Loading…
Loading…
Tender Value
₹3.0 Cr
EMD Value
₹3.0 L
Closing Date
30 Sept 2026, 6:00 pm2d left
Municipal Commissioner, Ahmedabad.
Augmentation work for Electrical, Mechanical & Instrumentation works with 3 years Comprehensive O&M for Existing E-3 Sewage Pumping Station (SPS) at Shahpur Riverfront of Ahmedabad Municipal Corporation (AMC)
346675
21 /2026-27
Open
Miscellaneous Works
Works
Ahmedabad
3 documents required · 3 mandatory
₹6,000
MUNICIPAL COMMISSIONER AHMEDABAD
₹3.0 L
19 Sept 2026
19 Sept 2026
19 Sept 2026
30 Sept 2026
19 Sept 2026
Name of Work : Augmentation work for Electrical, Mechanical & Instrumentation works with 3 years Comprehensive O&M for Existing E-3
Sewage Pumping Station (SPS) at Shahpur Riverfront of Ahmedabad Municipal Corporation (AMC).
Earnest Money Rs. : Rs. 3,02,900/-
Date of Opening of Tender :
Estimated Price : Rs. 3,02,84,670/-
1) I / We am / are willing to carry out work at _________ % above/below percent (in figures) (should be written in figures and words) of the
estimated cost, as mentioned above. Amount of my / our tender works out for Rs. ________________ (in figures)
Estimated amount put to tender Rs. Estimated amount put to tender Rs.
Signature of Contractor
Company’s seal :
SUMMARY OF SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-
MECHANICAL & INSTRUMENTATION WORKS WITH 3 YEARS OPERATION AND
COMPREHENSIVE MAINTENANCE FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT
(SRFDCL) OF AMC.
No. Amount (Rs.)
A MECHANICAL & INSTRUMENTATION WORKS
B ELECTRICAL WORKS
C O&M FOR 3 YEARS
I TOTAL CAPITAL COST WITHOUT GST ( A + B + C )
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
1.1.1 SUBMERSIBLE NON-CLOG PUMP SET 4 Set 26,64,000.00
Supply, installation, testing and commissioning (SITC) of Submersible NC Pump-Motor
set suitable for sewage application with semi-open or enclosed or suitable type Impeller &
wear Rings in CF8M with CI FG 260 Casing & casing cover, SS 410 shaft & with motor
suitable for 3-Phase, 415 V, 50 Hz., AC induction Air filled dry type submersible motor of
mini. rating as specified having max. 1000 RPM sync. speed, insulation Class 'F' With
temp. rise limited to class B and IP-68 protection.
The scope shall include all required accessories viz. automatic coupling device, SS-304
heavy duty & of suitable size double guide pipes of length to suit the sump height with
required supports, SS-304 or suitable stainless steel grade Chain with shackles (shall be
with dual hook / shackles of 100 mm or suitable higher size at app. every 1.5m C-C
distance) & of length as per existing sump height + min. 3m, Submersible Power & control
cable (copper flexible & stranded type conductor of reqd. cores & size for each pump
motor set) & 15 m length of each run with necessary electrical termination connection at
junction box / starter panel and auto coupling & delivery bend, PMU etc. complete as per
IS, and Specification and also including in scope any other parts / accessories / fittings
required to complete the work in all respects & satisfactory operation of pump set.
Pump Capacity: 2625 m3 / hr., (Main pump)
Motor Rating: min. 105 kW (or higher rating as reco. by pump mfg.)
Over all Efficiency at Duty- min. 72%
(Note: 1. The scope also includes ensuring the pump set's compatibility with the existing
duck foot bend and pump foundation block. This compatibility will be verified at the time
of supply at existing location.
2. The scope also includes all civil work items / Foundation with positioning / fixing /
strengthening / anchoring / grouting / required hardware’s, any other fittings, accessories,
1.1.2 Item Description as per 1.1.1 and suitable for following duty parameters complete in all 2 Set 6,67,927.00
Main Pump Capacity : 875 m3 / hr (Trimmer pump)
Motor Rating: min. 30 kW (or higher rating as reco. by pump mfg.)
Over all Efficiency at Duty- min. 68.0%
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
2.1.1 LEVEL MEASURING SYSTEM FOR SUMP (RADAR TYPE) 1 Set 1,08,000.00
Supply, installation, testing and commissioning of Non-Contact Radar Type Level
Transmitter with 20 meter cable along with Process Indicator for Local Display (local
mounted process indicator shall be 2 wire supported) in WP enclosure with signal
retransmission, required length of power and signal cable from ICP cubicle, gland,
termination, required accessories, hardware, consumables, mounting stand, etc. complete
in all respects and as per specification etc. and having following measurement ranges for
Sewage application:
Meas. Range: upto 20 m (at sump)
The scope also includes providing 4" flanged puddle pipe approximate 300 mm long
including fixing of the same in existing civil structure slab of Sump for mounting of
sensor. The work also include all necessary work like make hole,repair / modificationin
existing slab, etc.
3.1.1 FIXED TYPE ELECTRIC CHAIN HOIST 4 Set 1,33,130.00
SITC of Electrically Operated Chain Hoist, suitable to fix on Existing Girder, having
motorised motion in vertical lifting , manufactured as per IS:6547-1972-Class-II & IS-
3177- Class-II, complete with electrically operated chain hoist, brake, chain-gear, motors,
safety device, pendant push button, starter panel, cables from motor to starter panel and all
other required accessories like limit switches, panel, power supply system (Fastoon cable
type), fasteners, epoxy painting, etc. tested for over load as per IS complete as per
specifications and complete in all respect.
Capacity : 1 Ton. Min. (For Manual Screen Lifting & Lowering)
'Lift : 15.00 m as mini. or as per site req.
4.1.1 Providing, Supply of Structure Steel at site of work with freight, loading, unloading 2,000 kg. 64.84
carting, etc. including all taxes and duties complete such as joints, channels, angles, Iron
Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates (min. 8 mm thickness) for cable
trench etc. required for support structure of all Electro-mechanical equipment, piping, etc.
for support on floor / wall / beam / brackets etc. as per tender and IS.
4.1.2 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS 2,000 kg. 11.37
such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered
plates, for cable trench etc Complete with two coats of red oxide and two coats of
approved colour shade of epoxy paint as per relevant IS and as per specification.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
5.1.1 SITC of Rolling shutter with red oxide primer & colour made of 80 mm wide M.S. laths 1 Lot 31,605.00
inter-locked together through their entire length and jointed together at the ends by locks
mounted on specially designed pipe shaft with bracket plates, guide channels and
arrangement for inside and outside locking with push-pull with gear operated complete but
excluding the cost of hood cover and spring. (B) shutters having width above 3.5 m or
following size at room and other required accessories to complete the work in all respects.
Size : 3.5 m H x 3 m W - 1 No. shutter (size shall be as per actual existing site) - approx.
6.1.1 Job-Work of repairing the inlet sluice gate by releasing jammed spindle 2 Nos 1,20,692.35
rod from head stock, by repairing or replacing the gunmetal nut and servicing and
functionalizing the gate at Existing SPS.
Scope also include straightening of bent spindle, removing and releasing the bent and
jammed spindle from head stock foundation after breaking the concrete by electric
demolition hammer, reinstating the buckled head stock, removing bent lengths, adding new
straight length of spindle with new coupler, welding and fixing the bolts to hold the head
stock, replacing the fixing gun metal nut and set of thrust bearings, replacing gears
damaged inside the gear box, fabrication and fixing of brackets to hold straight the spindle
during up-down operations, greasing all parts and refaxing the gate, with arrangement of
welding set, gas cutting set, demolition hammer, rotary hammer drill, hand tools, all safety
equipment’s to work inside the inlet chamber, hanging zoola, safety ropes, safety belts, etc.
complete work in all respect. (Satisfactory erection & operation of Gate shall be
responsibility of Bidder/contactor.)
6.1.2 Job-Work of repairing, fabricating and fixing brackets in between the 2 Nos 76,541.90
barrier and head stock fixed by anchor bolts on inlet chamber inlet, and repairing of
railings to work safely around top of screen chamber, at Existing SPS.
Scope also include removing and cutting old bolts by arranging and carting all tools,
welding and gas cutting sets, MS angles, pipes, arrangement of skilled workers who can
work at heights with safety, and hand tools, all safety equipment’s to work, anchor bolts,
and misc. jobs as directed by E-I-C. complete work in all respect. (Satisfactory erection &
operation of Gate shall be responsibility of Bidder/contactor.)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
6.2.1 SS REMOVABLE COARSE MESH SCREEN 1 No. 1,71,170
Supply, installation, testing, and commissining of Removable Box/trough type manual
coarse mesh screen having min following size made of Steel plate having size 10mm thick
and 50mm wide suitable for screen chamber with Ex. guide channel with two lifting lugs,
including followings and as per specifications.
The screen shall be with SS perforated Screening Material Collection Box/trough at
bottom end of Screen, fabricated from 3 mm thk SS sheet, suitable to slide in existing
guide channel (MCP-100) with all required hardware, SS nuts, bolts & wahsers & SS
lifting chain with 100 mm holding ring / hook at every 1.5 to 2 m length with each screen,
etc. and provided with 1 set of cleaning rake with each screen, complete as per
Screen Size : 1150 mm (Appx. W- or as per actual site) x 1500 mm (H)
Screening Collection Box Size: 1050 mm (W- or as per actual site) x 100 mm (D) x
clear opening : 50 mm clear spacing
(Note : For manual box screen items execution shall be based on the feasibility to install in
existing screen chamber as per site condition.)
6.3.1 Job-Work of repairing the inlet screens by releasing / removing / recovering old 2 Nos 1,43,284.90
damaged / bent / jammed screens from over head lifting arrangement, repairing or
replacing the damaged angles / channels / screen flat bars and side rollers, strengthening of
the screens, repairing inner guides installed in walls up to full possible bottom sewage
level, adding new mild steel flat bars, fabricating and fixing roller guide brackets in walls
in screen chamber inlet wall, at SPS.
Rate to include removing and cutting old fixtures by arranging and carting all tools,
welding and gas cutting sets, MS. angles, structural steel, arrangement of skilled workers
who can work at heights with safety, and hand tools, all safety equipment’s to work,
anchor bolts, and misc. jobs as directed. (Satisfactory erection & operation of Screen shall
be responsibility of Bidder/contactor.)
7.1.1 MISCELLANEOUS WORK 1 Lot 90,000.00
Dismantaling & removal / shifitng & Reinstall in existing SPS like 6 nos. Submersible NC
Pump sets, ECH, Rolling shutter, all electrical cables, LT Panel, Cable end termination
etc. any other equipments not listed here in but installed in pump house & required to be
dismantled / shifting and including all Loading, Transportation, Unloading & Stacking
them at Store or location as per instruction of Engineer-In-Charge of AMC and as per the
tender scope / BOQ.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
7.1.2 Providing and applying epoxy paint of approved make to concrete surface for RCC 1900 m2 90.00
structure including cleaning the surface by scrapping and air blowers to the satisfaction of
Engineer-in-charge necessary scaffolding etc. complete with all leads and lifts and giving
satisfactory hydraulic test for water tightness as per IS codes. For new surface-Two coats
7.1.3 Providing and laying 50 mm thick heavy duty cement concrete flooring in 1:2:4 (1 33 m2 431.94
cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) with ironite
powder including finishing with a floating of neat cement etc. complete laid in one layer in
wet well area below GL, and for platform of pumphouse 50 mm thick
7.1.4 Providing and fixing 40mm dia. GI pipe medium weight quality as openable type with 100 m 1,784.00
angle iron support at 1.5 m c/c using 75 x 75 x 10 mm angles, 1 m long with three rows of
pipes as railing including necessary painting with two coats of approved quality oil paint
over one coat of approved primer including necessary welding, bolting required, id any.
7.1.5 Providing and applying of Wall Painting of Ex. SPS 1000 Sq. ft 71.50
7.1.6 Miscellaneous Civil Work 1 Lot 50,000.00
This scope covers all miscellaneous civil work required for the pump house, including, but
not limited to: cut-out provision, core cutting, finishing, and grouting. It also includes any
unforeseen or emergency civil work during pump dismantling and installation in the
operational pump house. All work must ensure the satisfactory installation and operation
of electro-mechanical equipment and instruments as per the tender scope/BOQ. Any
unlisted work required on site, as directed by the Engineer-In-Charge of the AMC.
8.1.1 All-in-One Computer with 27-inch FHD (1920 x 1080) Display, Intel Core i7 (13th 1 Set 1,00,799
Generation) Processor, 16 GB RAM, 1 TB SSD Storage, Pre-installed Windows
Operating System and Microsoft Office Suite 2024 or above or 365, with a dedicated
Graphics Card of minimum 2 GB.
A TOTAL OF MECHANICAL & INSTRUMENTATION WORK (W/O GST)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
1.1 ELECTRICAL WORKS 1 Set 13,15,680.00
H.T. INDOOR SWITCH GEAR PANEL
SITC of 11 kV, 500 MVA, 630A, Indoor, Extensible type, Horizontal draw out, Motorised spring
charging mechanism, 3 breaker Vacuum Circuit Breaker Panel (1 No. Incomer + 2 Nos.outgoing),
with EC grade copper busbars along with required Resin cast CT Dual primary & secondary, Cl:
0.5/5P10, 15VA, Digital MFM with RS 485 with 3 Line Display, Class-0.5s and PT (dual secondary)
Cl:0.5/3P, min 200VA or higher for metering and protection, 110V DC power pack for incoming &
outgoing feeder, Annunciator, Hooter, Indicating lamps, Numerical Protection relay
(Current & Voltage Based) with RS 485 with combined protection for 3O/C+1E/F, S/C, Under & Over
Voltage, Transformer Protection Aux. relay etc. High speed tripping relay, Trip ckt supervision relay,
Fuse failure relay, Digital Power factor meter for incoming & outgoing feeder, Ammeter, Voltmeter
(Only I/C), A/M switch suitable for PLC/SCADA etc. complete in all respects as per IS, Specification.
1.2 SITC of H.V. CABLES 100 Mtr. 1,210.00
SITC of 11 kV (E), 3C x 240 sq.mm., Aluminium, extruded innersheath, Armoured, XLPE , H.V Cable
as per IS 7098 (part 2) and Tech. Specification. (Torrent HT Panel to AMC HT Panel, AMC HT Panel
1.3 SITC of the Indoor Heat shrinkable Termination: 6 Nos. 4,798.00
SITC of Indoor H.T. cable end terminations Kit for 11 kV (E), 3C x 240 sq.mm. XLPE armoured
cable with all accessories as required.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
2.1 DISTRIBUTION TRANSFORMER 2 Nos. 11,45,181.00
SITC of 630kVA, 11/0.433 kV, Outdoor Transformer continuously rated, 3-phase, 50 Hz, OFF Load
Tap Changer, OCTC, ONAN cooled, copper double wound core type, vector group Dyn11,
Delta(HT)/Star(LT), Oil immersed winding with temperature rise in oil / winding 40/45 deg.C above
design temperature with neutral brought out to connect to separate earthing including Terminal
arrangement bushing / cable Box on HT side and busduct on LT side, first fill of oil along with Fittings
& accessories as per Energy efficiency Level-2 of IS:1180 (Part-1):2021 and its latest ammendments
and as per Tender Specification.
Note: Transformer shall be suitable for parallel operation. Minimum requirement shall be as
Both transformer shall have " Identical X/R ratio, phase angle shift, polarity, phase sequence,
frequency, position of tap changer. Turns ratio & voltage ratio".
2.2 Casting of transformer new plinth / foundation including design as per transformer full total weight load 2 Set 30,000.00
capacity / Transformer vendor recommendation / requirements. Top of transformer foundation shall be
mini. 600mm above finished ground level & two nos. padestal foundation of size minimum 1.2m x
1.2m each or higher as per vendor / statutory / electrical inspector requirements with situ reinforced
cement concrete in M 20 using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work
including providing of 53 grade cement & Fe 415 grade TMT bars, scaffolding, centering, form work,
curing etc. complete in all respect to install new Transformer.
2.3 (a) Supply and levelling of Switchyard & transformer yard using gravel, fine sand and other required filing 75 Sq.m. 340.00
material, enmarked for the Switchyard & Transformer yard including removing of trees or boulders etc.
if any. The general level of the yard shall be at a convenient level for movement of man and material
and it should match with FGL and as per Specification and Drg.
2.3 (b) Supply and Installation of GI Chain link fencing frames with L angle/Channel post around Switchyard 30 RMt. 1,060
& Transformer yard etc. as per Specification and Drg.
2.3 (c) SITC of 3.0 mtr wide gate with GI chain link as per Specification and Drg. 2 Nos. 10,660
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
3.1 LOW VOLTAGE (LT) PANEL BOARD (PMCC) : 1 Set 24,17,000.00
Dismantaling of Existing LT Panel, disconnection of existing all connected cables without any damage,
considering & subject to resposibility of comlpete the reconnection work in all respect with required all
miscellineous rectification / modification work required due to dismentaling of existing working LT
Panel, shall be carred out as directed by Eng. in charge of Client & SITC of PMCC Panel (50kA),
compartmentalized, Floor mounted/Stand mounted or As per site condition operating height maximum
1800 mm(As per site requirement/condition), Extensible on both ends, suitable for Manual & Auto
operation -Local & through PLC/SCADA operation as per site conditions complete in all respects as
per Tender SLD / Specification / IS and including following as minimum:
(1) INCOMER 1&2: FP, 1000A, 50 KA Microprocessor EDO ACB LSIG with inbuilt RS
MODBUS communication with Digital Voltmeter with VSS, Digital PF Meter, Digital Ammeter with
ASS, Resin Cast CT- Cl : 0.5,10VA, MFM with RS-485 Cl. 0.5, Breaker Control Switch (TNC), A/M,
L/R switch, Indicating lamps, Push buttons etc,. with electrical & mechanical interlocking between
Incomers and buscoupler.
(1.1) Surge protection device, 3P + N, Type 2 for lightning/surge protection. Load sensing CT in
Incomer & Busbar for APFC panel, Cl.-0.5. Constant voltage/control voltage transformer 1500VA,
415V/230V AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB & 25A Power contactor.
(2) BUS-COUPLER: One no. FP 1000A ACB (same as per Incomer)
(2.1) 1000A TPN, EC grade AL Main busbars. (Busbars size as per 50KA fault level and Temperature
rise with current density 0.8A/Sq.mm)
(3) TRANSFORMER FIXED COMPENSATION FEEDER (20 kVAR): 2 Set: Each comprising
of 63A FP Thermal Magnetic MCCB, Ind. Lamp, with Capacitor duty contactor, ON Delay timer,
individual MCCB/MCB as per Tender SLD.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
(4) STAR-DELTA STARTER FOR 110 KW MOTOR (SUBM.) : 4 NOS: rate incl in
Each feeder comprising of Star-Delta starter for 110 KW or higher as per pump manufacturer above price
recommendation Star-delta starter with 400A TPN MP MCCB (LSIG) with Adjustable O/L &
Adjustable S/C protection, 300A AC3 duty contactors (3 Nos), O/L Relay, star-delta timer, MFM with
RS-485, Resin Cast CT Cl: 0.5, MPR with RS-485, CBCT, SPP,PMU as per Pump vendor reco., A/M,
L/R switch, ON, OFF, TRIP Indication & Start, E-Stop & Reset pushbutton etc. for S/D starter.
complete in all respects, & LCS (PBS) for Actuator-valve with 16A FP MCB, open,close,stop PB,
open,close,trip & L/R indication & 2 nos. terminal strip, SP MCB etc.
(5) STAR-DELTA STARTER FOR 30 KW MOTOR (SUBM.) : 2 NOS:
30 KW or higher as per pump manufacturer recommendation Star-delta starter with 125A TPN
Thermal magnetic MCCB with Adjustable O/L & Adjustable S/C protection, 95A AC3 duty contactors
(3 Nos), O/L Relay, star-delta timer, MFM with RS-485, Resin Cast CT Cl: 0.5, MPR with RS-485,
CBCT, SPP, PMU as per Pump vendor reco., A/M, L/R switch, ON, OFF, TRIP Indication & Start, E-
Stop & Reset pushbutton etc. for S/D starter. complete in all respects, & LCS (PBS) for Actuator-
valve with 16A FP MCB, open,close,stop PB, open,close,trip & L/R indication & 2 nos. terminal strip,
Note : For Actuator LCS (PBS) shall be provide potential free contact for (open,close,trip & L/R
) indication and terminal for Open,close and stop command because actautor shall be operator
from PLC Panel also in addition to LCS (PBS).
(6) 175 KVAR APFC POWER FEEDER: 2 NOS.
Each feeder comprising of 400A TPN Thermal megnatic MCCB, 50kA with with Digital Ammeter,
ASS, CT, Indicating lamp, etc.complete in all respects.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
(7) 500A TPN MP MCCB POWER FEEDER: 2 NOS. (1no. for Existing STP Panel, 1no. Spare) rate incl in
Each feeder comprising of 500A TPN Micro processor MCCB (LSIG), 50kA with with Digital MFM above price
with Rs-485, CT, Indicating lamp, etc.complete in all respects.
(8) 63A TPN TM MCCB FEEDER : 4 NOS. (1 no. PDB, 1no. for EOT with ECH at Pump house,
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(9) 32A TPN TM MCCB FEEDER : 4 NOS. (2 nos. Dewatering Pump, 1no. for EOT Crane, 1 no.
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(10) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 2 SETS:
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
a) 8 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Ind LDB, 1 no. for ICP/PLC Panel, 6 nos. Spare)
b) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders (for Outdoor
c) 4 nos. 16A DP MCB feeders for 1-phase supply (1 no HT Panel, 2 no. X'mer marshaling box & 1 no.
d) LCS (PBS) with 16A FP MCB, indicating lamp,Push Button, A/M,L/R switch, SP MCB, etc. (2 nos.
for Inlet Gate)
(11) Multiplication relay as required for dry run protection of pumps.
NOTE: 1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L and Adj.S/c
(LSIG for MP MCCB),Extended rotary handle, Terminal spreader, Auxiliary Change over contact and
trip contact as required.2) All MFM, ACB, Soft Starter,MPR,Temp.Scanner etc shall be with inbuilt RS
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
3.2 Dismantaling of Existing LT APFC Panel, disconnection of existing all connected cables without any 2 Set 5,07,783.56
damage, considering & subject to resposibility of comlpete the reconnection work in all respect with
required all miscellineous rectification / modification work required due to dismentaling of existing
working LT APFC Panel, shall be carred out as directed by Eng. in charge of AMC & SITC of
KVAR at 415V, APFC Panel,compartmentalised, Stand mounted, extensible type on both sides with
Horizontal bus bar arrangement as per site requirement & complete in all respects as per SLD /
Specification / IS and including following as minimum:
1.1 400A, TPN, 50 KA TM MCCB with Digital Voltmeter with VSS, Digital Ammeter with ASS,
Resin Cast CT- Cl : 1.0, 10VA, Breaker Control Switch (TNC), A/M, L/R switch, Indicating lamps,
Push buttons etc. (1.2) Microprocessor based APFC Relay,144sq.mm, 12 STEP with RS 485 with
minimum operating current 10mA.
2. OUTGOING CAPACITOR FEEDER:
Capacitor feeder of following rating comprising of TPN MCCB/MCB with ON & TRIP Indication,
Capacitor duty contactor,Heavy duty MPP / gas filled capacitor unit, A/M Switch, ON Delay timer,ON
/ OFF Push button, ON, TRIP, Auto & Manual Indication lamp etc. as per Tender SLD&
(2.1) 50 KVAR FEEDER: 3 NOS (2.2) 10 KVAR FEEDER: 1 NO
(2.3) 5 KVAR FEEDER: 2 NOS (2.4) 2 KVAR FEEDER: 2 NOS
(2.5) 1 KVAR FEEDER: 1 NO
2.6.Two nos. Vacant feeder suitable for 1-50KVAr and 1-10KVAr to be provided.
NOTE: 1. cooling/exhaust fan : Heavy duty 8" Metalic Housing and Metal Impeller / Blade /
Vanes of Minimum2nos. or higher as required at the top of the panel with canopy/hood.
2. For Capacitors of rating ≤ 5 KVAr only, All types viz. APP/MPP/Gas Filled are acceptable.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
3.3 Supply & commissioning of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with 6 Nos. 5,080.00
detachable cable gland plate of 3mm thick, duly powder coated, with earthing terminals, steel structure
stand for mounting of JB, etc. for Jointing/Termination suitable for 1.1 kV Submersible Flexible
Copper Power & control cable with Aluminium/ Copper armoured power cable from PMCC .
Scope shall include providing suitable rating AL busbars, Support insulators, Crimping type
lugs,nuts,bolts,washers etc. complete in all respects as instructed by E.I.C. Drawing shall be got
approved before SITC of the same. Lugs of cables shall not be connected directly. (Structure steel for
Stand shall be measured separately)
JB of minimum Size: 900mm x 900mm x 100mm or higher as required.(for Subm. Pump)
3.4 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,568.94
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting & Outdoor Lighting
Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
3.5 SITC of Aux-Power Distribution Board (PDB) as under: 1 No. 14,353.11
3 Phase 4 Wire TPN, 8way Pre-wired-MOG / MOV PDB for Auxiliary accessories Load power
supply (4nos. EOT with ECH at Manual screen, Aux. supply & Rest spare)
Incoming: 63A TPN, MCCB
Outgoing: 8 nos. 32A 4P MCB 'C' Curve
3.6 SITC of LCS pushbutton station ON & OFF (E-stop) set complete with Enclosure, necessary 6 Nos. 2178.82
mounting/ fixing arrangement on wall / pipe support etc. to be installed near motors for remote
operation, etc. as per IS and specifications. (including structural steel) (For Pump)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
4.1(a) LOW VOLTAGE (LT) CABLES 400 Mtr. 1,367.54
Supply, laying , testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE insulated (IS
7098) AL / Cu stranded conductor, Extruded inner sheath cables as per specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick & sand
protection/in DWC pipes as per specified method and shall be laid in prepared trench/ on cable tray
when laid inside the building.
Supply of 3.5C x 300 sq. mm. A2XFY(X) Cable (4 Runs for Transformer-1 & 2 to PMCC Panel
Incomer-1 & 2, 2 run for PMCC panel to shankarbhuvan STP panel)
4.1 Laying, testing and commissioning of above cable 400 Mtr. 33.33
4.2(a) Supply of 3C x 95 sq. mm. A2XFY(X) Cable (2R for each PMCC Panel to 4nos. Proposed 110 kW 200 Mtr. 287.00
Pump motor set)
4.2(b) Laying, testing and commissioning of above cable 200 Mtr. 13.00
4.3(a) Supply of 3.5C x 120 sq. mm. A2XFY(X) Cable (2 runs for PMCC Panel to 2 no. APFC Panel) 100 Mtr. 512.07
4.3(b) Laying, testing and commissioning of above cable 100 Mtr. 22.22
4.4(a) Supply of 3C x 10 sq. mm. A2XFY(X) Cable (2R for each PMCC Panel to 2nos. Proposed 30 kW 100 Mtr. 117.16
Pump motor set)
4.4(b) Laying, testing and commissioning of above cable 100 Mtr. 12.12
4.5(a) Supply of 4C x 6 sq. mm. A2XFY (X) Cable (For 1 no. Indoor LDB, 1 no. Outdoor LDB, 1 no. EOT 300 Mtr. 112.11
at Pump House, 4 nos. for screen hoist, 2 nos. for Dewatering pump)
4.5(b) Laying, testing and commissioning of above cable 300 Mtr. 12.12
4.6(a) Supply of 4C x 2.5 sq. mm. 2XWY(X) Cable (6 nos. MOV at pump Delivery, 1 no.for ICP, 2nos. For 480 Mtr. 259.57
Inlet gate actuator)
4.6(b) Laying, testing and commissioning of above cable 480 Mtr. 10.10
4.7(a) Supply of 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (For 2 nos. Tr. Marshalling Box, 2 nos. 130 Mtr. 166.65
4.7(b) Laying, testing and commissioning of above cable 130 Mtr. 10.10
4.8(a) Supply of 5C x 2.5 sq.mm. 2XWY(X) Cable (For 6nos. Pump-Motor LCS) 180 Mtr. 210.00
4.8(b) Laying, testing and commissioning of above cable 180 Mtr. 10.50
4.9(a) Supply of 10C x 2.5 sq.mm. 2XWY(X)Cable (2 Run Tr. to HT Panel control cable) 120 Mtr. 480.00
4.9(b) Laying, testing and commissioning of above cable 120 Mtr. 24.00
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
4.10(a) Supply of 12C x 1.5 sq.mm. 2XWY(X) Cable (6 nos. MOV at pump Delivery, 2nos. For inlet gate) 420 Mtr. 350.00
4.10(b) Laying, testing and commissioning of above cable 420 Mtr. 17.50
5.1 CABLE END TERMINATION AND CONNECTION: 20 Nos. 976.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic lugs / sockets
with necessary tools and equipment's as specified in specifications and IS. The glands and lugs /
sockets shall be suitable for cable size and type mentioned below & as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common
2) The job also includes, if necessary, supply & fixing of extension busbar of same material on MCCB
or panel board terminal / connector to connect more than one no. of parallel cables or to connect
higher size cable to lower size unit. The job also includes earthing the glands and armour of the cable
with common earth bar or flexible copper mesh.(Cable termination qty. shall be as per site requirement)
SITC of 3.5C x 300 sq. mm. Cu. 2XFY Cable (4 Runs for Transformer-1 & 2 to PMCC Panel
Incomer-1 & 2, 2 run for PMCC panel to shankarbhuvan STP panel)
5.2 Same as above But, 3C x 95 sq. mm. A2XFY(X) Cable (2R for each PMCC Panel to 4nos. Proposed 16 Nos. 419.00
110 kW Pump motor set)
5.3 Same as above But, 3.5C x 120 sq. mm. A2XFY Cable (2 runs for PMCC Panel to 2 no. APFC Panel) 8 Nos. 431.00
5.4 Same as above But, 3C x 10 sq. mm. A2XFY(X) Cable (2R for each PMCC Panel to 2nos. Proposed 8 Nos. 126.00
30 kW Pump motor set)
5.5 Same as above But, 4C x 6 sq. mm. A2XFY (X) Cable (For 1 no. Indoor LDB, 1 no. Outdoor LDB, 1 18 Nos. 111.00
no. EOT at Pump House, 4 nos. for screen hoist, 2 nos. for Dewatering pump)
5.6 Same as above But, 4C x 2.5 sq. mm. 2XWY(X) Cable (6 nos. MOV at pump Delivery, 1 no.for ICP, 18 Nos. 110.00
2nos. For Inlet gate actuator)
5.7 Same as above But, 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (For 2 nos. Tr. Marshalling Box, 8 Nos. 65.65
2 nos. APFC CT)
5.8 Same as above But, 5C x 2.5 sq.mm. 2XWY(X) Cable (For 6nos. Pump-Motor LCS) 12 Nos. 180.00
5.9 Same as above But, 10C x 2.5 sq.mm. 2XWY(X)Cable (2 Run Tr. to HT Panel control cable) 8 Nos. 240.00
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
5.10 Same as above But, 12C x 1.5 sq.mm. 2XWY(X) Cable (6 nos. MOV at pump Delivery, 2nos. For inlet 16 Nos. 250.00
6.1 CABLE TRAY 100 Mtr. 694.88
SITC of G.I. (hot dip galvanised ) Ladder type medium duty (2mm thick) Cable Tray with necessary
bends, tees, reducers, covers and clamps for fixing. All material shall be Hot dip galvanised. All
hardware shall be Electro-galvanized/ SS 304 complete in all respects as per Specification. And
including all accessories.
600 x 100 mm - Ladder type
6.2 300 x 100 mm - Ladder type 150 Mtr. 556.51
6.3 150 x 50 mm - Ladder type 350 Mtr. 276.00
6.4 Supply, laying and erection of 125 mm (ID) approved make Double Walled Corrugated pipes 100 Mtr. 325.00
(DWC) of polyethelene (confirming to IS-14930 II) with necessary connecting accessoies of same
material at required depth for laying of cable below ground / road surface for enclosing cable and back
filling the same to make ground as per original. (For HT cable from psc DP to Client DP, from Client
DP to HT Panel, HT panel to transformer etc. ).
6.5 Supply, laying and erection of 75 mm ID approved make Double Walled Corrugated pipes (DWC) 150 Mtr. 144.00
of polyethelene (confirming to IS-14930 II) with necessary connecting accessoies of same material at
required depth for laying of cable below ground / road surface for enclosing cable and back filling the
same to make ground as per original. (LT cable etc)
6.6 Making Trench/ excavation in soft soil of suitable width and of depth (minimum 750mm depth (LT) 50 Mtr. 46.00
& 1000mm for HT) for laying cable/ DWC pipe and back filling the same and making the surface as
normal ground as per IS & Ternder Specification/Drg. (For laying of HT/LT cable)
6.7 Cable Protection/ Covering in Trench: Cable Covering with second class bricks or cement tiles laid 50 Mtr. 134.33
cover the cable (top) & also on both side with sand bedding/cusioning of 75mm.& covering of 150mm
Layer of sand above cable (16 bricks per meter.) as per IS & Tender Drg/ Specification. (For HT/LT
cable protection) complete in all respects as instructed by EIC.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
7.1 CHEMICAL EARTHING SYSTEM 8 Set 10,593.89
SITC of Maintenance free chemical earthing (copper) with earthpit of minimum bore size dia. 225mm
Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of
corrosion free Pipes having Outer pipe dia of 48 mm having 250 Micron copper plating, Inner
corrosion free Hot dip galvanised (80 to 100 micron) pipe dia of 26 mm with copper flat strip type
connection terminal 14mm dia with constant ohmic value surrounded by highly conductive corrosion
resistant chemical compound with high charge dissipation suitable for electrical installation & of 3Mtr.
length of Pipe with two nos. 25Kg. bag of Back filling compound.. (2nos. for HT Panel, 2 nos. Each for
neutral of Tr.-1 & 2, 2 nos. for ICP earthing,)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
7.2 SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 225mm Safe 12 Set 7,095.25
Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of
corrosion free Hot dip Galvanised (min 150 Microns) Pipes having Outer pipe dia of 76 mm , Inner
corrosion free Hot dip galvanised (80 to 100 micron) pipe dia of 26 mm with copper flat strip type
connection terminal 14mm dia with constant ohmic value surrounded by highly conductive corrosion
resistant chemical compound with high charge dissipation suitable for electrical installation & 3Mtr.
length of Pipe with two nos. 25Kg. bag of Back filling compound. (2 nos. Each for Tr.1 & Tr.2 Body,
2nos. for LT Panel, 2nos. for pumpset, 4nos. for all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
7.3(a) SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip including supply & 1404 Kg. 77.77
fixing using GI spacers, saddles when laid inside the building and inclusive of excavation & refilling of
earth when laid outside the building & interconnection with earth pit & all electro-mechanical
(50X8 G.I Strip wt.3.12 kg/m, 3.12x450Mt.=1404kg.)
7.3(b) Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip galvanized GI 150 Kg. 77.77
Strip including supply & fixing using GI spacers, saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the building & interconnection with earth pit & all
electro-mechanical equipments. (25X3 G.I Strip, 0.6 Kg/m, 0.6x250Mt.=150Kg.)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
7.3(c) Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes Copper Strip including supply & fixing 38 Kg. 794.87
of bolts, saddles when laid inside the building and inclusive of excavation & refilling of earth when laid
outside the building & interconnection with earth pit & PLC Panel (25X3 Cu. Strip, 0.761 Kg/m,
x 50 mtr.=38.05Kg.)
Copper Bolt,Nuts ,Washers shall be used for Connecting Earth electrode to individual eqp. Bitumen
shall be used at the place of joint/welding. (For PLC Panel to Earthing)
7.3(d) Supply, laying and erection of 40mm(w) x 6mm(T) etc. sizes Copper Strip including supply & fixing 113 Kg. 794.87
of bolts, saddles when laid inside the building and inclusive of excavation & refilling of earth when laid
outside the building & interconnection with earth pit & Tr. nutral. (40X6 Cu. Strip, 1.88 Kg/m, 1.88 x
60mtr.=112.8Kg.)
Copper Bolt,Nuts ,Washers shall be used for Connecting Earth electrode to individual eqp. Bitumen
shall be used at the place of joint/welding.
7.3(e) SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB, LCS, etc.) 31 Kg. 77.77
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 300Mt.=30.9)
8.1 INTERNAL WIRING 100 Mtr. 78.78
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked flexible
stranded copper conductor wires with medium class min. 25mm. dia. Rigid PVC pipe and accessories
to be erected concealed in / to be run on surface / wall / ceiling with following sizes as mentioned
below. The unit rate wirings shall be with connector, PVC junction box, wires, holder, ceiling rose,
angle holder, switch, sockets, switch board, brass chromium / cadmium plated machine screws, phase
and neutral wires, green Earth continuity wires etc. as required to complete wiring from LDB panel to
the final outlet termination points. The wiring shall be as per IS:732, IS:4648 and as per tender
specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
8.2 As per Sr. No.-9.1 (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender specification & IS. 150 Mtr. 96.96
8.3 As per Sr. No.-9.1 (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender specification & IS. 200 Mtr. 86.86
8.4 As per Sr. No.-9.1 (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender specification & IS. 250 Mtr. 120.19
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
8.5 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & earth wire of 1.5 58 Nos. 329.26
sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multistrand copper wires
pipe to be erected concealed in flushed on wall / ceiling, complete with 6A Tissino Type ISI marked
flush type switch / bell push & accessories erected on metal / PVC Box covered with 3 mm thick PC
(Polycarbonate) / Acrylic sheet with necessary lamp holder / ceiling Rose / H. D. connector as directed
with medium class Rigid PVC pipe & accessories.
8.6 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm 5 Nos. 290.88
(green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with
medium class Rigid PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked
3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal /
PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet.
8.7 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm 5 Nos. 570.65
(green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with
medium class Rigid PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked
3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal /
PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet.
8.8 SITC of Single Phase 20A 3 Pin Matal clad Industrial Type Socket with plug top and 20A 5 Nos. 820.00
SPMCB, suitable for flush mounting, in 16 SWG MS box of suitable size and covered with 3 mm thick
electrical grade hylam sheet or eqivalent ISI marked Electrical grade bakelite sheet and earthing with
2.5 sq.mm insulated copper wire run inside the conduit including interconnections etc. complete as
8.9 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 2nos. 4 sq.mm 5 Nos. 570.65
Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS
PVC insulated multistrand copper wires with medium class Rigid PVC pipe and accessories to be
erected on wall / ceiling, complete with ISI marked 3Pin socket and tissino type switch erected with
earth continuity connection erected on Metal / PVC box covered with 3 mm thick PC(Polycarbonet) /
Acrylic sheet. Plug point shall be near Ex.Fan.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
8.10 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball bearing, 5 Nos. 3,082.52
M.S.blades, mounting frame, forearms, suitable to operate on 230V,50 HZ AC supply conforming to
IS: 2312.Fan shall be painted with epoxy grey colour controlled by one 6 A flush type switch on board
and 6A plug point near Ex. fan.
8.11 LED LIGHT FIXTURES & LIGHTING: 20 Nos. 589.84
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube Light indoor
fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as
a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA polyester powder coated
and high U.V. & corrosion resistance with diffuser and/or Polycarbonate optics with company
120 to 300 V,Power Factor more than 0.9, THD < 10 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
8.12 Item description as per Sr. No. 8.1.1 SITC of 7 watts LED Lamps integral type,cool white with PC 5 Nos. 220.18
diffuser suitable for B22 LAMP holder.
8.13 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, canopies, 3 Set 1,596.81
shackle, rubber bush, blades, electronic speed regulator, suitable to operate on 230V,50Hz AC supply
conforming to IS: 374/1979.Fan shall be painted with white colour.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
8.14 SITC of 70W LED Surface / Wall mounted LED Flood Light fittings with High power White LEDs 20 Nos. 6,088.28
wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and
corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat
sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name
engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: ( Pump House)
8.15 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 cms x 20 cms 30 Nos. 558.53
x 3 mm thick M.S. base plate, erected on wall or corner for mounting luminaire with necessary
hardware materials duly painted for wall mounting indoor flood light fixtures on Wall of Buildings &
post top lantern.
9.1 EXTERNAL LIGHTING (Flood LIGHT): 10 Nos. 7,266.95
SITC of 100W LED Wall mounted LED Flood Light fittings with High power White LEDs wattage
of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free
High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (area lighting)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR EXISTING E-3 SPS
AT SHAHPUR RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
10.1 SAFETY ACCESSORIES 1 No. 8,671.86
SITC of following safety accessories complete with necessary fixing brackets, other accessories and
tools etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with necessary clamps
made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.
(For 1 no. for LT Room cum Pump House)
10.2 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds due burn, crepe 1 No. 299.97
bandage, gauge bandage, medicated ready to use bandage (Band-aid) adhesive tape for medicinal user,
scissors, antiseptic solution (Savlon or similar) etc. (1 no. for LT Room cum Pump House)
10.3 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and duly framed 1 No. 130.29
with front glasses, for treatment of person suffering from electric shock. (1 no. for LT Room cum Pump
10.4 Supplying & fixing of floor mounting stand for keeping four nos. of FIRE buckets comprising 1500 3 Nos. 1,798.81
mm in length, 900 mm height frame made out of 30mm X30 mm X 4 mm angle iron with cross
supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of
approved enamelled silver paint. (HT Panel, Tr. 1&2)
10.5 Supply and fixing of 20 W fluorescent lamp operated emergency light with maintenance free battery 1 No. 2,540.00
for 3 hours operation during mains power failure.
(1 no. for LT Room cum Pump House)
10.6 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as per IS:15652 20 Sq.mt 1,027.17
and with good electrical insulation property for 1.1KV/3.3KV as per site requirement. (For LT Panel) r.
10.7 Providing pair of rubber hand gloves ISI make suitable for working on 22 KV supply 2 Nos. 214.12
B TOTAL OF ELECTRICAL WORKS WITHOUT GST
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL WORKS WITH 3 YEARS O&M
FOR EXISTING E-3 SPS AT SHAHPUR RIVERFRONT OF AMC.
(C) OPERATION & MAINTENANCE
The works of this schedule comprises of the supply of all spare parts as required including the supply of all labour (including reliever to ensure presence of specified
type and no. of manpower per shift), materials, consumables (except electrical power), equipments, tools and tackles and comprehensive operations and
maintenance of E-3 SPS at SHAHPUR of AMC during the 3 Year of O & M from the date of successful commissioning as shown in table below.
Item No. Rate per Amount
Item of Work Duration Unit
1.0 Staff Salary
1.1 During First year 12 Months 1,13,226
The work of this schedule comprises of deployment of all operating crew/labour
(including reliever to ensure presence of specified type and no. of manpower per shift) at
Ex. SPS of AMC during 3 Years of O & M from the date of successful commissioning as
shown in table below.
Total staff salary for First years for Operation and security, repairing and maintenance for
the complete year period.
a) Pump operator - (ITI-Wireman/Eletrician) (3 nos - One for each shift of 8 hrs.)
b) Security cum Helper - (10th pass-of age < 45 years) (3 nos. - One for each shift of
1.2 Total of Manpower for Second Year 12 Months 1,18,888
1.3 Total of Manpower for Third Year 12 Months 1,24,833
2.0 Comprehensive Maintenance
2.1 Comprehensive repairing, supply of spares and maintenance of entire works in existing 12 Month -
SPS alongwith administration & management charges including running office, cost of
lubricants, consumables, spares, tools & tackles, statutory periodical approvals & testing
of eqipment etc. required in all except supply of electric power and sewage during O&M
period for First Year of O&M period.
(Covered under Defect Liablity Period for First Year)
Item No. Rate per Amount
Item of Work Duration Unit
2.2 Total of Comprehensive Maintenance, repairing, Spares, Consumables etc. for entire 12 Month 20,023
works in existing SPS including Proposed as well as all existing Electro-Mech.
equipment’s, for second year of O&M period.
2.3 Total of Comprehensive Maintenance, repairing, Spares, Consumables etc. for entire 12 Month 21,025
works in existing SPS including Proposed as well as all existing Electro-Mech.
equipment’s for Third year of O&M period
3.0 Operation, Comprehensive repairing and maintenance for 10 months (during 10 Months 1,48,170.50
Upgradation Phase) of existing SPS during installation, testing commissioning of
Proposed Electro-mech. & Inst. equipment’s etc.
C TOTAL OF O&M FOR 3 YEARS WITHOUT GST
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Volume-I_Technical Bid.pdf
Volume-II_Financial Bid.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .