Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 CrAccepted-AOC | ₹1.8 Cr | L1 | Accepted-AOC First Lowest |
| 2 | L2₹1.8 Cr+₹1.9 L (1.10%)Rejected-AOC KRISHNAKRIPA KOTTARAKARA | ₹1.8 Cr+₹1.9 L (1.10%) | L2 | Rejected-AOC Third Lowest |
| 3 | L3₹2.2 Cr+₹47.5 L (27.1%)Rejected-AOC 37 1634 IMPERIAL HOUSE KALOOR KATHRIKADAVU KATHRIKADAVU ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | ₹2.2 Cr+₹47.5 L (27.1%) | L3 | Rejected-AOC Second Lowest |
| 4 | Rejected-Technical | - | - | Rejected-Technical not submitted pwd registration and bankers certificate |
| 5 | Rejected-Technical | - | - | Rejected-Technical not submitted ITR 2020-21 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
15 Feb 2021, 4:00 pmClosed
Chief Engineer
Chief Engineer Kerala State Housing Board Santhinagar Thiruvananthapuram 695001
Internal Electrification works Neendakara Taluk Hospital
2021_KSHB_412437_1
2020_CE_KSHB_ 25_W (Electrical)
Open Tender
Electrical Works
Item Rate
120 days
Neendakara Kollam
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,600
Yes
₹50,000
Yes
21 Oct 2022
5 Feb 2021
16 Feb 2021
5 Feb 2021
15 Feb 2021
5 Feb 2021
Amount
WIRING POINTS
od153862/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required.<br>Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points.<br>Group A
od153868/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories).<br>Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Short point
od153876/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories)..<br>Single control light point without ceiling rose - Short point
od153880/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories)..<br>Twin Control light point with 6A, plate ceiling rose - Short point
od153883/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories)..<br>Single Control light point with 6A, plate ceiling rose - Short point
od153887/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories).<br>Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point
od153890/2020_2021 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required.<br>Independent plug <br>Group A
SUB MAIN WIRING&amp;amp; PVC CONDUIT
1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.14.4 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
1.14.7 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
1.14.8 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 4 sq. mm + 2 X 4 sq. mm earth wire
1.17.1 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.1 x 1.5 sq. mm
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.5 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.17.6 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.8 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.8 x 1.5 sq. mm
1.17.9 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.11 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
od153905/2020_2021 : Supplying and clamping the 20 mm dia sizes of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required.<br>
MODULAR BOX,PLATE,SWITCH,SOCKETS &ACCESSORIES
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.15 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.32 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.10.3.33 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
1.26 : Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
2.18 : Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
2.19 : Supplying and fixing 20 amps 415volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 amps "C" curve, TPMCB, in sheet enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
2.20 : Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth,metal enclosed plug top alongwith 30 amps "C" curve, TPMCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
FIXING LED TUBE ,SURFACE PANEL,BULB,BULK HEAD
90.3.19.3 : Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture
od153869/2020_2021 : Supply, conveyance installation testing and commissioning of pre-wired light 8W to 10W ordinary type LED light fittings complete with all accessories and lamps etc. directly on wall or ceiling with PVCround block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.
od153877/2020_2021 : Supply, conveyance, installation, testing and commissioning of LED Bulkhead fitting with all accessories, aluminium diecast housing with powder caoted wire guard. CRI>70, LED Make: Nichia/Cree/Osram/ Lumiled, LED Efficacy>120lm/W, color temperature-5700K, IP65 rated, 50000 burning hours as per L70 Criteria, Ambient temp-0 to 50DegC, Driver efficiency>85%, THD<20%, Powerfactor>0.95, Surge protection in CM-2KV, Multistage Isolated Constant Current-Constant Voltage Operated driver with range 150-270V AC and Safety Extra Low Voltage Safe level<60V DC as per IEC standard. 10W LED Bulkhead luminaire delivering > 720lm, similar to WIPRO ,CROMPTON,JAQUAR OR Equivalent
od153884/2020_2021 : Supply, conveyance, installation, testing and commissioning of High efficient Recess mounted IP54 rated, LED bottom opening cleanroom luminaire with CRCA powder coated Housing, Bottom frame, Satin finish high efficiency translucence (HET) diffuser is sealed with bottom frame and non-hygroscopic VHB gasket to ensure dust proofing, Surface finish in epoxy polyester powder coating lends higher corrosion resistance & life long finish. LED with 50000 burning hours as per L70 Criteria, CRI>70, LED Make: Nichia/Cree/Osram/ Lumiled, color temperature-5700K, , Electronic driver pre wired up to terminal block, Ambient temp-0 to 50DegC, Driver efficiency>85%, THD<10%, Powerfactor>0.95, Surge protection in CM-3.5KV, Multistage Isolated Constant Current-Constant Voltage Operated driver with range 150-270V AC and Safety Extra Low Voltage Safe level<60V DC as per IEC standard.Recess mounted BOCR luminaire, Wattage ≤ 60W, Cutout Dimension- 580 mm x 580 mm luminaire lumen ≥ 5400lm and System Efficacy ≥ 90lm/W. The light fitting need to be supported from ceiling with rod suspension accessories . similar to make Wipro ,crompton,or Equivalent and giving connection with 3 core round flex wire .etc .complete.<br><br>
od153888/2020_2021 : Supply, conveyance, installation, testing and commissioning of Recess mounted circular /squre LED downlighter with housing made up of white powder coated, pressure die cast aluminium for better heat management. Hight Transmittivity Polycarbonate diffuser for uniform light distribution, white rim moulded in engineering plastic, driver pre wired upto terminal block, CRI>80, LED efficacy>170lm/W, LED Make:Nichia/Cree/Osram/etc , Color temperature-6500K, IP20, 50000 burning hours as per L70 Criteria, Ambient temp-0 to 50DegC, Driver efficiency>85%, THD<10%, Powerfactor>0.95, Surge protection in CM-2KV, Multistage Isolated Constant Current - Constant Voltage operated driver with range 150-270V AC and Safety Extra Low Voltage Safe level<60V DC as per IEC standard.Circular recess mounted/squrerecess mounted,Wattage ≤ 11-18W recess mounted similar to make Wipro,crompton,jaguar,Philipser,etc. with luminaire lumen ≥ 820lm and System Efficacy ≥ 75lm/W.and including charges for cutting holes & frame for Gypsum/POP ceiling and.giving connection with 3 core round flex wire etc complete.<br>
od153889/2020_2021 : Supply, conveyance, installation, testing and commissioning of Recess mounted 300mmx300mm Slim LED downlighter, Wattage ≤ 24 W, Cutout Dimension-285X285 mm with luminaire lumen ≥ 2000 lm and System Efficacy ≥ 80 lm/W. ,IP20, Housing made up of die cast aluminium for better heat management. Hight Transmittivity non yellowing LGP PMMA Diffuser for better light output and uniform light distribution without glare. LED- CRI >80, Colour Temperature- 6000K, 50000 burning hours as per L70 Criteria, complying to photobiliogical safety norms as per IEC62471. Driver and accessories are pre wired for easy installation and long service, constant Current Operated driver with range 150 - 265 V AC ,Temperature range- 0 to 50DegC, Driver efficiency>85%, Power factor>0.95, THD<20%, Surge protection upto 2.5 KV,and complying to to Safety Extra Low Voltage Safe level<60V DC as per IEC standard.similar to to make Wipro,crompton,jaguar,Philips,etc. with luminaire lumen ≥ 3000lm and system efficacy>90lm/W.and including charges for cutting holes & frame for Gypsum/POP ceiling and.giving connection with 3 core round flex wire etc complete.
od153892/2020_2021 : Supply, conveyance, installation, testing and commissioning of Recess mounted full panel LED luminaire with Multi Angular design on diffuser White powder coated housing & frame in CRCA sheet, High efficiency LED grade diffuser, electronic driver duly wired upto terminal block, CRI>80, LED Make:Nichia/Cree/Osram/etc, Colour temperature-5600-5900k IP20, 50000 burning hours as per L70 Criteria, Ambient temperature-0 to 50DegC, Driver Efficiency>90%, THD<15%, Powerfactor>0.9, Surge protection in CM-2KV, ModelMultistage isolated Constant current-Constant voltage operated driver with range 150-270V AC and Safety extra low voltage safe level<60V DC as per IEC Standard.2ft x 2ft, Wattage ≤ 31-40W recess mounted similar to make Wipro,crompton,jaguar,Philips,etc. with luminaire lumen ≥ 3000lm and system efficacy>90lm/W.and including charges for cutting holes & frame for Gypsum/POP ceiling and.giving connection with 3 core round flex wire etc complete. Model Crompton Vectot I -LCTLRF1-36-CDL or equivalent<br>
od153893/2020_2021 : Supply, conveyance, installation, testing and commissioning of Recess mounted Slim LED downlighter, Wattage ≤ 15W, Cutout Dimension-178X178 mm with luminaire lumen ≥ 1200 lm and System Efficacy ≥ 80 lm/W. ,IP20, Housing made up of die cast aluminium for better heat management. Hight Transmittivity non yellowing LGP PMMA Diffuser for better light output and uniform light distribution without glare. LED - CRI >80, Colour Temperature- 6000K, 50000 burning hours as per L70 Criteria, complying to photobiliogical safety norms as per IEC62471. Driver and accessories are pre wired for easy installation and long service, constant Current Operated driver with range 150 - 265 V AC ,Temperature range- 0 to 50DegC, Driver efficiency>85%, Power factor>0.95, THD<20%, Surge protection upto 2.5 KV,and complying to to Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Wattage ≤ 9-12W recess mounted similar to make Wipro,crompton,jaguar,Philips,etc. with luminaire lumen ≥ 3000lm and system efficacy>96lm/W.and including charges for cutting holes & frame for Gypsum/POP ceiling and.giving connection with 3 core round flex wire etc complete.<br>
od153894/2020_2021 : Supply conveyance, installation, testing and commissioning of pre-wired Sensor type LED the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required<br>1200 mm 1X20W of pre-wired Sensor type LED Lamp with box type fixture<br>
FIXING CELLING,EXHAUST,WALL FAN
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
od153870/2020_2021 : Supply and providing every additional length of down rod of suitable size heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required.<br>
90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep - ceiling fan complete with 300mm down rod , canopies, shackeles and blades and resistance type regulator working on 230V/240V single phase A/C
od153881/2020_2021 : Supply Conveyance,installation,testing and commissioning of 1400 rpm HEAVY DUTY WALL FAN 600MM Should be of standard make like orient, havells &almonard
od153885/2020_2021 : Supply Conveyance,installation,testing and commissioning of Wall mounting Fans of all types using mounting brackets supplied along with the fan 300MM Should be of stand make like orient, havells &almonard
90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.4.9 : Charges for cutting holes suitable for accommodating exhaust fans above 305mm sweep and up to 450mm sweep including plastering colour washing etc. as required.
od153891/2020_2021 : Supply, conveyance, installation, testing and commissioning of the 450 mm exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS, 450 mm, single phase, heavy duty, 1400 rpm exhaust fan in metal frame<br><br>
od153895/2020_2021 : Supply, conveyance, installation, testing and commissioning of the 225mm exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS,225mm metal frame.
2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.2 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.3 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
90.11.1.10 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.11 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.13.3 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
2.14.3 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
90.11.1.18 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.2.13 : Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 30 KA 4 Pole
2.2.14 : Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp, 36 KA
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
MV CABLE LAYING
90.12.5.30 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 70 sq mm
90.12.5.31 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 95 sq mm
90.12.5.32 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 120 sq mm
90.12.5.33 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 150 sq mm
90.12.6.29 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 50 sq mm
90.12.6.30 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 70 sq mm
90.12.6.31 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 95 sq mm
90.12.6.32 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 120 sq mm
90.12.6.33 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 150 sq mm
90.12.6.34 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 185 sq mm
90.12.6.41 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.4 core 16 sq mm
90.12.6.42 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.4 core 25 sq mm
90.12.7.27 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp
90.12.7.29 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.7.30 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
90.12.7.31 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
90.12.7.32 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm
90.12.7.33 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
90.12.7.34 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.42 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.6.43 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.4 core 35 sq mm
90.12.7.43 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 35 sq mm with factory made clamp
90.12.6.37 : Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 400 sq mm
90.12.7.37 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm
PROTECTIVE PIPE TO CABLE,END TERMINION OF CABLE
90.12.10.2 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.10.5 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation90/75 mm or nearest size
90.12.10.6 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation110/94 mm or nearest size
90.12.10.7 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation120/102.5 mm or nearest size
90.12.10.8 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation125/109 mm or nearest size
90.12.10.9 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation145/123 mm or nearest size
90.12.10.10 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation160/135 mm or nearest size
LT END TERMINATION OF CABLES,CABLE BARE EARTHING,EARTH SCOKET
9.1.20 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)
9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.24 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
9.1.26 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
9.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
9.1.35 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)
9.2.28 : Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 400 sq. mm
90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
PLATE EARTHING
5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.6 : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.8 : Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
5.10 : Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
5.11 : Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
CABLE TRAY
4.1.1 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4.1.3 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
4.1.4 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
4.1.11 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 62.5 mm depth X 2.0 mm thickness
4.1.12 : Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.750 mm width X 62.5 mm depth X 2.0 mm thickness
4.2.11 : Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 62.5 mm depth X 2.0 mm thickness
4.2.12 : Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.750 mm width X 62.5 mm depth X 2.0 mm thickness
4.3.11 : Supplying and installing following size of perforated pre-painted M.S. cable trays reducers with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 62.5 mm depth X 2.0 mm thickness
4.3.12 : Supplying and installing following size of perforated pre-painted M.S. cable trays reducers with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.750 mm width X 62.5 mm depth X 2.0 mm thickness
4.4.11 : Supplying and installing following size of perforated pre-painted M.S. cable trays Tee's with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 62.5 mm depth X 2.0 mm thickness
4.4.12 : Supplying and installing following size of perforated pre-painted M.S. cable trays Tee's with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.750 mm width X 62.5 mm depth X 2.0 mm thickness
4.5.11 : Supplying and installing following size of perforated pre-painted M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 62.5 mm depth X 2.0 mm thickness
4.5.12 : Supplying and installing following size of perforated pre-painted M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.750 mm width X 62.5 mm depth X 2.0 mm thickness
od153898/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Reducer 450 X 300mm
od153899/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Ladder Type 90 Degree Horizontal Bend Radius 300mm with Cover for 300mm Tray
od153900/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Ladder Type 90 Degree Vertical Bend Radius 300mm with Cover for 300mm Tray
od153901/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Ladder type Equal Tee for 300mm Tray with Cover
od153902/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Ladder Type 90 Degree Horizontal Bend Radius 300mm with Cover for 450mm Tray
od153903/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Ladder Type 90 Degree Vertical Bend Radius 300mm with Cover for 450mm Tray
od153904/2020_2021 : supply and installation of FRP Ladder Type Cable Tray Ladder type Equal Tee for 450mm Tray with Cover
od153906/2020_2021 : supply and installation of FRP Ladder Type Cable Tray 450mm(W)X75mm(H)X25mmX3mm with FRP Cover 3mm thickness and Coupler plate 200mm X 50mm X 3mmSS hardware M6X 20
od153907/2020_2021 : supply and installation of FRP Ladder Type Cable Tray 300mm(W)X75mm(H)X25mmX3mm with FRP Cover 3mm thickness and Coupler plate 200mm X 50mm X 3mmSS hardware M6X 20
SCHEMATIC DRAWING FEE ,INSPECTORATE FEE,KSEB CONNECTION FEE
od153859/2020_2021 : Supply and installation laminated all Electrical Inspectorate final approved drawings with copy of final energisation sanction order on the wall of power house.
od153871/2020_2021 : Preparation of 3 set of Electric schematic drawing as per Electrical Inspectorate & KSEB rules and get Approval from Electrical Inspectorate concerned , one set of Approved schematic shall be laminated with good quality laminated paper and the same shall be fixed as directed by Engineer in charge <br>(Rate for each set ) Except statutory fee at Electrical inspectorate
od153882/2020_2021 : Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
od154125/2020_2021 : Provision for statutory fee (like Schematic approval fee, Testing of TriVector meter /CT/Multi Function meter etc as required ) at Kerala State Electricity Licensing Board -Amount will be reimbursed after submitting original document/receipt
NUMBERING OF FITTINGS
od153860/2020_2021 : Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required 6.5 cm, 8 cm or 13 cm height
od153872/2020_2021 : Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required 2.50 cm, 4 cm or 5 cm height
1.49 : Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.
TRANS FORMER
od153861/2020_2021 : Supply installation, Testing and commissioning of 630KV A Indoor Unitised Sub Station with 11KV, , 350 MVA Load Break switch Fuse Unit with HT HRC fuses, Aluminum bus bars, Seal OffBushings, 230 V AC Shunt Trip Coil etc coupled with 630 KVA Cast Resin Transformer of Ratio11KV/433V, Three Phase, 50Hz, AN cooled, Vector DYN 11 with offcirciut tapping's from +5%to -10% in steps of 2.5% changeable by tap links provided, with LV cable box suitable for 4 runs ofPVCA cable The whole unit shal be installed over the PCC foundation etc complete the rate inclusive of unloading ,installation &making foundation etc.
od153873/2020_2021 : Supply and installation of neutral CT of ratio 600/5A, class 5P10 15VA of accuracy for earth fault relay in a metalic enclosure including control wiring from the transformer.
HT PANEL
od153863/2020_2021 : Supply installation Testing and commissioing of Outdoor Type Load Break Switch Panel with necessary CTs and PT for KSEB Metering , HT HRC fuses, Seal off Bushings, TOD Meter, Aluminium busbars, and provision for sealing. Panel shall be self standing suiatble for outdoor installation of Ingress protection : IP:54.
GENERATOR
od153864/2020_2021 : Supply,Installation,Testing and commissioning of 250KVA/200KW DG Set with Standard Control panel ,CPCB II Type approved Accoustic Enclosure and anti Vibration pads as per CPCB norms comprising of radiator cooled ,Turbocharged after cooled diesel engine with individual cylinder heads, developing 300or more BHP at 1500RPM complete with standard accessories coupled to Alternator rated at 250KVA/200KW at415Volt mounted on base frame with inbuilt fuel tank of 650 litres capacity, Standard RunningControl Panel complying to Kerala Electrical Inspectorate specifications and batteries with lead and AVM Pads etc as per Electrical Inspectorate requirements including unloading charges and all duties and taxes and including cost of extending the exhaust pipe up to the DG set building by using B Class MS Pipe of suitable size formation of foundation and installation including providing emergency button(Excluding cost of Cable laying as per IS/Electrical Inspectorate standard norms)
od168040/2020_2021 : Supply,Installation,Testing and commissioning of 400KVA/320KW DG Set with Standard Control panel ,CPCB II Type approved Accoustic Enclosure and anti Vibration pads as per CPCB norms comprising of radiator cooled ,Turbocharged after cooled diesel engine with individual cylinder heads, developing 600 or more BHP at 1500RPM complete with standard accessories coupled to Alternator rated at 400KVA/320KW at 415Volt mounted on base frame with inbuilt fuel tank of 990 litres capacity, Standard Running Control Panel complying to Kerala Electrical Inspectorate specifications and batteries with lead and AVM Pads etc including unloading charges and all duties and taxes and including cost of extending the exhaust pipe up to the DG set building by using B Class MS Pipe of suitable size formation of foundation and installation including providing emergency button.(Excluding cost of Cable laying as per IS/Electrical Inspectorate standard norms)
od153875/2020_2021 : Supply and installation of exhaust piping complete with thermal insulation with mineral wool and AI cladding MS pipe of suitable dia,heavy duty bend,flexible connector and supports 200mm
X-RAY/CT
2.2.14 : Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp, 36 KA
90.14.11.2 : MCCB AccessoriesSupply and fixing one number earth fault Relay up to 125A to 200A with CBCT.
90.14.11.10 : MCCB AccessoriesSupply and fixing auxiliary switch + alarm switch (1 NO + 1 NC & 1 NO) in the existing MCCB of rating up to 630A.
90.14.11.11 : MCCB AccessoriesSupply and fixing one number under voltage release for all voltage range up to 630A MCCB.
90.14.11.12 : MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
od153865/2020_2021 : Supply, installation,and commissioning of 30kw UPS with min 10 modules Three phase in and out with vertical & horizontal modular parelleing compatibility with indoor (IP20) with surge protection system with 30 min backup battery @ 30kw .8 PF load (SMF battery of reputed approved make exide/Amararaja), having battery bank with Min VAH 32250 per ups, Input pf >0.99, input THDi <5 % without use of any external filters, external isolation transformer, double conversion technology with input voltage range 320-460 @ full load, 50Hz Three Phase, output 400V, 50Hz Three phase, SNMP card for network monitoring, compatibility etc. It shall be 100% generator compatible, with Efficiency > 94% and output power factor unity ( 30kVA= 30kW), Eco mode Efficiency 98% and including all accessories etc as required.The system shall comply to IEC /EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, CE, PEP (LEED) and relevant IS standards. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic bypass builtin. The system shall have IGBT rectifier and inverter. warranty 2 years for UPS and batteries. Approved brand - Fuji Electic/Legrand Numeric/APC/GE
od153867/2020_2021 : Supply, installation, and commissioning of 40kva UPS Three phase in and out standalone UPS. with future PRS option with indoor (IP20) with surge protection system with SMF battery of reputed approved make exide/quanta/panasonic), Input pf >0.99, input THD&5 % without use of any external filters, Internal isolation transformers at output, to have transformer output even in bypass mode, double conversion technology with input voltage range 350-475 @ full load, 50Hz Three Phase, output 400V, 50Hz Three phase, SNMP card for network monitoring, Compatibility etc. It shall be 100% generator compatible, with Efficiency > 93% and output power factor unity ( 40kVA= 32kw), Eco mode Efficiency 98% and including all accessories etc as required.The system shall comply Type test certificates, and relevant IS standards. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic bypass builtin. The system shall have IGBT rectifier and inverter. warranty 2 years for UPS and batteries. Approved brands Fuji Electric/APC/GE/Numeric-legrand Min: VAH for 30 min. per UPS kva 48000VAH
HT SUPPLY
od153866/2020_2021 : Supply and erection of Double pole structure using 10.5mtr 200 x 100mm RS joist with required quantity of 100 x 50mm MS channel for mounting AB switch, DO fuses, Lightning arrestors,etc with Ms flats clamps,base plate, bolts nuts etc., including cutting, welding, aluminium painting all as per standard requirements of Electrical inspectorate, complete including supply and installation of following overhead line accessories as required.<br>11KV pin insulators.<br>11KV Disc insulators.&11KV, 400A, 3 phase gang operated , vertical single make/break type off load Air breake switches complete with all hardwares like insulators, fixing channels, operating rods, handle locking arrangements, bolts nuts and complete.9kv, 5kA lighting arrestor <br>11kV, 400A dropout fuse sets, complete with all hard ware like supporting insulators , fuse rods, bolts and nuts complete.<br>4Nos.Pipe earth electrode for the DP structure & LA Earthing , 6 SWG Copper for Lightning arrestor earthing including all round fencing to a height of 1.8 meter with allround clearance of 1.25 meter and filling of 40mm granite gelly in the yard.
HT CABLE
od158520/2020_2021 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 11KV grade of 3 core 185 sqmm 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.<br>3 core 185 sq mm HT CABLE
od158521/2020_2021 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 3 core 185 sqmm 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.<br>3 core 185sq mm
od158522/2020_2021 : Supply & laying of one No. 3 core 185 sqmm 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments in the existing masonry open duct as required.<br>3 core 185 sq mm
od170706/2020_2021 : Supplying and making Outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminum conductor cable of 11 KV grade as required:<br>185 sq. mm
od170707/2020_2021 : Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:<br>185sq. mm
CAPACITOR PANEL
od157472/2020_2021 : ">> Supply, installation, Testing and commissioning of 160 KVAR APFC PANEL,Automatic Power Factor Correction panel shall be certified by 3rd party Certification body as per IEC 61439-1, 2. Test reports without certificate shall not be considered admissible proof of compliance. The Certifying Authority shall be qualified under ISO/IEC 17065 as per IEC 61439-1. >>The type tested designs of the switchboards shall be proven design from switchgear manufacturer (OEM) >>Switchboards shall have a short circuit level of minimum of 50 KA withstand. Switchboards shall have Rated Impulse withstand voltage of 12kv >>All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection of IP 42 unless otherwise stated. >>Switchboards shall be validated design for Seismic withstand as per standard IEC60068. >>Switchboards must have mechanical impact IK10 tested<br>>>Switchboards construction shall employ the principle of compartmentalised and metallic segregation for each circuit<br>>>Switchboard panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness, same as that of tested assembly per IEC61439-1 & 2 >>Doors with transparent safety glass with aesthetic appeal to avoid all risk of injury.<br>>> ( Approved Makes : Schneider Prisma , ABB MNS , SIEMENS Sivacon)" Incomer<br>*400, TP, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. <br>Instruments<br>*2A, C curve SP MCB - 1 set<br>*RYB indication lamp, LED type - 1 set<br>*On, Off, push button with indication lamp, LED type - 8 set <br>*1 No 3 phase Digital Multi function meter to read V, A, F, PF Acc class 1 and with RS485 communication port.<br>*400/5A 10VA class 1 resin cast CT - 1 set<br>*STEPS Details of Capacitor- 5KVR1 set,10KVR2 set,15KVR2 set,20KVR4,25KVR1 set<br>
MSB -PANEL
od170402/2020_2021 : Supply, installation, Testing and commissioning of MSB PANEL-LV Switchboards shall be certified by 3rd party Certification body as per IEC 61439-1, 2. Test reports without certificate shall not be considered admissible proof of compliance. The Certifying Authority shall be qualified under ISO/IEC 17065 as per IEC 61439-1. <br>>>The type tested designs of the switchboards shall be proven design from switchgear manufacturer (OEM)<br>>>Switchboards shall have a short circuit level of minimum of 50 KA withstand. Switchboards shall have Rated Impulse withstand voltage of 12kv<br>>>All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection of IP 42 unless otherwise stated. <br>>>Switchboards shall be validated design for Seismic withstand as per standard IEC60068.<br>>>Switchboards must have mechanical impact IK10 tested<br>>>Switchboards construction shall employ the principle of compartmentalised and metallic segregation for each circuit<br>>>Switchboard panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness, same as that of tested assembly per IEC61439-1 & 2<br>>>Doors with transparent safety glass with aesthetic appeal to avoid all risk of injury.<br>>> ( Approved Makes : Schneider Prisma , ABB MNS , SIEMENS Sivacon)<br>"<br>Incomer-1 - EB<br>"ACB 1000A FP 50KA EDO TYPE MP BASED LSIG<br>PROTECTION with UV- 1 no's"<br>Instruments<br>*6A, C curve SP MCB - 1 set<br>*RYB indication lamp, LED type - 1 set<br>*On, Off, Trip indication lamp, LED type - 1 set<br>*1set 3 phase Digital Multi function meter with RS485 communication port EM6400NG or eql<br>*1000/5A 15VA class 1 resin cast CT - 1 set<br>*REF and standby Earth fault relay - 1set<br>incomer-2&3 - DG<br>MCCB 630A TP 50KA MP BASED OC,SC PROTECTION - 1 NO<br>MCCB 400A TP 50KA MP BASED OC,SC PROTECTION - 1 NO<br>Nuetral contactor 160A & 95A TP AC-3<br>Instruments<br>*6A, C curve SP MCB - 2 set<br>*RYB indication lamp, LED type - 2 set<br>*On, Off, Trip indication lamp, LED type - 2 set<br>*2set 3 phase Digital Multi function meter with RS485 communication port EM6400NG or eql<br>*630/5A 15VA class 1 resin cast CT - 1 set,*400/5A 15VA class 1 resin cast CT - 1 set<br>*standby Earth fault relay - 2set<br>AMF and Synch<br>Synchronisation and Auto Load sharing of 2 DG set using AGC200 series DEIF make controller and accessories with battery charger - 2set<br>AMF using CGC400 series DEIF make controller and accessories with battery charger - 1set<br>Outgoing.<br>*400A, TPN, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no.<br>*315A, TPN, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1no.<br>*160A, TPN, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 2no.<br>*200A, TPN, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 4no.<br>*250A, TPN, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 4no.<br>All the outgoing MCCB's with Spreader and ROH<br>BUSBAR : suitable rating of Aluminium busbar as per type test<br>
GROUND FLOOR & FIRST FLOOR PANEL
od170401/2020_2021 : Fabrication, supply, conveyance, installation Testing and commissioning floor mounting, dust and vermin proof, cubicle type LV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm CRCA sheet as per approved design and requirement 2mm for frame , with front access facility, bus bar chambers with aluminium bus , hinged doors for all switch gear compartments , including providing interconnection between all the switch gears with 6 Sqmm PVC insulated copper conductor cableand earthing the doors using braided copper conductor and providing indication lamps, digital type Multi function meter suitable CTs, danger notice board etc The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. . The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthatic enamel paint over a coat of zinc chromate paint botling the frame to the panel and to the furnished floor using required bolts and nuts making good the dameges colour washing and fixing the following switch gears etc as required. br>Incomer200A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. Instruments2A, C curve SP MCB - 3 nos.RYB indication lamp, LED type - 3 nos.1 No 3 phase Digital Multi function meter to read V, A, F, PF, kW, kWh Acc class 1 and with RS485 communication port.200/5A, 10VA, class 1, resin cast CT - 1 setOutgoing. 125A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL protection -3nos.
UPS PANEL
od170405/2020_201: Fabrication, supply, conveyance, installation Testing and commissioning floor mounting, dust and vermin proof, cubicle type LV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm CRCA sheet as per approved design and requirement 2mm for frame , with front access facility, bus bar chambers with aluminium bus , hinged doors for all switch gear compartments , including providing interconnection between all the switch gears with 6 Sqmm PVC insulated copper conductor cableand earthing the doors using braided copper conductor and providing indication lamps, digital type Multi function meter suitable CTs, danger notice board etc The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. . The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthatic enamel paint over a coat of zinc chromate paint botling the frame to the panel and to the furnished floor using required bolts and nuts making good the dameges colour washing and fixing the following switch gears etc as required. br>. Incomer 200A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. Instruments 2A, C curve SP MCB - 3 nos. RYB indication lamp, LED type - 3 nos. 1 No 3 phase Digital Multi function meter to read V, A, F, PF, kW, kWh Acc class 1 and with RS485 communication port. 320/5A, 10VA, class 1, resin cast CT - 1 set Outgoing.125A, TP+NL, ISOLATOR -2 nos
CSSD&STP PANEL
od170421/2020_2021 : Fabrication, supply, conveyance, installation Testing and commissioning floor mounting, dust and vermin proof, cubicle type LV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm CRCA sheet as per approved design and requirement 2mm for frame , with front access facility, bus bar chambers with aluminium bus , hinged doors for all switch gear compartments and earthing the doors using braided copper conductor and providing indication lamps, digital type Multi function meter suitable CTs, danger notice board etc The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The cubical panel board shall have 9 Nos compartments of size not less than 300 mm x 600 mm and viewing glass for all outgoing compartment doors of suitable size but not less than 100 mm x 100 mmx 3 mm including providing interconnection between all the switch gears with 6 Sqmm PVC insulated copper conductor cable. The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthatic enamel paint over a coat of zinc chromate paint botling the frame to the panel and to the furnished floor using required bolts and nuts making good the dameges colour washing and fixing the following switch gears etc as required. Incomer250A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. Instruments2A, C curve SP MCB - 3 nos. RYB indication lamp, LED type - 3 nos.1 No 3 phase Digital Multi function meter to read V, A, F, PF, kW, kWh Acc class 1 and with RS485 communication port.320/5A, 10VA, class 1, resin cast CT - 1 setOutgoing.100A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL protection - 4 nos. 63A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL protection - 4 nos.
HVAC PANEL
od170401/2020_2021 : Fabrication, supply, conveyance, installation Testing and commissioning floor mounting, dust and vermin proof, cubicle type LV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm CRCA sheet as per approved design and requirement 2mm for frame , with front access facility, bus bar chambers with aluminium bus , hinged doors for all switch gear compartments , including providing interconnection between all the switch gears with 6 Sqmm PVC insulated copper conductor cableand earthing the doors using braided copper conductor and providing indication lamps, digital type Multi function meter suitable CTs, danger notice board etc The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. . The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthatic enamel paint over a coat of zinc chromate paint botling the frame to the panel and to the furnished floor using required bolts and nuts making good the dameges colour washing and fixing the following switch gears etc as required. br>Incomer200A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. Instruments2A, C curve SP MCB - 3 nos.RYB indication lamp, LED type - 3 nos.1 No 3 phase Digital Multi function meter to read V, A, F, PF, kW, kWh Acc class 1 and with RS485 communication port.200/5A, 10VA, class 1, resin cast CT - 1 setOutgoing. 125A, TP+NL, 36kA, MCCB with thermal magnetic release for adjustable OL protection -3nos.
PUMP PANEL
od157816/2020_2021 : Fabrication, supply, conveyance, installation Testing and commissioning floor mounting, dust and vermin proof, cubicle type LV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm CRCA sheet as per approved design and requirement 2mm for frame , with front access facility, bus bar chambers with aluminium bus , hinged doors for all switch gear compartments and earthing the doors using braided copper conductor and providing indication lamps, digital type Multi function meter suitable CTs, danger notice board etc The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthatic enamel paint over a coat of zinc chromate paint botling the frame to the panel and to the furnished floor using required bolts and nuts making good the dameges colour washing and including providing and fixing the following switch gears etc as required.<br>PUMP PANEL<br>Incomer<br>200A, 3P, 36kA, MCCB with Thermal magnetic release for adjustable OL, SC protection - 1 no. <br>Instruments<br>2A, C curve SP MCB - 4 set<br>RYB indication lamp, LED type - 2 set<br>On, Off, Trip indication lamp, LED type - 2 set <br>1 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with RS485 communication port.<br>200/5A 15VA class 1 resin cast CT - 2 set<br>Outgoing.<br>32A TP MPCB ……….5 Nos<br>63A, 3P, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. <br>40A, TP, 36kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. <br>32 A 3P COS……….5 Nos<br>Fully automatic star delta starter suitable for 10 hp pump set ……10 Nos.
90.9.1.1 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.1.2 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
90.9.1.7 : Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.1 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.2 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable devider
90.9.2.8 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.12 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.1 to 3 module mounting box
90.9.2.14 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.8 module mounting box
90.9.2.19 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Reducer 100 x 50 to 50 x 50mm
90.9.2.23 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External tee
1.28.2 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.5 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
K K Associates
AMS Electro Consultants and Contractors Private limited
Quilon Consulting Engineers
Imperial Engineering Company
Bidder Name
Imperial Engineering Company
K K Associates
MOHANS POWER CONTROLS
Quilon Consulting Engineers
AMS Electro Consultants and Contractors Private limited
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_585977.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .