Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 65 905 SEBASTIAN ROAD KALOOR KALOOR ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹12,086
Closing Date
5 Apr 2023, 3:00 pmClosed
AGM MM
O/o GMT BSNL Malappuram
Tender for Preventive maintenance of 6 Nos 100 KVA and 1 No 160KVA outdoor type substation under SSA Malappuram.
2023_BSNL_148513_1
KL MLP-17/19/3/2022-PLG MLP KRL/1 dtd 28.02.2023
Open Tender
Electrical Works
Works
61 days
All over Malappuram Bsnl area
as per tender document
3 documents required · 3 mandatory
₹590
Yes
AO (CASH), BSNL, MALAPPURAM
₹12,086
Yes
5 Jul 2023
15 Mar 2023
10 Apr 2023
15 Mar 2023
5 Apr 2023
15 Mar 2023
15 Mar 2023 - 22 Mar 2023
Amount
Carrying filtration of transformer oil of 11KV/433V 100 KVA outdoor transformer and CTPT unit, including heating, filtering, and bringing the breakdown strength of transformer oil to the required value as per standards, etc as required [TE Ponnani, Parappanangadi, Kuttippuram, Kottakkal, Kondotty and Edappal - 100 KVA] [TE Nilambur - 160 KVA]
Supplying and filling of transformer oil confirming to IS 335 suitable for 11KV/433 V step down transformer for topping up the oil level etc as required
Supply and fixing breather unit with fresh silica gel, suitably filled oil with appropriate level etc as reqd
Revamping of existing earth pit masonry enclosure and cover plate by making good with necessary brick work after removing the deposited soil, cement plastering all around the enclosure, including replacing the rusted watering funnel, painting the cover plate and masonry work, sign writing etc as reqd.
Painting of 4 pole HT yard structure members with single coat industrial primer and 2 coats of aluminium paint after thorough rubbing of existing paint and rust including Tightening of all jumper/lightning arrester/DO fuse/insulator connections, replacing corroded nut bolts, damaged contacts, giving standard colour code to all the component and connecting leads with enamel paint of approved colour, liaison work for getting shutting down of HT line from KSEB and restoration of supply arrangement etc. as reqd.
Painting of existing high yard fencing [approximately 15 m long x 1.80m] with a primer coat of zynchromate primer and 2 top coats of Aluminium paint after scratching off the rusted area ,white washing the fencing plinth with 2 coats of white cement including cleaning the yard removing bushes etc, making the door locking arrangement proper after replacing the damaged parts, applying grease on hinges as reqd.
Painting of existing 100KVA transformer, measuring CT - PT unit and metering kiosk with a coat of zynchromate primer and 2 coats of branded enamel Paint after scratching and rubbing of existing paint etc. as reqd [TE Ponnani, Parappanangadi, Kuttippuram, Kottakkal, Kondotty and Edappal]
Painting of existing 160KVA transformer, measuring CT - PT unit and metering kiosk with a coat of zynchromate primer and 2 coats of branded enamel Paint after scratching and rubbing of existing paint etc. as reqd [TE Nilambur]
Servicing of 11KV AB switch including testing all contacts applying soft grease/petroleum jelly, supplying fixing handle rod, etc as required
S/F following items in the HT structure to make the system in healthy condition i/c removing the faulty items, giving connections, testing, commissioning etc as reqd
11 KV Pin insulator
11 KV Disc insulator
11 KV Lightning arrestor
Removing the herbs, shrubs and bushes from the transformer yard of approximate area 25 sqm including levelling, stone aggregate etc as required
Servicing of existing 50 KVAR APFC panel having 4 capacitor banks i/c tightening connections at termination of cables/ bus bars, capacitor, contactors and all controls /metering wires including replacing the following items if any found faulty etc as reqd.
32 A Capacitor duty Contactor [L&T or similar superior make]
16 A Capacitor duty Contactor [L&T or similar superior make]
3 KVAR 3 phase MDXL Type Capacitor [L&T or similar superior make]
2 KVAR 3 phase MDXL Type Capacitor [L&T or similar superior make]
Checking the complete MV/LT panel for loose connections at termination of cables/ bus bars, all controls /metering wires , checking/servicing and of all out going switches, tightening of bolts /nuts, screws, cleaning, supply and fixing LED indicator lights for replacing the faulty indicator for phases etc as reqd
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .