Loading…
Loading…
Tender Value
₹24.7 L
EMD Value
₹24,750
Closing Date
14 Jul 2026, 6:00 pm5d left
Chief Officer, Dhoraji Nagarpalika, Dhoraji
Providing & Fixing Work Of Fire Hydrant System, At. K.O. Shah Municipal College, At. Dhoraji, Dist. Rajkot Under 15th Finance (Untide) Year-2024-25
319160
Jul-26/WN3
Open
Civil Works
Rajkot
3 documents required · 3 mandatory
₹900
Chief Officer, Dhoraji Nagarpalika, Dhoraji
₹24,750
30 Jun 2026
30 Jun 2026
30 Jun 2026
14 Jul 2026
30 Jun 2026
NAME OF WORK:- PROVIDING & FIXING WORK OF FIRE HYDRANT SYSTEM
LOCATION:- K.O. SHAH MUNICIPAL COLLEGE, AT. DHORAJI
PERCENTAGE RATE TENDER
Item No. & Description Quantity Rate Per Amount
Supply, Installation, Testing and Commissioning of Electric driven Fire pump
(Hydrant) suitable for automatic operation and consisting of following:
complete in all respect as required. a) Horizontal, centrifugal, end suction
pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and
farthest outlet at specified flow of 900 lpm at 70 m. head conforming to IS
standards. (15 HP) 1.00 76421.45 No.
Supply, Installation, Testing and Commissioning of Control Panel suitable for
automatic operation of fire fighting pumps consisting (Main Electric Pump)(a)
Necessary FRLS cabling, cable tray, wiring, earthing from panel to individual
equipment / pump in pump room shall be included in the quoted price.
Contractor has to submit panel SLD/GA dwg for approval. Complete in all
respect as required. 1.00 19149.60 No.
Supply, installation, testing and commissioning of C.I. Butterfly valve
(IS:13095 , PN 16) with flanges, nut bolts, gaskets complete as required.
Supply, Installation, Testing and Commissioning of Cast iron plate NRV valve
Supply, Installation, Testing and Commissioning of 150 mm dia. Pressure
Gauge (for all pipes) of range 0 - 21 Kg / cm² Polished Stainless Steel Case
with positive seal against weather, moisture & dust, with Glycerine filled,
screwed, nipple, isolation valve, U-type stainless steel siphon tube and
complete with necessary as required. 1.00 3173.02 No.
Supply, Installation, Testing and Commissioning of Pressure Switches for
automation of fire pumps. Pressure switches shall be SPDT type suitable for
single phase supply with diaphragm, IP 67 protection as required. 1.00 2171.50 No.
Supply, Installation, Testing and Commissioning of the following sizes of
flange jointed / screwed / welded, M.S. Pipes of Class C (Heavy class) ISI
marked including accessories such as MS bracket, U clamps with Anchor
fasteners, tees / elbows / reducers / couplings / unions / bends / flanges/
wrapping coating for u/g pipes etc., and laying on the surface including
painting with two coats of anticorrosive primer and two coats of approved red
enamel paint after laying and testing after Installation etc. as per
specifications complete as required. All fittings up to 50mm shall be forged
and above 50mm shall be butt welded.
Supply, Installation, Testing and Commissioning S.S. Fire Hydrant Single
Landing Valve with 80 mm N.B. flanged inlet, SS spindle controlled 63 mm
dia female instantaneous outlet type. SS coupling, blank cap, chain, twist
release type lug & all accessories Conforming to IS:5290. Including fixing with
anchor fastener and flanged tapping from wet riser complete as required.
Item No. & Description Quantity Rate Per Amount
Supply, installation, testing and commissioning of First Aid Hose Reel
conforming to IS:884 comprising of hose reel drum, 8 mm shut off nozzle,
hose reel tubing type-2 as per IS: 444 of 25 mm dia x 30 mtr. long, painting,
fixed wall type with fixing bracket, anchor fastener, bolts & nuts etc.
Supply, Installation, Testing and Commissioning of Fire Hose Cabinet wall
mounting type 18swg (750 mm x 600 mm x 250 mm deep) with required
accessories as per specification. 6.00 6273.92 No.
Supply, installation, testing and commissioning non-percolating rubber
reinforced lined Fire Hose pipe (as per IS : 636) of 63 mm dia and 1no.x15
mtrs long. The hose shall be rated for burst pressure of 38 kg/sqcm. Hose
shall be complete with ISI marked SS male & female coupling (IS:903) bound
as per specification 6.00 40383.84 No.
Supply, installation, testing and commissioning of forged brass Ball Valve.
Supply, Installation, Testing and commissioning of 63 mm dia instantaneous
pattern SS short branch pipe, 20 mm dia nozzle conforming to IS
suitable for inter connection to hose pipe coupling complete as required by
the Local Fire Authority. 6.00 4110.50 Rmt.
Supply, installation, testing and commissioning of Cast lron Two Way Fire
Brigade Inlet as per IS: 904 having 63 mm dia inlet with blank cap and chain
with necessary fittings, flanges, nut bolts etc. complete as required. 1.00 7716.20 No.
Supply, Installation, Testing and commissioning of Quartzoid Bulb type
Sprinkler Heads. a) Pendent Sprinkler 68°C - quick response - UL listed 55.00 565.60 No.
Supply, installation, testing and commissioning of ABC type 6 kg stored
pressure, squeeze type confirm to IS:15683, with ISI marked fitted with
required accessories including wall suspension brackets. 10.00 2235.53 No.
Supply, installation, testing and commissioning of Carbon Dioxide (Co2) type
Fire Extinguisher of 4.5 kg confirm to IS:15683, stored pressure, squeeze
type with ISI marked fitted with required accessories including wall
suspension brackets. 10.00 7708.99 No.
Getting Approval/NOC of Fire protection system (Hydrant, Sprinkler etc..)
from local fire authority and any other relevant statutory authority at initial and
various other stages of work, including preparation of report/drawings as per
fire authority. 1.00 101000.00 No.
Fire NOC Approved Structure drawing charges 1.00 35350.00 Job.
Supplying, installing, testing and commissioning of Fire Manual Call Point 6.00 1298.05 No.
Supplying, installing, testing and commissioning of Fire Alarm Sounder 6.00 1009.60 No.
Supply, installation, testing and commissioning of Pump on/off Remote
switches to each internal hydrant valve with required accessories. 6.00 747.40 No.
Supplying, installing, testing and commissioning of Fire Alarm smoke dedetor
4 ZONEpanel Installation & Commisionning Fire ALARAM Panel 1.00 9374.82 No.
Supplying, installing and testing of 1mm ,2 Core Fexibal cable fore fire alarm
system smoke cable. 380.00 201.92 Rmt.
Item No. & Description Quantity Rate Per Amount
Anticorosion Treatement 50.00 793.25 Liter
Core Cutting 20.00 1124.98 No.
Water Tank 5000 Liter 5000.00 12.63 Liter
Total Amount Rs..........
Total Amount Rs..........
Say Rs..........
I/We am/are willing to carry out the work @ ________% Above / Below_________Percentage (should be writen in
figures and words) of the Estimated rates mentioned above amount of my / our Tender works out as under.
Estimated Amount Estimated Amount
Put to Tender Rs. 24,72,113=00 Put to Tender Rs. 24,72,113=00
Add……………..% Rs. Deduct……………..% Rs.
Total Rs. Total Rs.
(In Words (In Words
Stamp with Signature of Contractor
Consl.Engineer Municipal Engineer
"DESIGN POINT" Dhoraji Nagarpalika
Chief Officer President
Dhoraji Nagarpalika Dhoraji Nagarpalika
Dhoraji Dhoraji
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01 Fire Hydrant System Vol I.pdf
02 Form B-1.pdf
03 Fire Hydrant System Vol II.pdf
04 Schedule B.pdf
05 Term and Condition.pdf
06 Specification of Building Work.pdf
07 Vendor Civil work.pdf
08 Test Require for Construction Material.pdf
09 GR All.pdf
10 DMO_2941_01-Apr-2026_744.pdf
11 GR Affidavit.pdf
12 Site Visit Certificate.pdf
Download all tender documents and submit your bid