| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.2 LAccepted-AOC | L1 | Accepted-AOC ACEEPTED BEING LOWEST TENDER | |
| 2 | L2₹12.7 L+₹5,915 (0.47%)Rejected-AOC | L2 | Rejected-AOC REJECTED BEING NOT LOWEST TENDER | |
| 3 | L3₹15.1 L+₹2.5 L (20.0%)Rejected-AOC FLAT NO C 401 LORD KRISHNA GREEN OPPOSITE DOON SCHOLAR SCHOOL KEDARPUR DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L3 | Rejected-AOC REJECTED BEING NOT LOWEST TENDER |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
26 Jul 2021, 6:00 pmClosed
GE I RND DEHRADUN
GE I RND DEHRADUN DEAL RESIDENTIAL COMPLEX RAIPUR ROAD DEHRADUN 248008
CERTAIN REPAIRS/REPLACEMENT OF ELECTRICAL PANNELS, HT AND LT CABLE AND ALLIED WORKS AT DEAL AND IRDE UNDER GE (I) R N D DEHRADUN
2021_MES_431357_2
GE(I)RND/9039/E8/20-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DEHRADUN
Class E Category a (i) FOR UNENLISTED CONTRACTOR (i) Enlistment criteria may be seen in Para 1.4 of section of Part I of MES Manual on contracts-2007 (Reprint 2012) as available in all MES formations (ii) Copy of police verification /passport.
6 documents required · 6 mandatory
₹500
GE I R N D DEHRADUN
₹40,000
Yes
6 Aug 2021
5 Jul 2021
28 Jul 2021
5 Jul 2021
26 Jul 2021
12 Jul 2021
5 Jul 2021 - 12 Jul 2021
Amount
Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection covers/ bricks & stacking serviceable bricks for reuse and disposal of unserviceable covers within 50 m all as directed. Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and brick protection. (ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations
M&L for Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed and tested complete all as specified and directed by Engineer-in-Charge.
M&L for Removal of surplus excavated soils not exceeding 50 Mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified.
Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches/ducts for cable protection complete all as specified and directed by Engineer-in-Charge.
M&L for old size sub class `B` bricks, kiln burnt, as in cable protection laid flat with axis of brick perpendicular to the axis of the cable complete all as specified and directed by Engineer-in-Charge.
Fixing / laying only old bricks of any description as obtained from dismantling of the cable complete all as specified and directed by the Engineer-in-Charge.
Disconnecting and taking out old existing unserviceable/ corroded GI tubing of any description and in any position complete all as specified and directed by the Engineer-in-Charge.
Supplying, laying & jointing GI water tubing, 80 mm bore, medium grade as in sleeving etc laid in trenches / ducts etc. complete all as specified and directed by Engineer-in-Charge.(MAKE : TATA/JINDAL/TT SWASTIK)
Supplying, laying & jointing GI water tubing, 50 mm bore, medium grade as in sleeving etc laid in trenches / ducts etc. complete all as specified and directed by Engineer-in-Charge.(MAKE : TATA/JINDAL/TT SWASTIK)
Dismantling & taking out unserviceable steel & iron items from poles and Supply & fixing cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts & bolts , washers , welding bending cold or hot , drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge.
Disconnecting and taking out old existing unserviceable/ non- functional LT Cable and Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminum conductor for working voltage upto and including 1100 Volts, cross sectional area of under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe complete all as specified and directed by Engineer-in-Charge. Make:Havells/CCI/ICL/GLOSTER/Incab/Nicco/Polycab/Plaza) (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and brick protection shall be measured and paid separately )
50 Sqmm 3½ core
70 Sqmm 3½ core
95 Sqmm 3½ core
120 Sqmm 3½ core
150 Sqmm 3½ core
185 Sqmm 3½ core
240 Sqmm 3½ core
300 Sqmm 3½ core
Re-laying LT cable Obtained form Item No 1( Any size)
M & L for cutting chases in hard standing road/path/drain etc for passing cables/pipes etc. size of cutting 100mm wide and 200mm deep and removing the excavated materials and disposal at 50 metre distance and making good the cutting after the pipe and cables are laid with PCC 1:3:6 type C-1 using 20mm graded stone aggregates complete all as specified and directed.
Dismantling & taking out of old existing unserviceable insulators of any description and in any position from LT poles all as specified & directed.
Supply & fixing pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 100mm height and 65mm dia suitable for working pressure upto and including 1100 volts grade complete all as specified for LT lines fixed on poles.
Supply and fixing shackle type porcelain vitreous, white, brown or green insulator for working pressure 1100V of 115mm dia and 100mm high including galvanized mild steel strip 31 x 3mm, insulator bolts 14mm dia washer and nut complete all as specified for LT lines fixed on poles.
Supply , Install and testing in replacement of unserviceable insulators pin type porcelain, vitreous, white, brown or green insulators,for working pressure 11000 volts of size 150mm height and 150 mm dia including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, etc for HT lines fixed on poles complete all as specified and directed.
Supply , Install and testing in replacement of unserviceable disc type porcelain, vitreous, white, brown or green insulators,for working pressure 11000 volts of size 145mm height and 255 mm dia including two in series assembly for tension with tension clamps for conductors, etc for HT lines fixed on poles complete all as specified and directed.
Restringing of HT/LT/street light over head lines of existing over head line of ACSR conductor /GI wire after disconnecting from the insulators & jumpers to the required tension & sag & binding up & connecting to insulators & jumpers properly testing complete, including chopping off tree branches (coming in the way line) all as directed by Engr-in-Charge.
Supply and fixing UNSV LT PVC separator 4 wire complete all as specified and directed.
Supply and fixing UNSV LT PVC separator 2 wire complete all as specified and directed.
Supplying,Straightening and Stringing in replacement of UNSV aluminum conductor steel reinforced (ACSR) conductor off size including jointing the conductor with new conductor on existing HT/LT pole and binding to insulator with the new aluminium wire binding wire 2 mm dia making and connecting jumper connections etc including connecting commissioning and testing complete, all as specified and as directed by Engr-in-Charge.
Supplying, Straightening and Stringing in replacement of UNSV Guard/ cradles hexagonal/ rectangular, fabricated in replacement of UNSV galvanized steel wire 3.15 or 4mm dia on LT/HT Pole lines connections etc complete, all as specified and as directed by Engr-in-Charge.
Material and labour for cleaning and preparation of all existing steel surfaces of pole structure of straight steel tubular poles 9/11 mtrs long for painting including mild steel cross arms, clamps and anti clibing device,protection pipe etc and applying one coat of aluminium paint all round the exposed steel surfaces of existing steel tubular poles structure of any description and in any position above the height of 1.50 mtr from the plinth of the pole and applying one coat of synthetic enameled paint of different colours in strips of 150mm width upto the height 1.5 mtr from the plinth of poles including writing pole No and other sign works with white paint over black painted base in the pattern and style as approved by the Engineer-in-Charge complete all as specified & directed.Note : Size of black painted base for numbering shall be 100mmx25mm and the size of numbers shall be not exceeding 10cm height.
Taking down old unserviceable MS junction boxes from the pole with disconnectiong all connections, Supplying and fixing in position new Pole box made of thermoplastic Polycarbonate having IP66/IP67 degree of protection (shock proof, dust proof, jet water proof and acid resistive). The gasket should be internally embedded, and made of Polyeutherene. The boxes shall be tested as per IEC 60670-2/ 60670-22. The boxes shall have self threaded holes & provision for mounting din rail. The lid should be hinged type with sealing screw. The screw should be of stainless steel so that there is no corrosion. The boxes should withstand temperature of -40c to +120c. The glow wire test should be conducted at 960 c or 750 c and material should be flame retardant & self extinguishing. UL subject 94, V-0. The boxes should be free from toxic substances like hal ogen and silicon. The boxes should have suitable pre-moulded knock out /or plan wall depending on requirement. Box dimension shall not be less than 130 X 180 X77 MM (LXBXH). Box shall be suitable for 16/25Sqmm cables including one no. MCB SP 230 volts 6 amps,10kA,C Curve and connecting the bus bars to cables with using suitable GI nut, bolts and washers and aluminum lugs etc fixed on pole using 30x5mm FI clamps,nuts,bolts & washers complete all as specified and directed. Make: Hensel Cat Part No KF 1010 G/GE/Legrand/Sentex..
Disconnecting & taking down old existing unserviceable MCCB of any description and in any position complete all as specified and directed by Engineer-in-Charge.
Supplying and fixing MCCB, 630 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu100% = 36 KA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/IndoAsian/Havells Cat No-IHLLSECF0630
Supplying and fixing MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Ics = 100% of Icu 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/IndoAsian/Havells Cat No-IHLLSECF0400
Supplying and fixing MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder / L&T /IndoAsian/Havells Cat No-IHLLSECF0250
Supplying and fixing MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder / L&T /IndoAsian/ Havells Cat No-IHLLSECF0200
Supplying and fixing MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, of Make : Legrand/Seimens/Schnieder/IndoAsian
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete all as specified and directed by Engineer-in-Charge.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of front operated ON Load type changeover switch 4 pole, 415 volts, 250 Amps without sheet enclosure complete all as specified and directed.Cat part No: IHCNFO0250 of make Havells or equivalent model of Legrand/Seimens/Schnieder / L&T /Indo Asian specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 400 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0400 of make Havells or equivalent model of Legrand/Seimens/Schnieder / L&T /IndoAsian/HPL specified make as approved by GE.
Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 630 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0630 of make Havells or equivalent model of Legrand/Seimens/Schnieder / L&T /IndoAsian / HPL specified make as approved by GE.
Supplying,fixing,testing and commissioning in replacement of LT panel board outdoor factory made kiosk cubbical type, dust & vermin proof of suitable size (1.65x1.0x0.50mm) Ip class protection made of 3 mm thick CRCA sheet and angle iron 50x50x6mm frame including power coating complete with locking arrangement mounted on PCC Plate form 100 mm thick made out of PCC 1:3:6,100 mm thich, 1 mtrs all round the panel board complete with the following items housed in :-
(i) Incoming :- (a) MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35/36 KA with adjustable thermal magnetic setting, Qty – 01 No.(Make:Legrand/Schnieder/Siemens/L&T/Indo Asian) (b) Digital Ammeter 3 Phase AC 0 – 400 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 800Amps rating and one No. bus bar of 400 Amps rating of suitable shape and size.
(ii) Out Going (a) MCCB, 200 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 35/36 KA with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens /Havells/HPL/Indo Asian)
(b) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity, 25 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens /Havells/HPL/Indo Asian)
Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level.
Supplying,fixing,testing and commissioning in replacement of LT panel board outdoor factory made kiosk cubbical type, dust & vermin proof of suitable size (130x1.0x0.50mm) Ip class protection made of 3 mm thick CRCA sheet and angle iron 50x50x6mm frame including power coating complete with locking arrangement mounted on PCC Plate form 100 mm thick made out of PCC 1:3:6,100 mm thich, 1 mtrs all round the panel board complete with the following items housed in :-
(i) Incoming :- (a) MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal magnetic setting, Qty – 01 No.(Make:Legrand/Schnieder/Siemens) (b) Digital Ammeter 3 Phase AC 0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 800Amps rating and one No. bus bar of 400 Amps rating of suitable shape and size.
(ii) Out Going (a) MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 35/36 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells)
(b) MCCB, 100 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells)
Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level.
Dismantling, taking down and removing the old existing un serviceable non-functional / broken hinges of any description and in any position of existing feeder pillar boxes/panel boards/feeder pillar boxes etc and supplying and fixing new cold rolled 50 mm long medium weight mild steel butt hinges in position with necessary spot welding etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed by Engineer-in-Charge. (Note :- Each hinge point shall be measured as one unit. )
-ditto- but supplying and fixing new cold rolled 100 mm long medium weight mild steel butt hinges in position –ditto-
Taking down unserviceable indication lamp and supplying, fixing, testing and commissioning indication lamp (LED type) with showing red, yellow and green in colour of 22.5 mm dia monitor on LT panel board suitable for 240 V AC supply all as specified and directed. Make : L&T /Binay.or equivalent approved.
Disconnecting, dismantling, taking out & removing unserviceable volt meter and Supplying, fixing, testing and commissioning of digital electronic volt meter 0-500 V range suitable for LT 415 Volts panel flush pattern square type 96mmX96mm with adopter complete with button all as specified and directed. Make : ENERCON/AE Note :- The rate quoted shall be deemed to including the following:- (i) Control wiring for auxiliary supply 230 Volts AC if required. (ii) Cutting the sheet of the panel to suit with existing panel if required. (iii) Calibration and testing the meter.
Demolition of cement concrete (unreinforced) of any description as in ground floors and pavings not exceeding 15 cm thickness (above or below ground floors) complete all as specified and directed.
M&L for cement concrete 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in cills, steps, copings, holdfast and the like including weathering, slightly rounded or chamfered angles and throating as directed with and including necessary form work complete all as specified and directed.
S& F in replacement of UNSV lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop retuning, filling & making cable lead by providing Aluminium lugs lead including crimping with crimping tools in the existing LT cable including necessary connection complete etc, all as specified and directed by Engineer-in-Charge.
Up to 50 Sq mm
From 70 Sq mm to 120 Sq mm
From 150 to 185 Sq mm
From 240 to 300 Sq mm
Supplying, Fixing, jointing and testing for provision of straight through joints, epoxy type with epoxy jointing materials, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables all as specified and directed by the Engineer-in-Charge. (MAKE : M.SEAL/DENSON/ MAHINDRA CHEMICALS/3M) :-
50 Sqmm 3½ core
70 Sqmm 3½ core
95 Sqmm 3½ core
120 Sqmm to 150 Sqmm 3½ core
185 Sqmm 3½ core
240 Sqmm 3½ core
300 Sqmm 3½ core
Disconnecting and Taking out old unserviceable ACB any type and shape, size, and Supply, installation, testing and commissioning ACB power rating 1600 Amp, 4 Pole, Ics=ICW=50 KA, 415 Volt, manual drawout version type with Microprocessor release with overload, short circuit, ground fault, neutral fault and intantenous protetion ( LSING) conforms to IEC 60947/is13947 ( Part 1 & 2), ACB shall have LCD display with bettery back-up of suitable capacity to diagnose the type of fault with stamping of time, date and minimum 10 Nos fault history complete, suitable for 415 volt 50 Hz all as specified and directed by the Engineer-in-Charge.Make- L&T Cat Part No. SL96065 or equivalent in Legrant, C&S,Indo Asian,ABB, Havells,HPL, Schneider,
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead 32X 6 mm GI strip, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate No . 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire mesh incl necessary excavation and earth work in any type of soil, and PCC (1: 3 : 6) type C-1 (using 20 mm graded black trap/ granite/ Basalt stone aggregate) for earth pit with 40x40x6 mm mild steel angle iron frame for cover and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1(using 20 mm graded black trap/granite/ basalt stone aggregate) with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle, complete all as specified & directed .
Disconnecting and taking down carefully old unserviceable GI strip of any type and size and Material and labour for laying along the wall/roof GI strip of size 32mm x 6mm complete with all accessories such as porcelain insulators, saddles and fixing screw etc for conductor complete, all as specified and directed by Engr-in-Charge
M&L for two coat of synthetic enamel paint over a one coat of red oxide including preparation of old surfaces of steel surfaces complet, all as specified and directed by Engr-in-Charge.
Supplying, Laying, testing and commissioning in replacement of UNSV XLPE insulated, PVC sheathed (heavy duty) armoured shielded cable with aluminium conductor for working voltage upto 11KV (Earthed) ,conforming to IS 7098 Part-II amended upto date complete, having cross sectional area under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe including making necessary connection with VCB/OCB/ 4 pole/2 pole structure etc. complete all as specified and directed. Make:Havells/CCI/ICL/GLOSTER/Incab/Nicco/Polycab/Plaza) (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and PCC protection shall be measured and paid separately )
120 Sqmm 3core
185 Sqmm 3core
Disconnecting/dismantling existing fixed type capacitor any capacity and supply/ install commissioning and testing of indoor suitable size for automatic power factor controller panel of output rating 30 KVAR 415 volt complete, modular design with enclosure made out of 2/1.6 mm CRCA sheet,powder coated with Dark SIEMENS Grey structure RAL 7032 dark shed cosisting of aluminium busbar with colour coated heat shrinkable PVC sleevs,panel will be front operated ,cable entry from bottom floor mounted complete with following accessories of :-
INCOMMER:-
(a) MCCB 100 Amp TPN of 25 KA 01 Nos. (b) Spreader Link -02 Nos (c) ROH - 01 Nos .(e) 06 Stage APFC Relay - 01 Nos .(f) Digital voltmeter - 01 Set. (g) Digital Ammeter with CT 100/5 - 01 Set (h) Indicating lamps LED type for three phase - R,Y&B - set of three.(j) 6A sp control MCB 10kA - 05 Nos. (k) Cooling Fan -01 Nos
OUTGOING:-
Ditto as item No 53 above but 20 KVAR, 415 volt outdoor type APFC panel with following accessories :-
INCOMMER:-
Incommer:-(a) MCCB 100 Amp TPN of 25 KA 01 Nos. (b) Spreader Link -02 Nos (c) ROH - 01 Nos .(e) 06 Stage APFC Relay - 01 Nos .(f) Digital voltmeter - 01 Set. (g) Digital Ammeter with CT 100/5 - 01 Set (h) Indicating lamps LED type for three phase - R,Y&B - set of three.(j) 6A sp control MCB 10kA - 05 Nos. (k) Cooling Fan -01 Nos
OUTGOING:-
MAHADEV ELECTRICALS
Ansh Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .