Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.2 LAccepted-AOC | L1 | Accepted-AOC LOWEST |
Tender Value
Refer Docs
EMD Value
₹23,700
Closing Date
30 Dec 2020, 6:00 pmClosed
Executive Engineer, Electrical, HEED
Executive Engineer, Harbour Engineering Electrical Division, Kamleswaram. Thiruvananthapuram
Upgradation of lighting in Yard at Sakthikulangara Fishery Harbour in Kollam
2020_HED_401898_1
32/HEED/2020-21/S
Open Tender
Electrical Works
Item Rate
90 days
Sakthikulangara Fishery Harbour in Kollam
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,500
Yes
₹23,700
Yes
5 May 2021
22 Dec 2020
4 Jan 2021
22 Dec 2020
30 Dec 2020
22 Dec 2020
Amount
Fabricating, supplying, conveying, lifting and erecting tubular post of overall height 11.70 m using 150mm and 125mm of Heavy duty G.I. Pipe sections having ISI mark and of approved quality(TATA , ZENITH , APOLLO) as per the drawing erected on a RCC footing, using 1:2:4 CC with nominal reinforcement and 6 Nos. of PCC well steining having 0.9m dia and 0.30m height with a muffing of 0.6mx0.6mx1.0m and 8 numbers of 20mm dia 2.80m long MS foundation bolts having 150mm long standard thread on both ends and 3Nos 20mm and 2Nos 20mm nuts at the top and bottom for each bolt . The post is to be provided with a 20mm thick MS flange of OD 300mm with 8 nos of 20mm bolt holes and a base plate of 450mm square 10mm thick with 8 Nos 20mm dia bolt holes embedded in the concrete 1.8m below ground level. The post should have a 1500mm dia ring made out of 50mm heavy GI pipe with cross supports using 40mm heavy GI pipe at the top for mounting the luminaries and its control gears. A 10mm thick MS flange having OD 300mm at 1200mm below the first ring mounted to the post . The top of the pipe should be sealed with 125mm table F Dummy flange.12mm dia wire rope is to be provided for the entire length of the post as mechanical support for the cables to the luminaries. Inverted Y arrangement using 50mm heavy GI pipe and flanges at the top and 75mm 4kgf/cm2 PVC pipe with bend to be provided in the concrete muffing for taking out cables. 8 x 75mm stainless steel Bolt & Nut shall be used for fixing all the flange covers.The post is to be painted with two coats of Industrial Epoxy paint and subsequent two coats of UV resistant polyeruthene paint of approved quality and colour over two coats of best quality Industrial Epoxy primer.All steel items shall be dip galvanised.
Supplying IP66, IK 10 rated 200W NW flood light luminaire with body of aluminium extrusion having luminaire efficacy >= 120lumen/watt supplied with IP67 rated best in class LED driver. Preffered make:Keselec-K Flood 200W- NW
Conveyance, installation, testing and commissioning of departmentally supplied flood light luminaire with lamp on the existing tubular post of height upto 15m from ground level.
Fabricating and supplying special clamping arrangement for fixing an asymmetrical beam integral LED flood light on 50 mm dia GI pipe ring with two clamps each made out of 50 x 6mm MS flat and 8x40mm SS nuts and bolts for one luminaire. The clamps are to be linked with 40x6mm MS flat with suitable holes 8mm ,10mm or 12mm size with suitable size SS Bolt& Nut to fix the luminaire. All the items are to be painted with two coats of epoxy based industrial primer of approved quality and two coats of best quaity synthetic enamel paint of approved colour as per drawing.
Supply and fixing Cable Junction Boxes IP 65 for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm ,80 X 80X 52 mm Cape model Abox i025 or equivalent and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle).
Supply of 4 core 10 sq mm PVC insulated and PVC sheathed armoured aluminum cable
Supply of 4 core 16 sq mm PVC insulated and PVC sheathed armoured aluminum cable
Supply of 2 core 2.5 sq mm PVC insulated and PVC sheathed armoured copper control cable
Supplying and making end termination nickel plated single compression brass cable gland for 2 core 2.5 sq mm PVC insulated and PVC sheathed armoured copper conductor cable 1.1 KV grade, including providing earth clip and superior quality copper cable socket.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 CX 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4C X 16 sq. mm (28mm)
Supply and providing 15mm pvc gland at the junction box including drilling necessary holes as required
Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 x 16 sq.mm
Supply of 50/38mm (OD/ID) Double Walled Corrugated (DWC) pipes made out of HDPE for mechanical protection to under ground power/communication/ OFC / Signal cable conforming to IS 14930 Part - II,
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.2x 2.5 sq. mm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.2 X 4 sq. mm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.4 X 6 sq. mm
Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metre.
Providing and fixing10 SWG copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Providing and fixing 4mm dia copper wire on surface or in recess for loop earthing as required
Providing and laying earth connection earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from on earth electrode including connection with copper thimble excavation and re-filling as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. (but without charcoal/ coke and salt) as required.
Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
Supply of superior quality copper earth socket for the 3.15mm (10 SWG) earth conductor including crimping etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
Supplying and fixing following ways surface / recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, IP 43 , IK 09, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, with provision for MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB's/ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4way (4+12) Double door
Supplying and fixing 40A, four pole, (three phase and neutral), 415 volts,Residual current circuit breaker with Overcurrent Protection (RCBO), having a sensitivity current of 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply, conveyance and fixing 40 A, 25 kA (Ics=100%Icu), 3 pole, MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL & SC conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required
Providing and fixing 32A TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.
Supply and providing 20A - 40A HRC fuse link in the existing Fusebase / SDF.
Supply and providing phase indication lamp
Supply and installation of wall mounting cubicle type dust and vermin proof CAPE make CA63 , 540x270x170mm IP66,IK 10 Glass fibre reinforced polyester enclosure including providing 0.20m copper earthstrip of 25 x 3mm
Dismounting the SV lamp flood light and control gear from the tubular post of height upto 15m from ground level without any damage and keep at a place as per the instruction of the depatmental officer at site.
Providing and laying in position reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required (excluding reinforcement).
Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge.
Scaffolding charges for dismounting light fittings and Control gear and for painting
Painting with 2 Coats of Industrial based Epoxy primer of approved brand and manufacture on steel galvanised iron/steel works (2 Coats)
Painting with epoxy paint of approved brand and manufacture to give an even shade. Two or more coats on new work
Numbering of ceiling fan/ exhaust fan as required.
Supplying and fixing 0.4m x 0.8m door using 14G powder coated Aluminium frame and aluminum infill of weight 0.55 kg/m with fixtures like rubber beeding,silicone sealant, hinges,Tower bolt and pad lock etc
Supply and fixing 20mm SS Nut in the existing foundation
Providing 20mm SS Nut in the existing foundation by lifting the mast using crane
Providing and fixing 50 mm dia nominal bore B class G.I. pipes with ISI mark complete with G.I. fittings and clamps, i/c cutting and making good the walls etc.
Supply and installation of wall mounting cubicle type dust and vermin proof CAPE make CA 63a 540 x 270 x 205 mm Glass Fibre Reinforced Polyester Enclosure IP66, IK 10 outdoor meterbox or equivalent with provision for fixing KSEB meter, cut out & Neutral link and 25A , 16kA TP MCCB, with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link. Supply and providing 1No of 25A,16kA ,Triple Pole MCCB with rotary drive kit , 1 No of 32A HRC fuse units with 20A HRC fuse link and 1No 32A 2way neutral link in the meter portion. Necessary holes are to be provided in the box for entry and exit of wire. The inter connection should be done using 6.0 sq.mm copper wire.
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_571425.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .