Upgradation of Building Management Systems installed at Prof.MGKM Lab CREST campus of IIA, Hosakote.
Integrator & IP 54 rated wall / Floor mount enclosure Intergator for Integration of VFD's - 9 No's Soft Points - 10 Points / VFD, Total - 90 Points Protocol - BACnet / MSTP or Modbus, Make: ALC, Model No.LGR-250X1
DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock; Should confirm to BACnet Building Controller (B-BC) Standard Device. Controller must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP Controller for AHU's - 5 no's, Make: ALC, Model No.BAC net SE Series
DDC panel - 1, IP 54 rated wall / Floor mount type enclosure panel, Make and Model: Standard
DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock; Should confirm to BACnet Building Controller (B-BC) Standard Device. Controller must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP Controller for FFU's, Make: ALC, Model: BAC net SE Series
DDC panel - 2, IP 54 rated wall / floor mount type enclosure panel, Make and Model: Standard
DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock; Should confirm to BACnet Building Controller (B-BC) Standard Device. Controller must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP, Controller for AHU's - 2no's, Make: ALC, Model: BAC net SE Series
DDC Panel-3, IP 54 rated Wall / Floor type enclosure panel, Make and Model Standard
DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock; Should confirm to BACnet Building Controller (B-BC) Standard Device. Controller must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP, Controller for Chiller Pumps, Make: ALC, Model: BAC net SE Series
DDC panel-4, IP 54 rated Wall / Floor type enclosure panel, Make and Model: Standard
Wiring: Supplying, laying, termination, testing and commissioning of communication cables, 2C X 1.5 Screened Cable, Make and Model: Standard,
Wiring: Supplying, laying, termination, testing and commissioning of communication cables, 25 mm PVC Conduit, Make and Model: Standard,
Wiring: Supplying, laying, termination, testing and commissioning of communication cables, CAT 6 Cable, Make and Model: Standard,
Field Sensors Cable Type- Temperature sensor ( For AHU CHW Supply and Return ) Quote for sensor with 100mm probe length of Thermowell and Temperature sensor Make :Greystone
Cable Type- Temperature sensor ( For Chiller CHW Supply and Return ) Quote for sensor with 100mm probe length of Thermowell and Temperature sensor Make :Greystone
Cable Type- Temperature sensor ( For Chiller Supply and Return header ) Quote for sensor with 100mm probe length of Thermowell and Temperature sensor Make :Greystone
Temperature and Relative Humidity sensor - Duct Type ( For AHU) Make :Greystone
Temperature sensor - Duct Type ( For AHU supply and Return ) Sensor probe length - 1 50 mm Make :Greystone
Duct Static pressure sensor (0 to 1000) pascal Ranges ±1250 / 0-1250 Pa Make :Greystone
Temperature and Relative Humidity sensor with Display - Room Type ( For AHU) Make :Greystone
Pressure sensor with Display - Room Type (0 to 50)pa Make :Greystone
Ambient Temperature and Humidity sensor Make :Greystone
Air Differential pressure switch for AHU run status ( 0 to 5) pa Make :Greystone
BMS Software & Display Device BMS Software for 500 points only, Make: ALC and Model: WC-A + WC Media
SMS Modem, Make and Model: Delmon
Display unit with a 10.9 inch Liquid Retina display, compatible with Wi-fi and with 256 GB of storage ,A14 Bionic chip,Touch ID integrated into the top button, Compatible with both Magic Keyboard and Smart Keyboard, Wi Fi 6 & 4G LTE, 802.11ax Wi-Fi 6; simultaneous dual band (2.4GHz and 5GHz); HT80 with MIMO Bluetooth 5.0 technology, Built‐in 28.6‐watt‐hour rechargeable lithium polymer battery. Make: Reputed
Dismantling Work: Dismantiling of existing controllers and panels
Project Managment, Screen development, graphics development, testing and commissioning charges
Installation Cost Any additional item required for installation may be included in the installation cost.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .