Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.8 LAccepted-Finance G 1 1154A MANSAROVER PARK SHAHDARA DELHI DELHI 110032 | SHAHDARA | DELHI | 110032 | L1 | Accepted-Finance Selected | |
| 2 | L2₹49.7 L+₹10.8 L (27.9%)Accepted-Finance NONE | L2 | Accepted-Finance Selected |
Tender Value
₹53.9 L
EMD Value
₹1.1 L
Closing Date
6 Mar 2026, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer (E)
O/o EE(E) PWD EMD M-351, R.No.185, Old Sectt Delhi
RMO E and M Services at Sewa Kutir, Kingsway Camp, Delhi. (SH- Replacement of Old defective feeder Panels with their accessories and cable work).
2026_PWD_287814_1
50/2025-26/EMD M-351/EE(E)(Revised)
Open Tender
Miscellaneous Services
Percentage
60 days
Sewa Kutir
Please refer Tender documents.
9 documents required · 9 mandatory
₹0
₹1.1 L
6 Mar 2026
27 Feb 2026
6 Mar 2026
27 Feb 2026
6 Mar 2026
27 Feb 2026
Supplying, installation, testing & commissioning of CPRI approved modular type polycarbonate thermoplastic floor mounted electrical panels of size 2300X1735X600 mm complete with 400 A Copper Bus bar suitable for following incomer and outgoing capacity alongwith CC foundation of 1:3:6 (1 Cement : 3 Coarse : 6 graded stone) aggregate 20mm (NS) (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick with necessary nuts & bolts or grouting into the foundation for fixing the panel, The enclosure shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anticorrosive, IP65, glow wire test for 960 deg. C, The gasket material shall be Polyurethane, while the gasket shall be internally embedded. The manufacturer of board/ panel shall submit a copy of CPRI test report, Degree of ingress protection IP-65 in accordance with IEC 60529, a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1 and IEC 61439-2 for power switchgear and control gear assembly, routine test certificate from manufacturer/ principal company in accordance with IEC 60439-1 (mainly consisting of Degree of protection of system, Temperature Rise Limit, Dielectric properties, Short Circuit withstand strength, Effectiveness of protective circuit, Clearance and creepage distance, Mechanical operation Etc.) for better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-1, DIN VDE 0304 Part3, UL Subject 94 for Flammability V-2, It should be tested at glow wire test for 960 Deg, C. The impact stregth of polycarbonate enclosure/ Boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. The MCB/RCCB switching operations/ accessing the MCB duly should be preferably by opening of a window flap. Panel should have consisted of dew guard which is a passive solution for mitigation of condensation i/c dismentling of old existing panel and disconnection the existing cables and reconnection in this panel i/c credit for old defective panel etc complete as per attached drawing etc as required. (Note:- The board manufacturer must submit the copy of type test reports for polycarbonate Thermoplastic Board)
Incomer-
a) 400 Amps, 36KA 4 Pole Microprocessor type MCCB with Ics=100%Icu with Microprocessor based releases for O/L, S/C & E/F protection - 1 Set
Metering-
a) Digital Voltmeter complete with all required accessories- 1 Set
b) Digital Ammeter complete with all required accessories- 1 Set
c) RYB LED Indicating lamp with 2 A control MCBs- 1 Set
Outgoing-
a) 250 Amps, 36KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories - 2 No.
b) 125 Amps, 25KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories -6 Nos.
c) 63 Amps, DP 10KA MCB - 3 Nos
d) 40 Amps, DP 10KA MCB - 2 Nos
e) Terminal Blocks as required - 1 Lot
Supplying, installation, testing & commissioning of CPRI approved modular type polycarbonate thermoplastic floor mounted electrical panels of size 1100X985X620 mm complete with 250 A Copper Bus bar suitable for following incomer and outgoing capacity alongwith CC foundation of 1:3:6 (1 Cement : 3 Coarse : 6 graded stone) aggregate 20mm (NS) (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick with necessary nuts & bolts or grouting into the foundation for fixing the panel, The enclosure shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anticorrosive, IP65, glow wire test for 960 deg. C, The gasket material shall be Polyurethane, while the gasket shall be internally embedded. The manufacturer of board/ panel shall submit a copy of CPRI test report, Degree of ingress protection IP-65 in accordance with IEC 60529, a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1 and IEC 61439-2 for power switchgear and control gear assembly, routine test certificate from manufacturer/ principal company in accordance with IEC 60439-1 (mainly consisting of Degree of protection of system, Temperature Rise Limit, Dielectric properties, Short Circuit withstand strength, Effectiveness of protective circuit, Clearance and creepage distance, Mechanical operation Etc.) for better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-1, DIN VDE 0304 Part3, UL Subject 94 for Flammability V-2, It should be tested at glow wire test for 960 Deg, C. The impact stregth of polycarbonate enclosure/ Boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. The MCB/RCCB switching operations/ accessing the MCB duly should be preferably by opening of a window flap. Panel should have consisted of dew guard which is a passive solution for mitigation of condensation i/c dismentling of old existing panel and disconnection the existing cables and reconnection in this panel i/c credit for old defective panel etc complete as per attached drawing etc as required. (Note:- The board manufacturer must submit the copy of type test reports for polycarbonate Thermoplastic Board)
Incomer-
a) 125 Amps, 25KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories - 1 Set
Metering-
a) Digital Voltmeter complete with all required accessories- 1 Set
b) Digital Ammeter complete with all required accessories- 1 Set
c) RYB LED Indicating lamp with 2 A control MCBs- 1 Set
Outgoing-
a) 100 Amps, 25KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories - 1 No.
b) 63 Amps, DP 10KA MCB - 1 Nos
c) DOL Starter 5 HP with all required accessories - 1 Set
d) Terminal Blocks as required - 1 Lot
Supplying, installation, testing & commissioning of CPRI approved modular type polycarbonate thermoplastic floor mounted electrical panels of size 800X1285X620 mm complete with 250 A Copper Bus bar suitable for following incomer and outgoing capacity alongwith CC foundation of 1:3:6 (1 Cement : 3 Coarse : 6 graded stone) aggregate 20mm (NS) (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick with necessary nuts & bolts or grouting into the foundation for fixing the panel, The enclosure shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anticorrosive, IP65, glow wire test for 960 deg. C, The gasket material shall be Polyurethane, while the gasket shall be internally embedded. The manufacturer of board/ panel shall submit a copy of CPRI test report, Degree of ingress protection IP-65 in accordance with IEC 60529, a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1 and IEC 61439-2 for power switchgear and control gear assembly, routine test certificate from manufacturer/ principal company in accordance with IEC 60439-1 (mainly consisting of Degree of protection of system, Temperature Rise Limit, Dielectric properties, Short Circuit withstand strength, Effectiveness of protective circuit, Clearance and creepage distance, Mechanical operation Etc.) for better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-1, DIN VDE 0304 Part3, UL Subject 94 for Flammability V-2, It should be tested at glow wire test for 960 Deg, C. The impact stregth of polycarbonate enclosure/ Boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. The MCB/RCCB switching operations/ accessing the MCB duly should be preferably by opening of a window flap. Panel should have consisted of dew guard which is a passive solution for mitigation of condensation i/c dismentling of old existing panel and disconnection the existing cables and reconnection in this panel i/c credit for old defective panel etc complete as per attached drawing etc as required. (Note:- The board manufacturer must submit the copy of type test reports for polycarbonate Thermoplastic Board)
Incomer-
a) 125 Amps, 25KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories - 1 Set
Metering-
a) Digital Voltmeter complete with all required accessories- 1 Set
b) Digital Ammeter complete with all required accessories- 1 Set
c) RYB LED Indicating lamp with 2 A control MCBs- 1 Set
Outgoing-
a) 110 Amps, TP Power Contactor - 1 No.
b) Digital Timer - 1 No.
c) 16 Amps, DP 10KA MCB - 8 Nos
d) Terminal Blocks as required - 1 Lot
Supplying,installation,testing & commissioning of CPRI approved modular type polycarbonate thermoplastic floor mounted electrical panels of size 2000X1735X600 mm complete with 400 A Copper Bus bar suitable for following incomer and outgoing capacity alongwith CC foundation of 1:3:6 (1 Cement : 3 Coarse : 6 graded stone) aggregate 20mm (NS) (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick with necessary nuts & bolts or grouting into the foundation for fixing the panel, The enclosure shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anticorrosive, IP65, glow wire test for 960 deg. C, The gasket material shall be Polyurethane, while the gasket shall be internally embedded. The manufacturer of board/ panel shall submit a copy of CPRI test report, Degree of ingress protection IP-65 in accordance with IEC 60529, a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1 and IEC 61439-2 for power switchgear and control gear assembly, routine test certificate from manufacturer/ principal company in accordance with IEC 60439-1 (mainly consisting of Degree of protection of system, Temperature Rise Limit, Dielectric properties, Short Circuit withstand strength, Effectiveness of protective circuit, Clearance and creepage distance, Mechanical operation Etc.) for better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-1, DIN VDE 0304 Part3, UL Subject 94 for Flammability V-2, It should be tested at glow wire test for 960 Deg, C. The impact stregth of polycarbonate enclosure/ Boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. The MCB/RCCB switching operations/ accessing the MCB duly should be preferably by opening of a window flap. Panel should have consisted of dew guard which is a passive solution for mitigation of condensation i/c dismentling of old existing panel and disconnection the existing cables and reconnection in this panel i/c credit for old defective panel etc complete as per attached drawing etc as required. (Note:- The board manufacturer must submit the copy of type test reports for polycarbonate Thermoplastic Board)
Incomer-
a) 400 Amps, 36KA 4 Pole Microprocessor type MCCB with Ics=100%Icu with Microprocessor based releases for O/L, S/C & E/F protection - 1 Set
Metering-
a) Digital Voltmeter complete with all required accessories- 1 Set
b) Digital Ammeter complete with all required accessories- 1 Set
c) RYB LED Indicating lamp with 2 A control MCBs- 1 Set
Outgoing-
a) 125 Amps, 25KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories -8 Nos.
b) Terminal Blocks as required - 1 Lot
Supplying,installation,testing & commissioning of CPRI approved modular type polycarbonate thermoplastic floor mounted electrical panels of size 3050X1985X750 mm complete with 630 A Copper Bus bar suitable for following incomer and outgoing capacity alongwith CC foundation of 1:3:6 (1 Cement : 3 Coarse : 6 graded stone) aggregate 20mm (NS) (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick with necessary nuts & bolts or grouting into the foundation for fixing the panel, The enclosure shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anticorrosive, IP65, glow wire test for 960 deg. C, The gasket material shall be Polyurethane, while the gasket shall be internally embedded. The manufacturer of board/ panel shall submit a copy of CPRI test report, Degree of ingress protection IP-65 in accordance with IEC 60529, a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1 and IEC 61439-2 for power switchgear and control gear assembly, routine test certificate from manufacturer/ principal company in accordance with IEC 60439-1 (mainly consisting of Degree of protection of system, Temperature Rise Limit, Dielectric properties, Short Circuit withstand strength, Effectiveness of protective circuit, Clearance and creepage distance, Mechanical operation Etc.) for better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-1, DIN VDE 0304 Part3, UL Subject 94 for Flammability V-2, It should be tested at glow wire test for 960 Deg, C. The impact stregth of polycarbonate enclosure/ Boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. The MCB/RCCB switching operations/ accessing the MCB duly should be preferably by opening of a window flap. Panel should have consisted of dew guard which is a passive solution for mitigation of condensation i/c dismentling of old existing panel and disconnection the existing cables and reconnection in this panel i/c credit for old defective panel etc complete as per attached drawing etc as required. (Note:- The board manufacturer must submit the copy of type test reports for polycarbonate Thermoplastic Board)
Incomer-
a) 630 Amps, 36KA 4 Pole Microprocessor type MCCB with Ics=100%Icu with Microprocessor based releases for O/L, S/C & E/F protection - 1 Set
Metering-
a) Digital Voltmeter complete with all required accessories- 1 Set
b) Digital Ammeter complete with all required accessories- 1 Set
c) RYB LED Indicating lamp with 2 A control MCBs- 1 Set
Outgoing-
a) 250 Amps, 35KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories -8 Nos.
b) Terminal Blocks as required - 1 Lot
Supplying,installation,testing & commissioning of CPRI approved modular type polycarbonate thermoplastic floor mounted electrical panels of size 1100X1585X620 mm complete with 250 A Copper Bus bar suitable for following incomer and outgoing capacity alongwith CC foundation of 1:3:6 (1 Cement : 3 Coarse : 6 graded stone) aggregate 20mm (NS) (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick with necessary nuts & bolts or grouting into the foundation for fixing the panel, The enclosure shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti-acid & anticorrosive, IP65, glow wire test for 960 deg. C, The gasket material shall be Polyurethane, while the gasket shall be internally embedded. The manufacturer of board/ panel shall submit a copy of CPRI test report, Degree of ingress protection IP-65 in accordance with IEC 60529, a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1 and IEC 61439-2 for power switchgear and control gear assembly, routine test certificate from manufacturer/ principal company in accordance with IEC 60439-1 (mainly consisting of Degree of protection of system, Temperature Rise Limit, Dielectric properties, Short Circuit withstand strength, Effectiveness of protective circuit, Clearance and creepage distance, Mechanical operation Etc.) for better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-1, DIN VDE 0304 Part3, UL Subject 94 for Flammability V-2, It should be tested at glow wire test for 960 Deg, C.
The impact stregth of polycarbonate enclosure/ Boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. The MCB/RCCB switching operations/ accessing the MCB duly should be preferably by opening of a window flap. Panel should have consisted of dew guard which is a passive solution for mitigation of condensation i/c dismantling of old existing panel and disconnection the existing cables and reconnection in this panel i/c credit for old defective panel etc complete as per attached drawing etc as required. (Note:- The board manufacturer must submit the copy of type test reports for polycarbonate Thermoplastic Board)
Incomer-
a) 250 Amps, 35KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories -1 Nos.
Metering-
a) Digital Voltmeter complete with all required accessories- 1 Set
b) Digital Ammeter complete with all required accessories- 1 Set
c) RYB LED Indicating lamp with 2 A control MCBs- 1 Set
Outgoing-
a) 100 Amps, 25KA 4 Pole Thermal Magnetic Release type MCCB with Ics=100%Icu for O/L, S/C protection complete with required accessories -3 Nos.
b) Terminal Blocks as required - 1 Lot
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
2 X 10 sq. mm (19mm)
2 X 16 sq. mm (22mm)
3½ X 25 sq. mm (28mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 70 sq. mm (38mm)
3½ X 95 sq. mm (45mm)
3½ X 120 sq. mm (45mm)
3½ X 150 sq. mm (50mm)
3½ X 185 sq. mm (57mm)
3½ X 240 sq. mm (62mm)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.08 MB
BOQ_381513.xls
BOQ • 0.46 MB
50SewaKutirFeederPanelRevised.pdf
Tender Documents • 2.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .