date of delivery Warranty for Line Interactive UPS 2 Years 1 Year
2 Years
5 Years
3 Years Installation and commissioning instructions No * CONSTRUCTIONAL Type of enclosure ABS * AC out put for printer (not through inverter) Yes Yes
No Inverter out put socket AC out put for printer (not through inverter) 3 Three pin 2 Three pin
3 Three pin
Hard wiring
Not applicable FUNCTIONAL Total harmonic distorsion (%) </= 40% * Input (Volt) Single phase sinewave(160-280v) * Switching over time (Mili sec) Maximum 10 milli seconds * Overload Time (Minutes) >/= 10 minutes * Load power factor >/= 0.6 * Variation in AVR output in AC mode (%) AVR (Voltage regulation) output voltage in AC Mode 230 Volts +/-9%
50 +/-3 Hz * Overload (%) >/=10% * Variation in output voltage in battery mode (%) (UPS output voltage in battery mode) 230 Volts +/- 10% * Variation on output frequency in battery mode (Hz) </=0.5 * PROTECTION Protection against (over discharge) discharge per 12v battery (Volt) 10.5 * Protection for outside input voltage range: If Input voltage goes outside the range 160 to 280 Volts
the system shall switch over to battery mode Yes * 2/4 Protection against short circuit of UPS Yes * Protection for over voltage and over load Yes * REPORTS AND CERTIFICATIONS Damp heat Test at 45 degree
RH -95% for 2-cycle as per IS:9000 pt-5/sec-1 Yes * Dry heat Test at 45 degree for 16 Hrs as per IS:9000 pt-3/sec-5 Yes * Cold Test as per IS:9000 pt-2/sec-4 Yes * Availability of the type test report from central Govt./NABL/ILAC Accredited Lab Yes * Type Test certificate no. and date - * Name Of Lab - * Address of Lab - * As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes * * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 SUJAY KUMAR 522004