Loading…
Loading…
Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance PANTHALANICKAL PULIYANOOR PO | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹2.2 L
EMD Value
₹5,602
Closing Date
24 Feb 2026, 6:00 pmClosed
Assistant Engineer
Assistant Engineer LID EW Section Pallickathodu G P 686503
Annual Plan-Pallikkathode GP Project No222/26-completion of chirakattukunnunaripara dwss ward 5-General Electrical Work
2026_LSGD_837269_1
96/AE/LIDEW/25-26
Open Tender
Electrical Works
Item Rate
60 days
Pallickathodu
Please refer Tender documents.
8 documents required · 8 mandatory
₹555
₹5,602
26 Feb 2026
17 Feb 2026
26 Feb 2026
17 Feb 2026
24 Feb 2026
17 Feb 2026
17 Feb 2026 - 24 Feb 2026
Chirakkattukunnu DWSS (Approved List of Materials Uploaded in Attachments & is Part of Tender/Agreement Document)
OD468573/2025-2026:Supply Conveyance Installation of borewell pump of EKKI make model -ER61/15 ,7.5hp 15 stage pump of Head Range-92 to 150mtr,Discharge of 225 to 100lpm and 50mm outlet or equivalent spec models.
OD468572/2025-2026:Supply & installation of 7.5HP Motor starter of BCH Brand model CPEYNALN13.2-20A
90.6.6.4:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.6 sq mm
90.12.41.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
OD468560/2025-2026:Supply & Laying HDPE pipes PE 100,12.5Kg,63mm Outer dia
OD468540/2025-2026:Supply & fixing the following Power Capacitors 3 phase delta connected in position and giving connection.
OD468533/2025-2026:Supply and fitting 50 mm flange with bolt and nut duly welded
OD468534/2025-2026:S&I of Pressure meter with acessories and stopper valve, ball valve etc on delivery side of 50 mm GI pipe line as required
OD468535/2025-2026:Supply and Providing 50 mm GI pipe (Medium class) Cutting threading welding and with accessories etc
OD468536/2025-2026:Supply and fitting 50 mm GI Bend on pumping main with flanges welded and nut bolt etc on pumping main.
OD468537/2025-2026:Supply and provide clamp set for pump set
OD468538/2025-2026:Supply and fitting 50 mm KARTAR Sluice valve CI on existing GI pipe with flanges etc
OD468539/2025-2026:Supply and fitting 50M mm Non Return Valve using required bolt and nut and flange etc
OD468542/2025-2026:Supply of Nylone Rope 14MM
OD468543/2025-2026:Supply & installation of hose color (H-TYPE)
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD468580/2025-2026:Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. As required including drilling necessary holes as required.
OD468579/2025-2026:Supply & installation of dust and vermin proof, wall mounting, SINTEX Meter Box of size 650x350x210mm suitable for fixing KSEB meter, fuse units, CT etc., hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment, knock out for cable entry and exit.(GSMB-6535)
OD468576/2025-2026:Supply and providing 63A HRC fuse with fuse holder and giving connection as required
OD468577/2025-2026:Supply and fixing 63A, 415 V, 2 way neutral link mounted on DMC/ SMC base in the existing meter board and giving connections etc.
OD468578/2025-2026:Charges for preparing drawing of the complete electrical installation after completion of the present work and preparing completion report with KSEB service connection application form and submitting to the consumer for availing three phase service connection/load regularization.
OD468581/2025-2026:Supply and providing anchor bolt hook type on wall /parapet for binding KSEB service connection capable as required
5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
stage.html
html • 0.02 MB
finance_1409849.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1409849.xls
BOQ • 0.32 MB
viewsbd.pdf
Tender Documents • 1.63 MB
PA.pdf
Tender Documents • 0.52 MB
Epayment.pdf
Tender Documents • 0.04 MB
IntegrityPact.pdf
Tender Documents • 0.04 MB
FOT.pdf
Tender Documents • 0.52 MB
AFFIDAVIT.pdf
Tender Documents • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .