Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.7 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | ₹29.7 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹34.8 L+₹5.1 L (17.0%)Rejected-Finance HENGRABAI LICHUBAGAN BYE LANE 2 HOUSE NO 2 GUWAHATI 781036 ASSAM | KAMRUP METRO | ASSAM | 781036 | ₹34.8 L+₹5.1 L (17.0%) | L2 | Rejected-Finance Unsuccessful bidder |
| 3 | L3₹37.5 L+₹7.7 L (26.0%)Rejected-Finance WZ 409 0 B 1ST FLOOR PLOT NO 12 JANAK PARK HARI NAGAR NEW DELHI 110064 | NEW DELHI | WEST DELHI | DELHI | 110064 | ₹37.5 L+₹7.7 L (26.0%) | L3 | Rejected-Finance Unsuccessful bidder |
| 4 | L4₹40.3 L+₹10.6 L (35.5%)Rejected-Finance | ₹40.3 L+₹10.6 L (35.5%) | L4 | Rejected-Finance Unsuccessful bidder |
| 5 | L5₹55.7 L+₹25.9 L (87.2%)Rejected-Finance NIL | ₹55.7 L+₹25.9 L (87.2%) | L5 | Rejected-Finance Unsuccessful bidder |
Tender Value
₹41.9 L
EMD Value
₹83,740
Closing Date
22 Oct 2024, 6:00 pmClosed
CWE Tezpur
HQ CWE TEZPUR PO DEKARGAON DIST SONITPUR PIN 784501 (ASSAM)
SPL REPAIR/REPLACEMENT OF BER TRANSFORMERS HELD AT NAA UNDER GE (N) TEZPUR
2024_MES_673554_2
CWE/TEZ(N)/T-27 of 24-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(N) Tezpur
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE(N) Tezpur
₹83,740
Yes
12 Dec 2024
1 Oct 2024
24 Oct 2024
1 Oct 2024
22 Oct 2024
8 Oct 2024
Amount
Supply, install, testing and commissioning of outdoor type ONAN cooled, oil immersed step down transformer of capacity100 KVA copper wound HT/LT 11 KV/433 Volts 3phase,4 wire ,50 Hz, ONAN cooled with 7 position off tap changer (Tapping range +/- 7.5% in step of 2.5% each) with vector grp Dyn-11 all as IS 1180 (Part-I) 2014 with BEE 3 star rating as per latest ammendment complete with forst fill of transformer oil having di-electric strength not less than 60 KV at 2.5 mm air gap and following accessories (a) HV & LV cable box with cable glands (b) Off cicuit tap changer switch (c) Name , rating, and diagram plate-01 no. (d) Earthing Terminals - 02 no. (e) Lifting Lugs - 02 no. (f) Oil level indicator - Flush Type (g) Oil drain valve with plug-01 no (h) Conservator with oil fitting hole-01 no. (i)Thermometer pocket- 01 no. (j) 4" dial type thermometerstem type - 01 no. (k) Air release plug-01 no. (l) Silica gel breather - 01 no.(m) Explosion vent -01 no. (n) U directional rollers -04 no. (o) Buczhole relay Note:- (i) Any left out standard accesssories which are not mentioned above for smooth functioning of The transformer shall be included in the quoted rate without any extra cost (ii) The transformer shall be factory tested by the rep of accepting officer before dispatched. Cost for the same shall be deemed included in the unit quoted rates. (iii) Cost of Foundation for tanformer is included in this rate and should be done as per drawing provided by manufacture of tranformer as per requirement of site. (iv) Dismantling of existing old Transformer from site with disconnection of all HT & LT cables and shted to MES store yard shall be included in this rate (v) All LT/HT side electrical connection with existing line are included in this rate.
Supply, install, testing and commissioning of outdoor type ONAN cooled, oil immersed step down transformer of capacity 250 KVA copper wound HT/LT 11 KV/433 Volts 3phase,4 wire ,50 Hz, ONAN cooled with 7 position off tap changer (Tapping range +/- 7.5% in step of 2.5% each) with vector grp Dyn-11 all as IS 1180 (Part-I) 2014 with BEE 3 star rating as per latest ammendment complete with forst fill of transformer oil having di-electric strength not less than 60 KV at 2.5 mm air gap and following accessories (a) HV & LV cable box with cable glands (b) Off cicuit tap changer switch (c) Name , rating, and diagram plate-01 no. (d) Earthing Terminals - 02 no. (e) Lifting Lugs - 02 no. (f) Oil level indicator - Flush Type (g) Oil drain valve with plug-01 no (h) Conservator with oil fitting hole-01 no. (i)Thermometer pocket- 01 no. (j) 4" dial type thermometerstem type - 01 no. (k) Air release plug-01 no. (l) Silica gel breather - 01 no. (m) Explosion vent -01 no. (n) U directional rollers -04 no.(o) Buczhole relay Note:- (i) Any left out standard accesssories which are not mentioned above for smooth functioning of The transformer shall be included in the quoted rate without any extra cost (ii) The transformer shall be factory tested by the rep of accepting officer before dispatched. Cost for the same shall be deemed included in the unit quoted rates. (iii) Cost of Foundation for tanformer is included in this rate and should be done as per drawing provided by manufacture of tranformer as per requirement of site. (iv) Dismantling of existing old Transformer from site with disconnection of all HT & LT cables and shted to MES store yard shall be included in this rate (v) All LT/HT side electrical connection with existing line are included in this rate.
M&L for Earthing complete with Copper plate electrode of size 600x600x3.15 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 2.4 meter below normal ground level connected to Copper strip of size 32x6 mm as earth lead by means of nuts, bolts, check nuts, washers of tinned brass, protected by galvanized iron pipe 40mm bore (Medium grade) for protection of copper strip all as directed including earth test point of gun metal or phoshorus bronze size of 75x75x25 mm drilled and screwed including 3 nos 8mm dia 25mm long hex and cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering,including supplying and laying of charcoal or coke and salt in alternate layers and filling earth pit with fresh vegetable soil below GI plate and above upto ground level as required and necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I of 2009 including testing on completion all complete as specified and directed.
M&L for Earthing complete with GI plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 2.4 meter below normal ground level connected to Galvanised iron strip of size 32x6 mm as earth lead by means of nuts, bolts, check nuts, washers of tinned brass, protected by galvanized iron pipe 40mm bore (Medium grade) for protection of GI strip all as directed including earth test point of gun metal or phoshorus bronze size of 75x75x25 mm drilled and screwed including 3 nos 8mm dia 25mm long hex and cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering,including supply and laying of charcoal or coke and salt in alternate layers and filling earth pit with fresh vegetable soil below GI plate and above upto ground level as required and necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I of 2009 including testing on completion all complete as specified and directed.
NOTES: 1. The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum. 2. The rates for RCC/PCC shall deemed to include the cost of formwork, shuttering etc., required for complete and proper execution of the item. Refer Schedule "A" notes for details.
S and B Electricals (BID ID -3137943)
Flint India (BID ID -3139030)
M/S L N ENTERPRISE (BID ID -3139543)
M/S N S CONSTRUCTION (BID ID -3147272)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3140269)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .