GE AF TEZPUR PO- SALONIBARI,DISTT- SONITPUR ASSAM-784104
Repair replacement to LA and Earthing system and connected misc work for Technical bldg and flame proof exhaust fans, MCBs, DBs and sub main wiring at AF Station Tezpur under GE (AF) Tezpur
2020_MES_344965_1
8491/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
TEZPUR
Class D cat b(i)
6 documents required · 6 mandatory
₹500
Yes
GE AF TEZPUR
₹89,800
Yes
22 Jun 2020
15 May 2020
15 Jun 2020
15 May 2020
13 Jun 2020
29 May 2020
15 May 2020 - 22 May 2020
Amount
Supply, installation, testing and commissioning of maintenance free chemical earthing system using single spike 17.2mm dia, 3000mm long high tensile low carbon steel circular rod, molecularly bonded with copper on outer surface (minimum copper bonding thickness of 250 microns) meeting the requirements of under writers laboratories (UL) 467-2007 or latest with 250mm long copper strips of size (50X3)mm, exothermally welded on top of electrode complete including augering (boring) 100-125mm dia hole as required for electrode in any type of soil and back filling with carbon based ground enhancing compound (GEC) compound (with minimum qty 35 Kg per electrode) conforming to IEEE/BS standrads incl pit cover light weight made out of high quality polymer with lid made of HDG steel complete all as specified and as directed. Note:- (i) The work of earthing shall be carried out by authorised trained rep of OEM. (ii) The acceptable earth resistance at earth busbar/ test point shall be as per users requirement as desired by Engr-in-Charge but it should be below 01 Ohm . At certain locations, it may not be possible to achieve desired earth resistance with one electrode / pit due to higher soil resistivity,in such cases, provision of loop earthing consisting of more than one earth electrode pits shall be done. The number of pits required shall be decided based on the resistivity of soil and resistance achieved for the earth pits already installed. The distance between two successive earth electrodes shall not be less than 3 metres. (iii) The procedure mentioned here-in-before for one earth pit shall be repeated for other earth pits. (iv) Additional earth electrode pits and loop conductor shall be measured and paid seperately .(v) The rate quated shall also be included the following elements: (a) Complete earthwork including drilling holes for electrode.(b) Earhing electrode-01 only (c) Backfilling carbon based ground enhancing compound (GEC). (d) Pit cover light weight made out of high quality polymer with lid made of HDG steel. (e) Copper strip as earthing lead of size 50mmx3mm, 250 mm long only, beyond 250mm, other size shall be measured and paid for separately under respective item here -in-after. (f) All labour and T&P required including testing of earth network. (vi) Testing for earth resistance shall be carriedout in presence of GE and Engr-in-charge. (vii) Taking out old earthing system complete. (viii) Original purchase vouchers for copper rod and back fill compound and manufacturer test certificate of entire quantity shall be produced by the contractor before commencement on ground.
M and L as in repairs earthing complete with galvanized steel earth plate electrode (600mmx600mmx6mm) thick buried directly in gournd (earth pit not less than 2.25 Mtr deep below normal ground level) with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanized Iron strip (32x6) mm as earthing lead upto 7.5 mtrs from testing point fixed by means of steel bolts, nuts, check nuts and washer, of galvanized earth wire protected by 25mm bore medium grade galvanised iron pipe and other end connected to earthing test point including funnel with watering pipe of 20mm bore light grade galvanised iron, wire mesh, charcoal or coke and common salt in alternate layer of 15cm (Compacted thickness) all around earth electrode with concrete earth pit in PCC (1:3:6) type C-1 50mm thick precast RCC M-20 nominal mix cover slab of size (450mm x 450mm) reinforced with 8mm dia TMT bar 10 cm C/C and suitable handle of 10mm dia round bar including necessary execavation, earth work in soft / loose soil and deposited soil to a distance n.exc 50 M and necessary testing complete all as shown in electrical plate No. 3 of MES shedule of SSR Part-I complete all as specified and as directed. Note:- Earth lead beyond 7.50m shall be measure and paid for separately under relevent Item here-in-after.
M & L as in repairs earthing complete with galvanized steel earth plate electrode (600mmx600mmx6mm) thick buried directly in gournd (earth pit not less than 2.25 Mtr deep below normal ground level) with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanized 4 mm dia earth wire as earthing lead upto 7.5 mtrs from testing point fixed by means of steel bolts, nuts, check nuts and washer, of galvanized earth wire protected by 25mm bore medium grade galvanised iron pipe and other end connected to earthing test point including funnel with watering pipe of 20mm bore light grade galvanised iron, wire mesh, charcoal or coke and common salt in alternate layer of 15cm (Compacted thickness) all around earth electrode with concrete earth pit in PCC (1:3:6) type C-1 50mm thick precast RCC M-20 nominal mix cover slab of size (450mm x 450mm) reinforced with 8mm dia TMT bar 10 cm C/C and suitable handle of 10mm dia round bar including necessary execavation, earth work in soft / loose soil and deposited soil to a distance n.exc 50 M and necessary testing complete all as shown in electrical plate No. 3 of MES shedule of SSR Part-I complete all as specified and as directed. Note:- Earth lead beyond 7.50m shall be measure and paid for separately under relevent Item here-in-after.
M & L Copper earth Strip of size (32 x 6)mm for interlinking between earth electrodes and for continuity fixed with wall/ recess/ chases or buried in ground or any indicated position incl brazing of joints complete all as directed. (Note:-Earth work and excavation shall be measured and paid separately)
M&L copper strip with saddles/ insulators for main earthing lead from test point equipments and fixed with wall/recess/chases or buried in ground or any indicated position of size 20 x 3.15 mm including brazing of joints complete all as specified. (Note:-Earth work and excavation shall be measured and paid separately)
M&L galvanised iron Strip of size (32 x 6)mm for interlinking between earth electrodes and for continuity fixed with wall/ recess/ chases or buried in ground or any indicated position incl brazing of joints complete all as directed. (Note:-Earth work and excavation shall be measured and paid separately)
S&F GI wire dia 4 mm size complete all as specified and as directed. (Note:-Earth work and excavation shall be measured and paid separately)
M&L test point terminal block made of gun metal or phosphorus bronze size (75x75x25)mm drilled and screwed including 3 Nos 8mm dia 25mm long hex. Head screw complete all as specified and directed.
M&L Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and directed
S&F 40 mm bore galvanized steel tubing, medium grade fixed to poles/Walls etc, for holding Air termination with coupling, complete all as specified and directed.
S&F 20 mm bore galvanized steel tubing, medium grade used for watering pipe in conventional earthing pits, complete all as specified and directed.
S&F funnel and wire mesh used for fixing in watering pipe in conventional earthing pits, complete all as specified and directed.
S&F in repair brass bolts, nuts with washer for joinining purpose strips with test terminal block, complete all as specified and directed.
M&L brazing of joints from one end to other end, complete all as specified and directed.
M&L in repairs of earthing complete with galvanised iron pipe electrode 40 mm bore ,medium grade 1mtr length ,buried directly and preferably vertically in ground with top edge not less than 1 mtr below groung level connected with earth lead of 4 mm dia galvanised iron or steel wire complete all as specified and directed.
M & L for making concrete earth pit by dismantling old unserviceable concrete earth pits in PCC type C-1 (1:3:6), 50mm thick precast RCC M-20 nominal mix cover slab of size 600mm x 600mm reinforced with 8mm dia TMT bar 10 cm C/C and suitable handle of 10mm dia round bar including necessary execavation, earth work in soft / loose soil complete all as specified and as directed.
Dressing of copper/GI strips of any size with saddles/ insulators by dismantiling of existing and old broken insulators replace with new insulators of existing size from site and making good disturbed surfaces of floors/walls/ceiling etc complete all as directed.
Supply only carbon based ground enhancing compound ( GEC) compound conforming to IEE/BS standards complete all as specified and as directed. Note: (i) Carbon based ground enhancing compound shall be supplied in packing as per originally packed by the manufacturer. (ii) Material shall be delivered in the store yard of AGE E/M or as directed by AGE E/M and nothing extra shall be payable on this account.
Supply only earthing salt complete all as specified and as directed. Note: (i) Material shall be delivered in the store yard of AGE E/M or as directed by AGE E/M and nothing extra shall be payable on this account.
Supply only earthing charcoal complete all as specified and as directed. Note: (i) Earthing charcoal shall be supplied in packing as per originally packed by the manufacturer. (ii) Material shall be delivered in the store yard of AGE E/M or as directed by AGE E/M and nothing extra shall be payable on this account.
Taking down old unserviceable copper/GI strip and GI wire with saddle of any size and type complete all as specified and as directed.
Taking down old unserviceable Air termination rod 12mm dia ,300mm long of any size and type complete all specified and as directed.
Taking down test point terminal block of any size and type complete all as specified and as directed.
Taking down old unservisable GI steel tubing 20mm bore complete all spcified and as directed
Taking down old unservisable GI steel tubing 40mm bore complete all spcified and as directed
Taking down old unservisable funnel and wire mesh complete all spcified and as directed
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in soft/loose soil for removing/laying of pipe line complete all spcified and as directed
Returning, filling in, including spreading,levelling watering and well ramming in layers notexceeding 25 cm in soft/loose soil complete all spcified and as directed
Removing above the starting point excavated soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all spcified and as directed
Taking down carefully copper/ aluminium point wiring (light/fan/bell/ socket or power point) complete inclusive of all fittings such as switches, ceiling roses, pendants, regulators, sockets, fittings etc. removing materials from site and making good disturbed surfaces of floors/walls/ceiling etc complete all spcified and as directed
Taking down carefully sub main wiring of any type and size including fittings and fixtures, removing materials from site complete all spcified and as directed
Disconnecting from electric circuit and taking out existing unserviceable SFUS, MCB DB SPN/ TPN or change over switches etc any number of ways including MCB etc removing materials from site and making good disturbed surfaces of floors/ walls/ ceiling etc complete all spcified and as directed
M&L point wiring complete with 1.5 Sqmm PVC insulated unsheathed multistranded copper conductor FRLS cable 1100 volts grade, single core, drawn through and including stove enamelled steel conduit not less than 20mm dia with all flame proof accessories such as junction box, MS coupling, unions branch, reducers, elbow, sealing conduit etc. including including 1.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLS Cable (green colour) 1100 volts grade, single core as earth continuity conductor connected to common earth dolly for one light point / fan Point controlled by one one way switch complete all spcified and as directed
All as per ser item No 33 here-in-before but wiring with 4.0 sqmm and 4 Sqmm PVC insulated unsheathed cable 1100 volts grade with multistranded copper conductor cable 1100 Volts grade, single core earth continuity conductor connected to common earth dolly for 3/5 pin 6/16 Amps socket outlet on independent board.
S&F switch flame proof rotary type with termination box in LM6, 16Amps, single pole 250 volts complete all as specified and as directed.
S&F flame proof switch socket & plug combination in LM6 cable termination box in LM6, 16 Amps, 250 volts, 2p+earth complete all as specified and as directed.
S&F ceiling rose, surface bakelite, three terminals, 50mmx65mm complete all as specified and as directed.
S&F LED tube light fittings 1x20W flame proof type FLP-WP made of aluminium alloy LM6, with electronic driver, bipin holder, connected block, etc. complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all spcified and as directed.
S&F LED tube light fittings 2x20W flame proof type FLP-WP made of aluminium alloy LM6, with electronic driver, bipin holder, connected block, etc. complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all spcified and as directed.
S&F BULK HEAD flame proof LED light fitting flame proof type FLP-WP of 1 x 26 watt built in control gear box made of aluiminium alloy LM6,with all accessories, electronic driver, lamp holders,etc internally prewired complete all spcified and as directed.
M&L for two single core PVC insulated unsheathed cable 6.0 sqmm with multistranded copper conductor FRLS cable,1100 volts grade drawn and including Rigid Steel Conduit 20 mm bore and continuous earth wire of single core PVC insulated, unsheathed cable 6.0 sqmm with multistranded copper conductor 1100 volts grade for sub main wiring including taking down old unserviceable sub main wiring of any size and making good disturbed surfaces complete all as specified and directed. Note : Two run of wiring cable, one run of earth wire and one run of rigid steel conduit shall be measured as one unit.
M&L two single core PVC insulated unsheathed cable 4.0 sqmm with multistranded copper conductor FRLS cable,1100 volts grade drawn through and including Rigid Steel Conduit 20 mm bore with accessories and continuous earth wire of single core PVC insulated, unsheathed cable 4.0 sqmm with multistranded copper conductor 1100 volts grade for sub main wiring including taking down old unserviceable sub main wiring of any size and making good disturbed surfaces complete all as specified and directed. Note : Two run of wiring cable, one run of earth wire and one run of rigid steel conduit shall be measured as one unit.
S&F sheet metal enclosures MCB DB 4 way SPN, double door, with 200 Amp rated bus bar including earth & neutral link, complete fixing acessoreies complete all spcified and as directed.
S&F sheet metal enclosures MCB DB 8 way SPN, double door, with 200 Amp rated bus bar including earth & neutral link, complete fixing acessoreies complete all spcified and as directed.
S&F sheet metal enclosures MCB DB 4 way TPN, Vertical type , with 200 Amp rated bus bar including earth & neutral link, complete fixing acessoreies complete all spcified and as directed.
S&F Miniature circuit breaker (MCBs) Single Pole, 240 Volts, 10KA, 6 to 32 Amps, 'C' curve complete all as specified and directed.
S&F MCB SPN 6 to 32 Amps 10KA ‘C’ series 240 volts complete all as specified and as directed.
S&F Miniature circuit breaker (MCBs) Single Pole and Neutral, 240 Volts, 10KA, 40 Amps, 'C' curve complete all as specified and directed.
S&F Miniature circuit breaker (MCBs) Triple Pole and Neutral, 415 Volts, 63KA, breaking capacity 'C' curve complete all as specified and directed.
S&F backlite blanking plate in lieu of MCB's complete all as specified and directed.
M&L sub main wiring with twosingle core PVC insulated unsheathed cable 6.00 Sqmm (Nominal area) with multistranded FRLS copper conductor cable, 1100 volts grade drawn through and including PVC casing & capping of size not less than 25mm with accessories and earth continuity conductor of single core PVC insulated, unsheathed cable 6.0 Sqmm (Nominal area) with multistranded copper conductor, 1100 volts grade and making good disturbed surfaces complete all as specified and as directed. Note:- (i) Two run of wiring cable, one run of earth wire and one run of PVC casing & capping shall be measured as one unit.
M &L sub main wiring with twosingle core PVC insulated unsheathed cable 4.00 Sqmm (Nominal area) with multistranded FRLS copper conductor cable, 1100 volts grade drawn through and including PVC casing & capping of size not less than 25mm with accessories and earth continuity conductor of single core PVC insulated, unsheathed cable 4.0 Sqmm (Nominal area) with multistranded copper conductor, 1100 volts grade and making good disturbed surfaces complete all as specified and as directed. Note:- (i) Two run of wiring cable, one run of earth wire and one run of PVC casing & capping shall be measured as one unit.
M&L two single core PVC insulated unsheathed cable 4.0 sqmm (Nominal aera) with multistranded copper conductor cable, 1100 volts grade, drawn through existing PVC concealled conduit with accessories and continious earth wire of single core PVC insulated, unsheathed cable 4.0 sqmm (Nominal area) with ultistranded copper conductor (green), 1100 volts grade for sub main wiring and making good disturbed surfaces complete all as specified and as directed. Note:- (i) Two run of wiring cable, one run of earth wire shall be measured as one unit.
M &L two single core PVC insulated unsheathed cable 6.0 sqmm (Nominal aera) two run with multistranded copper conductor cable, 1100 volts grade, drawn through existing PVC concealled conduit with accessories and continious earth wire of single core PVC insulated, unsheathed cable 6.0 sqmm (Nominal area) with ultistranded copper conductor (green)one run 1100 volts grade for sub main wiring and making good disturbed surfaces complete all as specified and as directed. Note:- (i) Two run of wiring cable, one run of earth wire shall be measured as one unit.
Dressing of Sub main wiring of any size by dismantiling of existing Point wiring/Sub main wiring and old broken casing caping/steel conduit replace with new casing caping/steel conduit of existing size from site and making good disturbed surfaces of floors/walls/ceiling etc complete all spcified and as directed. Note: Casing caping/Steel conduit shall be measured and paid seprately.
Supply only Casing caping of size 25 mm complete all spcified and as directed.
Supply only Steel conduit of size 20 mm complete all spcified and as directed.
S&F LED as in repair tube light fittings 1x20W flame proof type FLP-WP made of aluminium alloy LM6, with electronic driver, bipin holder, connected block, etc. complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all spcified and as directed.
S&F as in repair LED tube light fittings 2x20W flame proof type FLP-WP made of aluminium alloy LM6, with electronic driver, bipin holder, connected block, etc. complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all spcified and as directed.
S&F as in repair BULK HEAD flame proof LED light fitting flame proof type FLP-WP of 1 x 26 watt built in control gear box made of aluiminium alloy LM6,with all accessories, electronic driver, lamp holders,etc internally prewired complete all spcified and as directed.
M&L rewinding of unserviceable flame proof ceiling fan rotor of any make and 1200 mm sweep size with original gauge of super enamelled copper wire after necessary cutting, removing burnt winding of flame proof Ceiling Fan from core and cleaning all parts including insulation materials, varnishing, heating and replacement of unserviceable spare parts such as capacitor, bearing etc and painting the fan with blade and including testing on full load current complete all spcified and as directed. Note:- (i) Taking down of ceiling fan and refixing shall be included in the quoted rate. (ii) Unit rate of this item is including the cost of transportation charges from original site to workshop and back from work shop to original site.
M&L rewinding of unserviceable flame proof exhaust fan rotor of any make and any sweep size with original gauge of super enamelled copper wire after necessary cutting, removing burnt winding of flame proof exhaust Fan from core and cleaning all parts including insulation materials, varnishing, heating and replacement of unserviceable spare parts such as capacitor, bearing etc and painting the fan with blade and including testing on full load current complete all spcified and as directed. Note:- (i) Taking down of ceiling fan and refixing shall be included in the quoted rate. (ii) Unit rate of this item is including the cost of transportation charges from original site to workshop and back from work shop to original site.
M&L for repair and conversion of conventional light to LED light 1x20W in existing single side flame proof light fitting with spray painting of outer fixture complete with all accessories and complete connection with wiring and make good of all distubed surfaces complete all as specified as directed.
M&L for repair and conversion of conventional light to LED 2x20W light in existing double side flame proof light fitting with spray painting of outer fixture complete with all accessories and complete connection with wiring and make good of all distubed surfaces complete all as specified as directed.
M&L for repair and conversion of conventional light to LED light 1x26w in existing bulk head flame proof light fitting with spray painting of outer fixture complete with all accessories and complete connection with wiring and make good of all distubed surfaces complete all as specified as directed.
S&F as in repair Knobs of flame proof rotary type switch complete all as specified and as directed.
S&F in repair integral LED aviation light luminaries comprising of aluminium housing with polycarbonate enclosure complete all spcified and as directed.
S&F in repair LED 45 W post top made in die cast aluminium with decorative clear opal acrylic diffuser & IP 65 protection complete all spcified and as directed.
S&F as in repair LED batten with tube 1 x 20 Watt, 6500K, System Luminous Efficacy more than 100 lm/W with high quality aluminium extruded with decorative end caps complete all as specified and directed.
S&F as in repair 18 Watt, 6500K T8, retro only led tube,aluminium housing and PC diffuser, complete all as specified and directed.
S&F as in repair Miniature circuit breaker (MCBs) Single Pole, 240 Volts, 10KA, 6 to 32 Amps, 'C' curve complete all as specified and directed.
S&F as in repair MCB SPN 6 to 32 Amps 10KA ‘C’ series 240 volts complete all as specified and as directed.
S&F as in repair Miniature circuit breaker (MCBs) Single Pole and Neutral, 240 Volts, 10KA, 40 Amps, 'C' curve complete all as specified and directed.
S&F as in repair Miniature circuit breaker (MCBs) Triple Pole and Neutral, 415 Volts, 63KA, breaking capacity 'C' curve complete all as specified and directed.
S&F in repair sheet metal enclosure SPN with two pin earth plug and socket complete with one single pole MCB 20 Amps, 10KA, 240 Volts complete all as specified and directed.
THE BUILDERS
M/S Annu Electronics
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .