Executive Engineer-Electrical
CMD Office, IIT Hyderabad campus, Kandi-502284, Sangareddy, Telangana
Provision of Mechanical Air Ventilation System to the HT and LT Panels inside the Electric substation buildings at IIT Hyderabad, Kandi
2026_IITH_916019_1
IITH/CMD/ELE/NIT/2026-27/08
Open Tender
Electrical Works
120 days
IIT Hyderabad Campus, Kandi
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹88,800
6 Jul 2026
6 Jul 2026
21 Jul 2026
6 Jul 2026
20 Jul 2026
6 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1GSS Ducting | |||||
| 1.1 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and as per technical specifications with all the necessary mounting accessories as required at site for complete installation of following sheet thickness complete | - | - | - | - |
| 1.3 | Thickness 0.80 mm sheet | 780 | Sq.Mtrs | - | - |
| 2Supply and return air-grills | |||||
| 2.1 | Supplying & fixing of powder coated extruded aluminium Supply/Exhaust Air Grills with aluminium volume control dampers as per technical specifications with all the necessary mounting accessories as required in accordence with the approved shop drawings and as per technical specifications and mounting accessories as required for complete installation. | 65 | Sqm | - | - |
| 3Tube Axial Fan | |||||
| 3.1 | Supply, installing, testing and commissioning of Tube Axial fan complete with tube casing, impeller, bird screen, necessary nut bolts and directly coupled TEFC Sq.cage, IE-2 induction motor (if not mentioned) suitable for 415V±10%, 50 Hz. 3 phase electric supply and complete as per technical specifications,noise level shall not be more than 65 dB (A) measured at 1.0m distance (if not mentioned). with all the necessary mounting accessories, vibration isolators as required for complete installation. | - | - | - | - |
| 3.2 | The motor and impeller speed shall be less than 1500 RPM and capacities shall be as follows: | - | - | - | - |
| 3.3 | Air Qty. = 9500 CFM LT panel room exhaust Maximum sound power level at source (LWA) -90 dB (A).Axial fans with fire Rating for 250ºC for 2 hrs with 'H'Class Protection of Motor. | 13 | Each | - | - |
| 3.4 | Total Static Pressure = 25 mm Wg | - | - | - | - |