Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.0 CrAccepted-AOC | ₹28.0 Cr | L1 | Accepted-AOC being lowest |
| 2 | L2₹28.9 CrRejected-Finance | ₹28.9 Cr | L2 | Rejected-Finance Not lowest |
| 3 | L3₹31.0 CrRejected-Finance | ₹31.0 Cr | L3 | Rejected-Finance Not lowest |
| 4 | L4₹31.4 CrRejected-Finance STREET NO 11 SECTOR NO 04 TILAK NAGAR SAGAR ROAD BIKANER RAJASTHAN 334001 | BIKANER | RAJASTHAN | 334001 | ₹31.4 Cr | L4 | Rejected-Finance Not lowest |
| 5 | L5₹36.7 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹36.7 Cr | L5 | Rejected-Finance Not lowest |
Tender Value
₹34.5 Cr
EMD Value
₹15 L
Closing Date
17 May 2022, 6:00 pmClosed
CE AF GANDHINAGAR
MES AF GANDHINAGAR LEKAWADA PATIA CHILODA 382042
PROVISION OF EXTERNAL SERVICES FOR AMS AT AF STN PHALODI
2022_MES_506115_1
80310
Open Tender
Civil Works
730 days
GE AF PHALODI
AS PER NIT
8 documents required · 8 mandatory
₹3,000
GE AF PHALODI
₹15 L
Yes
2 Jul 2022
5 Feb 2022
18 May 2022
5 Feb 2022
17 May 2022
25 Apr 2022
8 Feb 2022 - 15 Feb 2022
Amount
NOTE: Schedule ‘A’ Part I to XIII are under Ser No. 1.00 to 14.00 are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lump sum price worked out for Building / Structures as listed in Sch `A’ Part I.
Lump sum price worked out for Excavation & Earthwork as listed in Sch `A’ Part II
Lump sum price worked out for Internal Water Supply as listed in Sch `A’ Part III
Lump sum price worked out for Internal Electrification as listed in Sch `A’ Part IV
Lump sum price worked out for Road/Path/Culvert/Hardstanding as listed in Sch `A’ Part V
Lump sum price worked out for Sewage Disposal as listed in Sch `A’ Part VI
Lump sum price worked out for Area Drainage as listed in Sch `A’ Part VII
Lump sum price worked out for Security Fencing and Gate as listed in Sch `A’ Part VIII
Lump sum price worked out for Retaining Wall as listed in Sch `A’ Part IX
Lump sum price worked out for External Water Supply listed in Sch `A’ Part X
Lump sum price worked out for External Electrification listed in Sch `A’ Part XI
Lump sum price worked out for Lightening Protectionlisted in Sch `A’ Part XII
Lump sum price worked out for Air Conditioning & Refrigeration as listed in Sch `A’ Part XIII
Provisional Sum for WATER FILLING POINT (i) Contractor has to quote rate/ amount above/ below for Rs 30,000.00 for this scope. The relative percentage above/ below will be derived for the pricing purpose from quoted amount.
Supply and fix LED wall mounted bracket light fitting floret wall light fixture with plastic body suitable for retrofit LED bulb / lamp (holder B22) 10 watt, polycarbonate white opal diffuser for glare free light, complete all as specified and directed.
Supply and fix High beam revolving search light LED 300 W 700 Mtr focus range, High intensity LED, Energy saving long rage , IP-66, High lumen output>140 lm/w, PF>.95, CCT 5000K-6500K, CRI>70, optical grade PMMA/PC lensrelator efficiency >95%, multiple circuit to avoid complete rum down, narrow beam 7 degree, die cast LM6 body with air fins contant current, average lux (in 500mm circle) at 10 meter away 2500-6000, working volatge 100v-300v, protection from short circuit, over load, low/high volt, working temp -20 degree C to + 60 degree C with CS stand manually operated for suitable for mounting of search light on watch tower , stand made out of Steel & suitable for manual ratation of light on the horizontal(more than 360 degree)and vertically(more than 45 degree) with provision of both locking arrengement at desired position complete all as specified and directed. Make Kalin cat no CS-LRFLL25-PC30 or equivenlent in philips/Bajaj
Supply and fix distribution board made out of sheet metal powder coated, factory made, enclousure double door type TPN 4way vertical type with 200 (Amps rated copper bus bar, neutral bar, earth bar, TP 43 protection including provision of housing of incomer MCCB 63 Amps, triple pole and neutral, 415V, 16 KA breaking capacity fixing of DB flush to wall surface complete all as specified and directed. Note: MCB & MCCB will be measured and paid seperatly.
Supply and fix flame proof exhaust fan of size 305 mm (12'') sweep 240 V 50 Hz ,1440 RPM single phase heavy duty complete with louver shutter and flame proof wire from ceiling rose to exhaust fan, including taking down old fan and deposited in Store yard of AGE E&M complete all as specified and directed.
Supply and fix flame proof and weather proof industrial type DBs with various combination of incoming and outgoing MCB suitable for and including (a) 01 no. MCB SPN 16 Amps, C type (incoming) (b) 1 no. MCB SP 10 Amps C type includin necessary connection complete all as spedfied and directed. Make: Sudhir Cat No. MCDB/186 or eqivalent make mentioned in appendix 'B'.
Material and labour for Wet Mix Macadam (WMM) 150 mm thick (compacted thickness) in two layers of 75 mm each with coarse aggregate of specification grade as per MORTH spread rolled and consolidated to required gradient and camber complete using mechanical paver/grader and tandem vibratory rollerd/earth compactor of capacity exc 8 tonne and n.exc 15 tonne at OMC to achieve the min 98% density of MOD determined using modified density determination method as per IS Code on prepared subgrade complete all as specified and directed.
Supply and fix solar delineator 1.00 m height complete all as specified and directed.
Supply and fix concertina coil 700 mm dia for fixing of U top of fencing complete all as specified and directed.
Supply install testing and commissioning of diesel Engine driven generating set 62.5 KVA capacity, 3 phase, 4 wire, 440 V, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integrated acoustic enclosures having salient features modular bolted construction with fabrication on imported CNC turrert punch machines, Nine tank treatment process with pure polyester based powder coating to ensure long life in all weather conditions and for outdoor application/installation. Integrated design thereby facilitating/easy handling installation and shifting of the eqpt at site. The design of integrated acoustic enclosure should be of type approved by National physical laboratory as per central pollution control board (CPCB) latest norms/regulation with fuel tank, battery and standard accessories including cost of PCC (1:2:4) type B-1 foundation for (acoustic enclosures foundation Height shall be 800 mm out of which 500 mm shall be above ground level) as recommended by manufacturer , Vibration pad sand cushioning around PCC foundation etc all and Tools and spares as provided by manufacturer all as specified and as directed with the following specifications :-.
(A)ENGINE : Water cooled with radiator diesel Engine (confirming to IS : 10001/10002) of 1500 RPM capacity to match the 62.5 KVA alternator under NTP conditions with provision of 10% overload for 1 hour in every 12 hours running conforming to IS 6514/ IS 10001 / 10002 the Engine shall consist of the following :- i) ) Fly wheel ii) Flexible coupling with guard bolts and nuts etc iii) Air cleaner heavy duty dry type (iv) Radiator with guard and water pump engine mounted v) Dynamo of suitable capacity. vi) Air cleaner heavy duty dry. vii) Fuel injection pump. viii) Radiator fan (Blower type) with guard. (ix) Electronic/ A1 class governor. (x) Fuel filter (Mounted). xi) Lubricating oil filter (mounted). (xii) 12V self regulating alternator belt driven by engine. (xiii) Exhaust silencer heavy duty residential type xiv) Corrosion resistor / scale inhibitor. (xv) Starter 12 V DC. xvi) Lubricating oil cooler. xvii) Lubricating oil pump (Gear type). (xviii) Turbo Charger xix) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminum sheet.
xx) Instrument panel complete with the following:- (a) Auto manual starting switch with key. (b) Lubricating oil temperature gauge. (c) Lubricating oil pressure gauge. (d) Water temperature gauge. (e) Battery charging ammeter. (f) Battery charging indicating lamp. (g) Hour meter with RPM indicator. (h) Safety control against high temperature of water. (i) Safety control against high temperature of water. (j) Safety control against low lubricating oil pressure. (k) Over speed stop with double driven adaptor. (l) Over load
(B) BRUSH LESS ALTERNATOR (i) Alternator coupled to Engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be conforming to BS-2613 or relevant IS-13364 (ii) Type :- Self excited self regulated with automatic voltage regulator. (iii) Rating :- 62.5 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition 3 (iv) Speed :- 1500 RPM (v) System :- 415 Volts +/- 2.5% AC 3 Phase 4 wire 50 Hz. (vi) Connection :- 4 wire star connected. (vii) Enclosure :- Screen protected dip proof. (viii) Ventilation :- Self ventilated (ix) Insulation :- Insulation Class H
D) AMF Panel cum Protection :- Separate Outdoor type AMF panel for automatic ON during power failure and off while power is on with adjustable time delay, panel totally enclosed fabricated out of CRCA sheet 3.15mm thick , over an angle iron frame made out of 50 x 50 x 6 mm angle with removable side cover hinged front panel and rear panel of easy accessibility complete with internal wiring of suitable size copper conductor cable and cable glands for external connection and comprising of following :- (i) AMF relay &power contactors of suitable rating for automatic starting on mains failure- 1 set (ii) Digital type Frequency meter -1Nos (iii) RPM meter -1Nos (iv) Under Voltage relay-1No (v) Over voltage relay- 1No (vi) Reverse power relay- 1NO (vii) Trivector meter-1No (viii) Energy analyzer with CT- 1No (ix) Earth fault protection-1Nos (x) Under/Over frequency relay- 1No (xi) HRC type instruments fuses (xii) Copper bus bar of suitable size
(E) FUEL TANK :- One No of sheet steel 14 SWG and capacity to hold diesel sufficient for running 16 hrs running at full load including necessary piping. (i) Level indicator on fuel tank (ii) Drain plug (iii) MS class 'C' piping for inlet from pump to tank of engine (iv) Fuel strainer (v) Air vent.
(F) BATTERY As recommended by manufacturers (G) Acoustic enclosure- Acoustic Enclosure suitable for 62.5 KVA DG set as under. i) Fabricated out of CRCA sheet of suitable thickness not less than 1.6mm. Polyester based powder coated internally and externally with lockable type door handle. All nuts and handles shall be zinc coated. ii) The doors are gasket with EPDM gaskets. The construction should be such that it prevent entry of rain water splashing in to enclosure and allows free and quick flow of rain water to the ground in the event of heavy rain, iii) Sound proofing with high quality rock wool/mineral wool confirming to IS 8183 of density at 96 Kg /M3 covered with fiber glass cloth and perforated powder coats sheet specially designed alienators (Sound controller) at air entry and exit of the container noise level shall be not exceed 75 Db at 1 meter distance as per CPCB norms. iv) Adequate ventilation to meet air requirement for combustion and heat removal with provn of a blower. v) Emergency stop push button outside the container. vi) Provn of light inside the canopy providing of FTL fitting 1x20 watt with wiring and control switch. vii) The canopy should be provided with height enclosure temperature safety device.
Supply install testing and commissioning of diesel Engine driven generating set 320 KVA capacity, 3 phase, 4 wire, 440 V, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integrated acoustic enclosures having salient features modular bolted construction with fabrication on imported CNC turrert punch machines, Nine tank treatment process with pure polyester based powder coating to ensure long life in all weather conditions and for outdoor application/ installation. Integrated design thereby facilitating /easy handling installation and shifting of the eqpt at site. The design of integrated acoustic enclosure should be of type approved by National physical laboratory as per central pollution control board (CPCB) latest norms/regulation with fuel tank, battery and standard accessories including cost of PCC (1:2:4) type B-1 foundation for (acoustic enclosures foundation Height shall be 800 mm out of which 500 mm shall be above ground level) as recommended by manufacturer , Vibration pad sand cushioning around PCC foundation etc all and Tools and spares as provided by manufacturer all as specified and as directed with the following specifications :-.
(A)ENGINE : Water cooled with radiator diesel Engine (confirming to IS : 10001/10002) of 1500 RPM capacity to match the 320 KVA alternator under NTP conditions with provision of 10% overload for 1 hour in every 12 hours running conforming to IS 6514/ IS 10001 / 10002 the Engine shall consist of the following :- i) ) Fly wheel ii) Flexible coupling with guard bolts and nuts etc iii) Air cleaner heavy duty dry type (iv) Radiator with guard and water pump engine mounted v) Dynamo of suitable capacity. vi) Air cleaner heavy duty dry. vii) Fuel injection pump. viii) Radiator fan (Blower type) with guard. (ix) Electronic/ A1 class governor. (x) Fuel filter (Mounted). xi) Lubricating oil filter (mounted). (xii) 12V self regulating alternator belt driven by engine. (xiii) Exhaust silencer heavy duty residential type xiv) Corrosion resistor / scale inhibitor. (xv) Starter 12 V DC. xvi) Lubricating oil cooler. xvii) Lubricating oil pump (Gear type). (xviii) Turbo Charger xix) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminum sheet.
xx) Instrument panel complete with the following:- (a) Auto manual starting switch with key. (b) Lubricating oil temperature gauge. (c) Lubricating oil pressure gauge. (d) Water temperature gauge. (e) Battery charging ammeter. (f) Battery charging indicating lamp. (g) Hour meter with RPM indicator. (h) Safety control against high temperature of water. (i) Safety control against high temperature of water. (j) Safety control against low lubricating oil pressure. (k) Over speed stop with double driven adaptor. (l) Over load
(B) BRUSH LESS ALTERNATOR (i) Alternator coupled to Engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be conforming to BS-2613 or relevant IS-13364 (ii) Type :- Self excited self regulated with automatic voltage regulator. (iii) Rating :- 320 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition 3 (iv) Speed :- 1500 RPM (v) System :- 415 Volts +/- 2.5% AC 3 Phase 4 wire 50 Hz. (vi) Connection :- 4 wire star connected. (vii) Enclosure :- Screen protected dip proof. (viii) Ventilation :- Self ventilated (ix) Insulation :- Insulation Class H (x) Over load withstand capacity :- (+) 10%
(D) AMF Panel cum Protection :- Separate Outdoor type AMF panel for automatic ON during power failure and off while power is on with adjustable time delay, panel totally enclosed fabricated out of CRCA sheet 3.25mm thick , over an angle iron frame made out of 50 x 50 x 6 mm angle with removable side cover hinged front panel and rear panel of easy accessibility complete with internal wiring of suitable size copper conductor cable and cable glands for external connection and comprising of following :- (i) AMF relay &power contactors of suitable rating for automatic starting on mains failure- 1 set (ii) Digital type Frequency meter -1Nos (iii) RPM meter -1Nos (iv) Under Voltage relay -1No (v) Over voltage relay- 1No (vi) Reverse power relay- 1NO (vii) Trivector meter-1No (viii) Energy analyzer with CT- 1No (ix) Earth fault protection-1Nos (x) Under/Over frequency relay- 1No (xi) HRC type instruments fuses (xii) Copper bus bar of suitable size
(E) FUEL TANK :- One No of sheet steel 14 SWG and capacity to hold diesel sufficient for running 16 hrs running at full load including necessary piping. (i) Level indicator on fuel tank (ii) Drain plug (iii) MS class 'C' piping for inlet from pump to tank of engine (iv) Fuel strainer (v) Air vent.
(F) BATTERY As recommended by manufacturers (G) Acoustic enclosure- Acoustic Enclosure suitable for 1010 KVA DG set as under. i) Fabricated out of CRCA sheet of suitable thickness not less than 1.6mm. Polyester based powder coated internally and externally with lockable type door handle. All nuts and handles shall be zinc coated. ii) The doors are gasket with EPDM gaskets. The construction should be such that it prevent entry of rain water splashing in to enclosure and allows free and quick flow of rain water to the ground in the event of heavy rain, iii) Sound proofing with high quality rock wool/mineral wool confirming to IS 8183 of density at 96 Kg /M3 covered with fiber glass cloth and perforated powder coats sheet specially designed alienators (Sound controller) at air entry and exit of the container noise level shall be not exceed 75 Db at 1 meter distance as per CPCB norms. iv) Adequate ventilation to meet air requirement for combustion and heat removal with provn of a blower. v) Emergency stop push button outside the container. vi) Provn of light inside the canopy providing of FTL fitting 1x20 watt with wiring and control switch. vii) The canopy should be provided with height enclosure temperature safty device.
Supply install testing and commissioning of diesel Engine driven generating set 1010 KVA capacity, 3 phase, 4 wire, 440 V, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integrated acoustic enclosures having salient features modular bolted construction with fabrication on imported CNC turrert punch machines, Nine tank treatment process with pure polyester based powder coating to ensure long life in all weather conditions and for outdoor application/ installation. Integrated design thereby facilitating /easy handling installation and shifting of the eqpt at site. The design of integrated acoustic enclosure should be of type approved by National physical laboratory as per central pollution control board (CPCB) latest norms/regulation with fuel tank, battery and standard accessories including cost of PCC (1:2:4) type B-1 foundation for (acoustic enclosures foundation Height shall be 800 mm out of which 500 mm shall be above ground level) as recommended by manufacturer , Vibration pad sand cushioning around PCC foundation etc all and Tools and spares as provided by manufacturer all as specified and as directed with the following specifications :-.
(A)ENGINE : Water cooled with radiator diesel Engine (confirming to IS : 10001/10002) of 1500 RPM capacity to match the 1010 KVA alternator under NTP conditions with provision of 10% overload for 1 hour in every 12 hours running conforming to IS 6514/ IS 10001 / 10002 the Engine shall consist of the following :- (i) ) Fly wheel ii) Flexible coupling with guard bolts and nuts etc iii) Air cleaner heavy duty dry type (iv) Radiator with guard and water pump engine mounted v) Dynamo of suitable capacity. vi) Air cleaner heavy duty dry. vii) Fuel injection pump. viii) Radiator fan (Blower type) with guard. (ix) Electronic/ A1 class governor. (x) Fuel filter (Mounted). xi) Lubricating oil filter (mounted). (G) 12V self regulating alternator belt driven by engine. (G) Exhaust silencer heavy duty residential type xiv) Corrosion resistor / scale inhibitor. (G) Starter 12 V DC. xvi) Lubricating oil cooler. xvii) Lubricating oil pump (Gear type). (xviii) Turbo Charger xix) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminum sheet.
xx) Instrument panel complete with the following:- (m) Auto manual starting switch with key. (n) Lubricating oil temperature gauge. (o) Lubricating oil pressure gauge. (p) Water temperature gauge. (q) Battery charging ammeter. (r) Battery charging indicating lamp. (s) Hour meter with RPM indicator. (t) Safety control against high temperature of water. (u) Safety control against high temperature of water. (v) Safety control against low lubricating oil pressure. (w) Over speed stop with double driven adaptor. (x) Over load
(B) BRUSH LESS ALTERNATOR : Alternator coupled to Engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be conforming to BS-2613 or relevant IS-13364 (i) Type :- Self excited self regulated with automatic voltage regulator (ii) Rating :- 1010 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition 3 (iii) Speed :- 1500 RPM (iv) System :- 415 Volts +/- 2.5% AC 3 Phase 4 wire 50 Hz. (v) Connection :- 4 wire star connected (vi) Enclosure :- Screen protected dip proof. (vii) Ventilation :- Self ventilated (viii) ) Insulation :- Insulation Class H (ix) Over load withstand capacity :- (+) 10%
(D) AMF Panel cum Protection :- Separate Outdoor type AMF panel for automatic ON during power failure and off while power is on with adjustable time delay, panel totally enclosed fabricated out of CRCA sheet 3.25mm thick , over an angle iron frame made out of 50 x 50 x 6 mm angle with removable side cover hinged front panel and rear panel of easy accessibility complete with internal wiring of suitable size copper conductor cable and cable glands for external connection and comprising of following :- (xiii) AMF relay &power contactors of suitable rating for automatic starting on mains failure- 1 set (xiv) Digital type Frequency meter -1Nos (xv) RPM meter -1Nos (xvi) Under Voltage relay -1No (xvii) Over voltage relay- 1No (xviii) Reverse power relay- 1NO (xix) Trivector meter-1No (xx) Energy analyzer with CT- 1No (xxi) Earth fault protection-1Nos (xxii) Under/Over frequency relay- 1No (xxiii) HRC type instruments fuses (xxiv) Copper bus bar of suitable size (xxv) Circuit diagram plate
(E) FUEL TANK :- One No of sheet steel 14 SWG and capacity to hold diesel sufficient for running 16 hrs running at full load including necessary piping with following accessories:- (i) Level indicator on fuel tank (ii) Drain plug (iii) )MS class ‘C’ piping for inlet from pump to tank of engine (iv) Fuel strainer (v) Air vent. (vi) Manual hand operated pump with 3Mtr PVC pipe for filling of fuel.
(F) BATTERY : As recommended by manufacturers (G) Acoustic enclosure- Acoustic Enclosure suitable for 1010 KVA DG set as under. i) Fabricated out of CRCA sheet of suitable thickness not less than 1.6mm. Polyester based powder coated internally and externally with lockable type door handle. All nuts and handles shall be zinc coated. ii) The doors are gasket with EPDM gaskets. The construction should be such that it prevent entry of rain water splashing in to enclosure and allows free and quick flow of rain water to the ground in the event of heavy rain, iii) Sound proofing with high quality rock wool/mineral wool confirming to IS 8183 of density at 96 Kg /M3 covered with fiber glass cloth and perforated powder coats sheet specially designed alienators (Sound controller) at air entry and exit of the container noise level shall be not exceed 75 Db at 1 meter distance as per CPCB norms. iv) Adequate ventilation to meet air requirement for combustion and heat removal with provn of a blower. v) Emergency stop push button outside the container. vi) Provn of light inside the canopy providing of FTL fitting 1x20 watt with wiring and control switch. vii) The canopy should be provided with height enclosure temperature safty device.
Supply install, testing and commissioning of 33 KV, single phase, oil cooled, outdoor type, current transformer(CT) of ratio 120-60/5+5+1 Amp class 1.0-5P10 burden 15 VA insulation level 70/170 KV conforming IS-2705 including all control wiring with copper conductor multicore of suitable size complete all as specified and directed.
Supply, install, testing and commissioning of 33 KV single phase, outdoor type, potential transformer(PT) , oil cooled of ratio 33KV/rt3/110V/rt3/10V/rt3 class 0.5-3 Burden 50 VA-50 VA, insulation level 70/170KV, voltage factor 1.2 cont and 1.9 for 30 sec, confirming to IS-3156 including all control wiring with copper conductor multi core of suitable size complete all as specified and directed.
Material and labour for cable route indicator made out of CI plate 100 dia, 6mm thick and fixed over angle iron of size 60 x 60 x 6mm, 120cm in length duly painted with aluminium paint suitable for HT cable all as specified and including embedded in PCC(1:3:6) type C-1 of size 30 x30 x20cm in ground complete all as specified and directed.
Material and labour for dry tibba sand in trenches cushioning to under ground cable spreading, levelling, hand punning complete all as specified and directed. Note: Punned down thickenss shall only be measured and considered for payment.
Supply and installation of HT 11 KV, 3phase, 50 Hz totally enclosed metal clad switch gear panel having 2 Nos Incoming VCBs + 02 Nos Out going VCBs + 1Nos Bus coupler each VCB have indoor type minimum630 Amp, 26.3 KA breaking capacity, all specified as per IEC 62271-100 & IEC 62271-200 totally enclosed single bus bar for each phase, floor mounting, metal clad, flush fronted, horizontal draw out type, horizontal. isolation type, Indoor extensible type, with Electrical and Mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assembly of 3 vacuum interrupters, with epoxy support insulations and self - aligning finger type isolating contacts, truck having integral racking with necessary interlocks ( for insertion and withdrawal of VCB), manual and automatic motor charged independent closing/ tripping spring , trip free operating mechanism with closing and tripping push buttons and mechanical breaker , suitable rating inbuilt power pack for control all standard fitting and accessories of following with earth fault protection system , Amp meter, Volt meter all as specified as under Note :- (i) 02 nos of incoming VCB and 02Nos of outgoing VCB and 01 No. of Bus coupler mounted in same panel (ii) Bus couplers between 2 incomer. VCB must include following accessories :- (a) Housing of circuit breaker carriage. (b) Mechanical interlock and automatic safety shutter gear including pad locking arrangement. (c ) Isolating plug. (d) 11 KV, 400 Amps, VCB panel board having outgoing VCB , incoming VCB and Bus coupler comprising of
(e) Assembly of VCB interupters complete with epoxy support insulator and self aligning finger type isolating contacts (f) Hand and Motor (220 Volt AC) charged independent spring closing/tripping trip free operating mechanism with mannual closing and tripping push bottons and mechanical breaker closed/open, spring charged/discharged indication. (g) Electric release coil 24 V DC (h) Mechanical operation counter. (i) Breaker operated auxillary switch (j) Bus bar chamber including a set of 3 phase 400 Amp copper bus bar (k) 230 volts AC single phase 80 W rated strip type heater with indicator complete (l) Voltage transformer (VT) incorporating 3 phase 3 limb with drawable type VT having ratio 11 KV/110V and out put of 100 VA per phase with accuracy class I as per IS-3155 complete with HT and LT HRC fused n primary and secondary sides respectively (confirming related IS specification) (m)Current transformer (CT) chamber incorporating 3 single phase resin cast, dual ratio CTs of 100/50/5/2.5/1 with suitable VA burden and accuracy class.
Supply and fix float cum boasting charger with power battery bank consisting of 55 Nos of solid SMF batery cell rated 100 Ah,2 Volt Dc for back supply of VCB and connected to VCB complete all as specified and directed.
Supply, installation, testing and commissioning of extensible 11 KV , 630 Amps, outdoor type safe plus Extensible Compact switch gear "Ring Main unit" one incoming and two out going having 01 No motorised Vacuum circuit break switch, 02 No load break switch and 01 No Metering module as Bus PT along with bottom cable entry and front cable termination with following specification PCC and block masonary for installation of Ring Main Unit complete as per manufacturer instruction and design all as dirtected:- STANDARDS AND MECHANICAL DATA Metal Enclosed switchgear: IEC 62271-200 General Purpose switches: IEC 60265-1 Disconnectors and Earthing switches: IEC 62271-102 Circuit Breakers: IEC 62271-100 Common clauses: IEC 60694 Pressure of SF6 gas: 1.4 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C Outdoor Degree of protection: SF6 tank: IP 67 Front cover: IP 2X Cable cover: IP 3X Enclosure: IP 54 Busbars: 240 mm2 Cu Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 Thickness of Stainless Steel Tank: 2.5 mm
Colours: Front cover: RAL 7035 Side and cable cover: RAL 7035 Enclosure: IS 632 ELECTRICAL DATA – 12 kV - 28kV-1min Rated current busbars: 630 A Rated current cable switch disconnector : 630 A Short time withstand current: Cable switch disconnector with interface C (400-bolt) bushing: 20kA/3 sec. Vacuum circuit breaker with interface C (400-bolt) bushing: 20 kA/3 sec Rated current for transformer T-off : 630 A Impulse withstand voltage : To earth and between phases: 75 kV Insulation level: Power frequency 1 min: 28 kV A01 to A02 Incoming Vacuum Circuit Breaker Module Type V (i) SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (A-mech.). (ii) SafePlus type V: Vacuum circuit breaker 12kV, 630A - 01 Nos Stored energy mech. for manual operation - 01 Nos (iii) Self Powered OC+EF Protection Relay - 01 Nos (iv) Set of 03nos. Ring Core Protection CTs of suitable ratio as per feeder load, 2.5VA, 10P10 - 01 Nos
Supply, installation, testing and commissioning of extensible 11 KV , 630 Amps, outdoor type safe plus Extensible Compact switch gear "Ring Main unit" two incoming and one out going having 02 No motorised Vacuum circuit break switch, 01 No load break switch and 01 No Metering module as Bus PT along with bottom cable entry and front cable termination with following specification PCC and block masonary for installation of Ring Main Unit complete as per manufacturer instruction and design all as dirtected:- STANDARDS AND MECHANICAL DATA Metal Enclosed switchgear: IEC 62271-200 General Purpose switches: IEC 60265-1 Disconnectors and Earthing switches: IEC 62271-102 Circuit Breakers: IEC 62271-100 Common clauses: IEC 60694 Pressure of SF6 gas: 1.4 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C Outdoor Degree of protection: SF6 tank: IP 67 Front cover: IP 2X Cable cover: IP 3X Enclosure: IP 54 Busbars: 240 mm2 Cu Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 Thickness of Stainless Steel Tank: 2.5 mm Colours: Front cover: RAL 7035
Side and cable cover: RAL 7035 Enclosure: IS 632 ELECTRICAL DATA – 12 kV - 28kV-1min Rated current busbars: 630 A Rated current cable switch disconnector : 630 A Short time withstand current: Cable switch disconnector with interface C (400-bolt) bushing: 20kA/3 sec. Vacuum circuit breaker with interface C (400-bolt) bushing: 20 kA/3 sec Rated current for transformer T-off : 630 A Impulse withstand voltage : To earth and between phases: 75 kV Insulation level: Power frequency 1 min: 28 kV A01 to A02 Incoming Vacuum Circuit Breaker Module Type V (i) SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (A-mech.). (ii) SafePlus type V: Vacuum circuit breaker 12kV, 630A - 01 Nos Stored energy mech. for manual operation - 01 Nos (iii) Self Powered OC+EF Protection Relay - 01 Nos (iv) Set of 03nos. Ring Core Protection CTs of suitable ratio as per feeder load, 2.5VA, 10P10 - 01 Nos (v) Set of 03nos. Ring Core Metering CTs of suitable ratio as per feeder load, 2.5VA, Class 1.0 - 01 Nos (vi) Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos
(vii) Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos A03 Load break switch Module Type C (i) SafePlus C is a Load Break switch module with , three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (A-mech). (ii) SafePlus type C: Load break switch 12kV, 630A - 01 No (iii) Stored energy mech. for manual operation - 01 Nos (iv) Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos (v) Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos A04 Metering Module Type M (i) SafePlus M is an air insulated metering module. (ii) SafePlus type M: Air insulated metering module 12kV, 630A (IAC AF 16kA 1 s)- 01 Nos
Disconnecting HT/LT connections of serviceable transformers up to 500 KVA capacity, taking down from pole/plinth, shifting and re-commissioning at new location including connecting with HT/LT side of existing system and testing complete all as specified and directed.
Supply, erecting and fixing in true vertical position steel tubular swaged pole, swan neck type 9 mtr long complete with cast iron base plate, finial taper plug, bolt, nuts and screws as specified and of type 410 SP-31, conforming to relevant IS, including one primer coat of red oxide and two coats of aluminium paint and two coats of bituminous paint inside and outside of bottom portion up to 1.8 mtr length complete all as specified and directed.
Supply and fix street light bracket of GI light grade 40 mm dia pipe 1.5 mtr long bend to shape with clamp nut bolts etc complete all as specified and directed.
Supply and fix LT Cable junction box outdoor shall be made out of Polycarbonate with glass fiber reinforced and size should be not less than 225mm x 295mm x 122 mm(upto Cable Size 35/50sq.mm). The Polycarbonate Junction Box shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive. The Junction Box shall be rated for Degree of ingress Protection IP 66/69 in accordance with IEC 60529.Weatherproof, UV-resistant, rainwater-proof, temperature-resistant. The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22 & IEC 60670 - 2 - 5. The Junction Box with Connectors or Terminal Trip or Bus Bar. The manufacturer of Junction Box / Enclosure shall submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade & Current Carrying Capacity upto 102Amps. The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector and one no. MCB SP 'B' curved 6-32 Amp and chromium plated clamps and nut bolts, Glands complete all as per manufacturer’s instructions
Supply and fix copper service wire 1.5 sqmm 3 core PVC insulated and PVC round sheathed multistranded copper conductor flexible industrial cable 1100 V grade drawn in street light poles complete all as specified and directed.
Supply and fix energy effcient LED street light fitting of 70 Watt, epoxy powder coated pressure die cast alumminium housing to act as heat sink for effcient dissipation of heat and toughened glass with IP 66 degree of protection, system luminous efficency more than 100 lumens / watt, individual LED's should have lenses for beter throw across and along road, PF>0.9 with voltage range 140 to 270 Volt, fitting should be provided with inbuilt 10KV minimum surge protection, short circuit and over voltage protection facility for Driver and fitting & including making electrical connection complete all as specified and directed. (203 LED for new pole + 272 LED and bracket for existing pole)
Supply and fix in replacement Intelligent, flexible & smart outdoor lighting control unit for automatic switch ON at dusk automatic switching OFF at Dawn with Astronomical Time Switch, high voltage and low voltage protection, 3 Pole / 230V For 12 KW load equally distributed over 3 phases. Minimum IP54 Degree of Protection
Supply, Installing, testing and commissioning of LT panel indoor type ,size 1510mm X 1310 mm X450 mm metal enclosed fixed type, free standing, floor mounting, compartmentalized, modular type suitable for indoor installation, cubical type, factory assembled in bolted design fabricated from 2 mm thick CRCA sheet steel frame work and painted with two coat of synthetic enamelled paint, degree of protection IP-54 as per IS-13947,consisting high conductivity copper bus bar of rating 200 amps and of suitable size with heat shrinkable sleeves, fault rating 36 kA for 1 sec, including multifunctional digital voltmeter, ammeter, frequency meter and power factor meter with comprising the followings:- MCCB 100 Amp, 36 kA,4 Pole -01 Nos MCCB 63 Amp,25 kA,4 Pole-02 Nos MCB 6A 10 kA,TPN-01 Nos MCB 6A 10 kA,SPN-01 Nos On Load Changeover 100 Amp,4 Pole-01 Nos Multifunctional meter-01 Nos RYB Indicator set-01 Nos
Supply, installing, testing and commissioning of LT panel indoor type ,size 2010mm X 1500 mm X600 mm metal enclosed fixed type, freestanding, floor mounting, compartmentalized, modular type suitable for indoor installation, cubical type, factory assembled in bolted design fabricated from 2 mm thick CRCA sheet steel frame work and painted with two coat of synthetic enamelled paint, degree of protection IP-54 as per IS-13947,consisting high conductivity copper bus bar of rating 1000 amps and of suitable size with heat shrinkable sleeves, including multifunctional digital voltmeter, ammeter, frequency meter and power factor meter with comprising the followings:- MCCB 630 Amps 50KA 4 Pole -01 Nos MCCB 400 Amp,35 kA,4 Pole -02 Nos MCCB 63 Amp,25 kA,4 Pole -01 Nos MCB 6A 10 kA SPN, -02 Nos On Load Changeover 630 Amp,4 Pole -01 Nos Multifunctional meter-01 Nos RYB Indicator -set 01 Nos
Supply, installing, testing and commissioning of LT panel indoor type ,size 3010mm X 2000 mm X600 mm metal enclosed fixed type, freestanding, floor mounting, compartmentalized, modular type suitable for indoor installation, cubical type, factory assembled in bolted design fabricated from 2 mm thick CRCA sheet steel frame work and painted with two coat of synthetic enamelled paint, degree of protection IP-54 as per IS-13947,consisting high conductivity copper bus bar of rating 3000 amps and of suitable size with heat shrinkable sleeves, including multifunctional digital voltmeter, ammeter, frequency meter and power factor meter with comprising the followings:- ACB 1600 Amps 65KA 4 Pole-01 Nos ACB 1250 Amps 65KA 4 Pole-01 Nos MCB 6A 2 kA,SPN-03 Nos On Load Changeover 1600 Amp,4 Pole -01 Nos Multifunctional meter-01 Nos RYB Indicator set-01 Nos
Supply and fix 400 sqmm PVC insulated single core unsheathed copper cable industrial type as per IS 694:1990 connected to Transformer to LT panel through DG and AMF Panel complete all as specified and directed.
Supply and fix 400 sqmm PVC insulated single core unsheathed Aluminium cable industrial type as per IS 694:1990 connected to Transformer to LT panel through DG and AMF Panel complete all as specified and directed.
Supply and fix LED Flood light fitting 200 watt, system efficiency not less than 115 lumens/watt, IP 66 protection consisting of inbuilt surge protection device 10 KV high/low voltage cut off maintenance free isolated electronic driver circuits, low THD PMMA grade high quality. Transmittance lens, epoxy powder coated Die cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws & connecting complete all as specified and directed by Engg –in-charge.
Supply and fix HT 11 KV sock proof synthetic insulated mats as per IS 15652-2006 (superseding IS 5424) of size 1 mtr x 2 mtr x 3mm with specification : sock proof and anti-slippery Chemically inert, Ensure superior accuracy in blast patterns, Superior protection from acids, oils and Lightweight complete all as specified and directed.
Supply, lay, jointing and testing centrifugally cast (spun) ductile iron pressure pipe of 100mm dia with socket and spigot ends class 'K-7', ISI marked, confirming to IS: 8329/2000 suitable and including rubber gasket joint and fittings (push on) with inside cement mortar lining laid in trenches under floor complete all as specified and directed.
Supply and fix Sluice valve of 100mm dia with brass spindle with hand wheel of class PN 1.6, conforming to IS 14846-2000 including suitable size bolts, nuts and washer and rubber gasket complete all as specified and directed.
Supply and fix DI special fittings like unequal Tee, reducer tee, reducer, extension with/without flange for connecting to required size pipe with all fitting including cutting DI line of any size upto 150 mm dia and insertion of any size up to 100mm of DI special complete all as specified and directed.
Material and labour for construction of valve pit in stone masonry built in CM (1:6) of size 1200mm x 1200mm x 1000mm (internal dimension) with precast cement concrete block of PCC 1:4:8 type D-2 using 40mm graded stone aggregate and 15 mm thick rendering in CM 1:6 on internal and exposed external surfaces including 40x40x6 mm mild steel angle iron frame and 3 mm thick MS sheet cover with locking arrangement and 1 no. 50 mm size 4 lever lock with triplicate keys including painting to steel and iron surfaces with two coats of black bituminous paint over a coat of red oxide primer complete all as specified and directed.
Supply and fix wall mounted type line-Voltage Stabilizer of capacity 2 KVA for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of +/- 2.5% and speed of correction 8 volt per second complete all as specified and directed.
Supply and fix desert cooler electric driven (single phase) with overall dimension 760x1060 x 610 mm having tank capacity 70 ltrs with fan of size 500 mm, grass padded walls with motor arrangement for air circulation, motor should be ISI marked with variable speed (High 1400 rpm, Med 1300 rpm, Low 1250 rpm) , efficiency of fan motor should be 40% with PF >0.85 totally enclosed, having nominal air flow capacity of 4000 CuM per hour (or nearest size), should also include water pump of Head 5ft, input watt-20W, operating voltage-single phase, 220 V, 50Hz, complete all as specified and directed.
Sch of credit Rs 6,86,744.10
SHRI GURMUKHDAS CONTRACTORS PVT. LTD.
MANGLA AMIT BUILDERS PVT LTD
FRIZO INDIA PVT LTD
SOOD ASSOCIATES PVT LTD
Komal Buildcon Pvt. Ltd.
Rabina Enterprises Pvt Ltd
mahinder pal and co
Hariom Projects Pvt Ltd
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid