Chief Engineer, TTD, Tirupati
Room No.128, Admn Building, Tirupati
Shifting, Installation, Testing and Commissioning of packaged AC units from SVIMS Hospital to Central godown building for medical stores in SVIMS Hospital, Tirupati
945117
92/DE(Elec)-II/TTD/TPT/2026-27
OPEN - NCB
Electrical Works
CHITTOOR
6 documents required · 6 mandatory
₹484
₹34,200
10 Jun 2026
10 Jun 2026
10 Jun 2026
Supply, installation, testing& commissioning of GSS Ducting with required angle flanges & installation materials such as heavy duty supports by anchor fasteners etc as required as per IS 655 /SMACNA Standards. Makes:TATA/Jindal
Supply &Fixing of 13mm Duct Thermal Insulation applied outside of the duct work with All. backed Closed cell nitrile/ Cross linked foam duly fixed with adhesive and tapes.
Supply & Fixing of 10 - 15mm thick Duct Acoustic Insulation applied inside of the duct work with All. backed Open cell nitrile duly fixed with adhesive and tapes
Supply, Installation, Testing and commissioning of extruded Aluminum powder coated grills/ diffusers for supply with removable core type with collar damper
Supply, Erection and Testing of GI Opposed blade Volume control dampers made out of 18G frame and 20G blades
Supply, installation and testing of Canvas connection for the Treated Fresh Air units to the duct
Supply, installation and testing of Refrigerant Piping consisting of copper tubes of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings, Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site. Makes:Totaline / Mandav / Mexico
The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations
Supply, installation, and testing of UPVC Drain Piping with 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings (including enlarger, bends, T-Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap.
Supply of ……...ISI marked, PVC insulated and sheathed FRLS/FRLS-H round copper cable for voltage up to 1100V as per IS 694/1990. Makes: Finolex / RR kabel / Havells/ Finecab /KEI/Polycab/ Gloster/ Goldmedal/GM// Fortune Arrt/Anchor /Million
3 core, 1.5 Sq mm
3 core, 2.5 Sq mm
Supply and Transportation of XLPE/PVC insulated & PVC sheathed armoured cables of 1.1 KV grade with copper conductor as per IS 7098 Part-I -1988 etc., complete. Make: Torrent / Universal / Unicab / Havells / KEI /Polycab/Gloster/Orbit/ Paragon/RR Kabel /RPG /Rhino /Pawancab/AKG/LS cable/ Polywires
Supply and Fixing of ISI Mark 25mm outer dia medium grade (1.80mm thickness) with IS:9537 part -3 P.V.C. pipe with all accessories fixing on chromium plated metallic base saddles for surface wiring on Brick / stone walls, RCC roofings, Trusses, channels including all labour charges etc., complete. (If PVC Pipes are fixed on Trusses / Channels with MS Clamps, the rate for MS Clamps will be paid Separately) Makes: Sudhakar / Finolex / Polycab / Kumar / AKG / Indian-tubes / GM / Anchor / Nandi / Polyline / Gold Medal
Additional Refrigerant R407c gas
Lifting, shifting, positioning, Installation and testing of the ODUs including all accessories with Vibration Isolators / Rubber pads for ODUs etc., complete
6 to 8 HP / 7.5 TR
Lifting Shifting, Positioning, Installation Testing and commissioning of the following indoor units with including all required accessories etc complete.,
Supply, transportation & installation of following sizes of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees, cross members and other accessories as required and duly suspended from the ceiling / Wall with suspenders etc., complete. NB: Add 30% Extra for perforated cable tray with cover)
300mm x 50mm x 1.6mm
(Rupees Thirteen Lakhs Sixty Six Thousand Six Hundred Fifty and Paise Forty Two only)