Loading…
Loading…
Tender Value
₹31.3 L
EMD Value
₹62,500
Closing Date
2 Apr 2025, 3:00 pmClosed
KOTA - Extension of ART shed, construction of office building and augmentation of infrastructure of ART/ARMV of Kota Division. (Cost of Electrical G Work regarding Lighting. Wiring, Pre-Cooling, charging and other arrangements.)
EL-50-243-2024-25
EL-50-243-2024-25
Open
Works - General
4 Months
Kota, Rajasthan
₹0
₹62,500
10 Mar 2025
10 Mar 2025
A-Tender schedule
Supply & fixing of T-5 20 watt LED batten 4' long (Approx.) with cool white light complete with extruded aluminum housing with decorative end cap, aluminum heat sink, heat resistant square polycarbonate defuser, input voltage 142 to 270 volts AC, 50 Hz, constant current LED driver with short circuit protection, over voltage protection, under voltage protection, driver 01 surge protection of minimum 1.5 KV ±3% with power factor >0.95. full load efficiency >90%, CRI >75, CCT 5700K to 6500K, THD <20% at full load, view angle of LED should be 120 degrees, LED output efficiency >100 lumens per watt, LED life >50000 hours, fitting should be IP-20, LED should be of OSRAM, PHILIPS, NICHIA, CREE, SEOUL, LUMILEDS, LEDNIUM, AVAGO, SAMSUNG make. (Note - LED data sheet used and driver and LM-80 report should be submitted along with the quotation and along with the delivery challan/bill.)
Supply and fixing of BEE 5 star rated energy efficient BLDC ceiling fan, sweep size: 1200 mm with wiring connection etc as per detailed technical specification as below- Supply and fixing of BEE 5 star rated energy efficient BLDC ceiling fan, sweep size : 1200 mm with Modular Electronic Regulator, length of down rod (without shackle) - 300mm, Motor Brushless DC (BLDC), 02 Super-efficient power consumption(watt) <30 watt, Harmonic Distortion -10% Max., Color- Standard White, Blade thickness (Min.)- 1.1mm, Blade material - Aluminum, Double ball bearing-Yes, Shank Thickness - (Min.) 2mm, Canopy - 02 Nos., Confirming to IS: 374(Latest), Air Delivery 220M³/Min., Speed Control - Modular Electronic Regulator, Availability of test report for NABL/ILAC accredited or Central Govt. Lab to prove product specification - Yes & Test report number & date name and address of Laboratory - Yes.
Supply, Fixing, testing & commissioning of exhaust fan sweep size 300 mm suitable for 230volt AC, 50HZ confirming to IS : 555 latest complete with accessories.
Supply and fixing of wall mounted bracket fan sweep 400 mm suitable for 230 volts , 50 hz moving type with regulator and control switch on & off with accessories confirming to IS : 555 latest complete with accessories.
Supply and installation of Flykill-LITE Insect killer machine approximate:26 Inch L X 4.5 Inch W X 12.5 Inch H. Two tubes 18W X 2 ,Aluminium Body.
Supply, installation, testing & commissioning of concealed wiring of light/Fan/Bell points in PVC rigid conduit pipe size 25mm dia medium class minimum thickness approx. 1.6mm to 06 1.8mm of ISI mark with 1.5 sq.mm. multistrand PVC insulated copper conductor cable confirming to IS:694-1990 or latest with one holder/ceiling rose on junction box with round plate with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing alongwith connection etc. including stone wall cutting, replaster, painting and other civil work
Supply of material for concealed wiring of sub main phase & neutral in PVC rigid 07 conduit pipe size 25mm dia medium class minimum thickness approx. 1.6mm to 1.8mm of ISI mark with 4 sq.mm. PVC insulated single core multistrand copper cable with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing & connection etc. Separate PVC pipe to be provided for this item. including stone wall cutting, replaster, painting and other civil work
Erection, testing & commissioning of concealed wiring of sub main phase & neutral in 08 PVC rigid conduit pipe size 25mm dia medium class minimum thickness approx. 1.6mm to 1.8mm of ISI mark with 4 sq.mm. PVC insulated single core multistrand copper cable with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing & connection etc. Separate PVC pipe to be provided for this item. including stone wall cutting, replaster, painting and other civil work
Supply of material & fixing of flush metal box of 2-Module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate Inner & Outer 2-Module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 4-Module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate Inner & Outer 4-Module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 6-Module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate Inner & Outer 6-Module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 8-Module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate Inner & Outer 8-Module used for concealed modular wiring.
Supply of material & fixing of flush metal box of 12-Module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate Inner & Outer 12-Module used for concealed modular wiring.
Supply of material & fixing of 6 Amp. 5-pin socket (2-Module) used for concealed modular wiring.
Supply of material & fixing of S.P. switch 6 Amp. one way (1-Module) used for concealed modular wiring.
Supply of material & fixing of 6/16 Amp. 6-pin combined shuttered socket (2-Module) used for concealed modular wiring.
Supply of material & fixing of S.P. switch 16 Amp. one way (1-Module) used for concealed modular wiring.
Supply & fixing of blank plates (1-Module) used for concealed modular wiring.
Supply of material & fixing of fan regulator 5-step (2-Module) used for concealed modular wiring.
Supply, Installation, Testing & Commissioning of 2-Ton Spilt AC as per detailed technical specification as below- Supply, Installation, Testing & Commissioning of 2-Ton Spilt AC with 5 BEE star rating marking on split AC as per IS:1391 (Part-2). Technology of AC - Inverter AC (variable 25 speed) Refrigerant type- R-32 Compressor type - High EER Twin Rotary - BLDC Coil material evaporator - Copper Coil material condenser - Copper Rated cooling capacity in watt as per IS:1391 (Part-2) cooling capacity value should match with respect to their nominal marketing capacity in tonnage 5201< 7000. Nominal marketing capacity as per BEE Star rating lable (Hint - 1 ton = 3000 KCAL/Hr.) Input power supply - 230 V AC ±10% 50 Hz. Noise level - As per IS:1391 latest. Installation kit - Yes.
3" Hole in stone/Bricks wall with PVC pipe fixing.
Supply and fixing of PPR drain pipe (1" in main line & ½" in branch line) concealed in wall complete with all accessories like T, Elbow, Socket etc.
Supply of copper tube pipe line 5/8"+ 3/8" copper tube with insulation sleeve with 4 core copper cable 1.5 sq.mm for 2.0 Ton Split AC.
Installation of copper tube pipe line 5/8"+ 3/8" copper tube with insulation sleeve with 4 core copper cable 1.5 sq.mm for 2.0 Ton Split AC.
Supply of 5.0 KVA Automatic line voltage stabilizer as per detailed technical 30 specification below- Supply, installation, testing & commissioning of 5.0 KVA Automatic line voltage correctors (step type) confirming to IS:8448-1989 or latest. Input voltage range single phase sine wave (120-280 V AC) Output voltage range single phase sine wave (195-245 V AC) Material winding - Copper Voltmeter - Digital volt meter Indicator Lamp - Yes Mounting type- Wall mounting.
Supply and fixing of 'L' type wall mounted stand for outdoor split AC units.
Supply & fixing of MCB Modular SP 20/25 Amp with box.
Supply & fixing of Metal Clad Plug and Socket box 250volt.
Supply of material, installation, testing and commissioning of distribution box as per 34 model No. DBDD 12 or similar and separate neutral link with one MCB triple pole 63 Amp. rating in the incoming and five Nos. single pole 25 Amp. and 6 Amp. MCB for outgoing circuit. The internal wiring from 63 Amp. MCB to 25 Amp. MCB should be done with 10 sq.mm. copper PVC insulated conductor by distributing all three phase etc.
Supply of materials and fixing of main distribution box 10 way suitable for housing MCB and ELCB with copper busbar and neutral link. Distribution box should be fixed on wooden taper 35 plug or steel fasteners etc. with providing and fixing of 01 no. MCB DP 32 Amp. breaking capacity 6 KA and 06 Nos. MCB SP 6-32 Amp. breaking capacity 6 KA with 01 No. ELCB 40 Amp. DP, sensitivity 100 m.Amp. and connections etc. The distribution board is to be fixed on wall with the help of rag bolt /fastener or on board and connecting the same with suitable size of wire duly crimped lugs.
Supply of materials and fixing of main distribution box 4+2 way suitable for housing MCB and ELCB with neutral link. Distribution box should be fixed on wooden taper plug or steel 36 fasteners etc. with supply and fixing of 01 no. MCB SPN 16 Amp. breaking capacity 10 KA and 02 Nos. MCB SP 6-32 Amp. breaking capacity 10 KA with 01 No. ELCB 25 Amp. DP, sensitivity 30 m.Amp. and connections etc. The distribution board is to be fixed on wall with the help of rag bolt /fastener or on board and connecting the same with suitable size of wire duly crimped lugs.
Supply, installation, testing & commissioning of VTPN Double Door Distribution Board 8 Way TPN IP43 with provision of MCCB 125 Amp. 4P 25 KA - 01 No. in Incoming and MCB SP 32 Amp. C-Curve - 18 Nos. in Outgoing circuit wirh provision of internal wiring and other civil work as per attached detailed specification.
Supply & fixing of MCB distribution board double door Wall mounted having MCCB 100 Amp TPN on incoming & 12 Nos MCB SP 06-32 Amp braking capacity 10 KA,on outgoing connected through busbar & equally distributed on 3- phase complete with connection.
Supply of material and wiring , testing and commissioning of light/fan point in PVC 39 rigid conduit pipe size 19/20 mm medium class with 1.5 sqmm multistrand PVC insulated copper conductor cable confirming to IS: 694-1990 or latest amd 2.5 sqmm PVC insulated copper wire coloured for earthing alongwith connections etc.
Supply of material and wiring , testing and commissioning of sub main phase and 40 neutral in PVC rigid conduit pipe size 25 mm dia. Medium class mark with 4 sq.mm. PVC insulated single core multistraned copper cable with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing and connection etc. Separate PVC pipe to be provided for this item.
Dismantling of old wiring, LP/FP/fittings/boards etc & depositing to Concern Rly Store.
Supply, Installation, fabrication, testing & commissioning of LT Distribution panel suitable for outdoor use with canopy and double door type with stand as under, INCOMING CIRCUIT- 01 No. MCCB 4 pole 400 Amp. 50 KA MP based LSIG Adj. O/L Adj. S/C. Ampere meter with selector 42 switch -01 no., voltmeter with selector switch -01 no., indication lamp RYB 03 nos., Change over 01 no., Energy meter - 01 no., CT 400/5- 03 nos., Copper busbar 400 Amp. rating- 01 set, MCB 6A SP C 10KA - 04 nos.. OUTPUT CIRCUIT - 04 no. MCCB 3pole 200 Amp. 36 KA TMD, 02 no. MCCB 3pole 100 Amp. 36 KA TMD. All MCCB in outgoing circuit will provided with HRC Fuse etc. as per attached detailed specification.
Supply and Installation, fixing of Octagonal pole/pole of 3/3.5 meter (approx.) height 43 Double Arm Type capable of fixing of LED light fitting and should have inbuilt junction box. The material should be of relevant IS and design as per site conditions (Note:- Design should be approved by railways before supply by competent authority.). The Pole should be complete in all respect as per explanatory notes.
Supply and installation of LED FLOOD Light Fitting 50 watt complete suitable for 230 V AC 50 HZ.
Supply and installation of LED FLOOD Light Fitting 100 watt complete suitable for 230 V AC 50 HZ.
Supply of Stranded compacted circular aluminum conductor A2XFY conductor 46 screened with extruded , semi conducting compound XLPE insulated screened with extruded semi conducting compound in combination with copper tape (0.3 kA to 1 sec) core laid up inner sheath (ST- 2) PVC galvanized steel strip armored and overall PVC sheathed black cable HT cable size 3 core x 70 sqmm suitable for 11 kV(E) 6.6 kV (UE) confirming to IS 7098(Part-II) 1985 /with latest amendments.
Laying, testing and commissioning of Stranded compacted circular aluminium conductor A2XFY conductor screened with extruded , semi conducting compound XLPE insulated 47 screened with extruded semi conducting compound in combination with copper tape (0.3 kA to 1 sec) core laid up inner sheath (ST-2) PVC galvanized steel strip armoured and overall PVC sheathed black cable HT cable size 3 core x 70 sqmm suitable for 11 kV(E) 6.6 kV (UE) confirming to IS 7098(Part-II) 1985 /with latest amendments.
Supply and fixing of 11 kV cable end box outdoor type heat shrinkable type for 11kV XLPE 3 core 50-95 sqmm size and connection with crimped lugs on cable end box.
Supply of material and Providing of copper plate Earthing arrangement by digging the Pit. Copper Plate size 600 X 600 X 3 mm as per drg.No.DRM/KOTA/01927/ELR.
Laying, testing and commissioning of LT XLPE insulated stranded armour conductor cables of various size. The cables to be laid in existing trench/ air/ pipe and connection with crimped lugs & cleating of the cable. Note - Cable will be supplied by Railway.
Digging of trench in pucca trench in yard/ platform 50 cm. deep and 35 cm. wide 51 including re-plaster on surface by cement concrete after laying of cable. Wherever the digging of trench to full size is not possible, measurement will be proportionate to the actual volume of cross section and length of the trench.
Digging of trench in all type of soils/ road cutting 100 cm. deep and 50 cm. wide. B 52 class bricks on both sides and top of the cable are to be provided. Brick length to be kept across the length of the cable including refilling the trench after laying of cable. Payment for trench will be made on flat rate basis, if it is dug more or less by 1 meter, payment will be made proportionately.
Drilling of Horizontal bore below track/road by pushing method for laying of HDPE/DWC pipe of various size.
Supply of material, providing, commissioning and laying of DWC/HDPE pipe of 160/138 mm dia cabling under road/track. As per explanatory notes.
Supply, laying , fixing of heavy duty ISI marked B class GI pipe of 3.65 mm wall thickness & 50 mm diameter to be laid along the wall or floor with proper galvanized clamp through the wall or underneath the floor in cement concrete.
Supply of material, fabrication, fixing , connecting , testing and commissioning of heavy duty ISI marked B class GI pipe of 80 mm diameter with suitable clamps on rail/pole/joists with nut/bolts and GI socket as per site requirement.
Supply of material & providing GI. pipe earthing arrangement by digging the pit as per 57 DRM/KTT's Drg. No. 01913EL/R1 or latest complete in all type of soils including rocky area. Earth value will be taken by the contractor in the presence of Railway representative and written on the earth pit by the contractor.
Supply of material, erection, manufacturing, testing & commissioning of pre-cooling cum battery charging switch board cabinet with accessories as per Drg. No. DRM/EL/G/2051 of Sr. DEE/G-Kota as per detailed technical specification attached.
Supply of material, erection, testing and commissioning of battery charger complete 200 Amp. as per detailed technical specification attached.
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .