Construction of 50 bedded upgraded to 100 bedded additional accommodations for Civil Hospital at Jawalamukhi, District Kangra H.P SH Providing MGPS (Medical Gas Pipe Line system therein)
2026_PWD_126294_1
Elect. Division HPPWD Palampur
Open Tender
Electrical Works
Percentage
Jawala ji
Please refer Tender documents.
8 documents required · 8 mandatory
₹5,000
₹3.6 L
21 Feb 2026
20 Jan 2026
27 Jan 2026
20 Jan 2026
27 Jan 2026
20 Jan 2026
Oxygen System
Oxygen Manifold and control panel
The manifold and control panel should comprise of two banks of 10+10 cylinders each In additional bank of 10 cylinders should be supplied and installed for emergency supply of oxygen.
The control panel should be meant for the supply of oxygen at 1500 litres per minute
The unit (control panel)should comply with international standards like NFPA/ HTM-2022/ BIS/CDSSO
The control panel will need to be adjusted at a pressure to ensure 4 bar pressure in the two blocks of the hospital
The control panel should be from reputed manufacturers like: Becon Maedas/Ohio Medical/ Penlon/ Medicop/ Drager/Atlas COPCO/Aktive EuCE or USFDA certified
Feed Gas:Medical grade oxygen as per Indian Pharmacopeia 99.5% at pressure 130 – 140 bar
Gas Delivery Temperature (–) 10oC to (+) 30oC and ambient relative humidity of exceeding 80%
Altitude above MSL: 2250 meters
Frost formation and pressure drop is common problem in winters and rainy season. Therefore heating arrangement for the control panel have to be provided and be documented and quoted.
Safety relief valves, pressure gauges, NRVs and Alarms etc should be provided with means to prevent tampering by Un-authorized persons.
Supply Installation and Testing commissioning of 4+4 Emergency Manifold and piston operated regulator.
Wall outlets oxygen
Makes:-Beacon Medeas, Greggersen, Aktiv Raj med, Wed Med
Oxygen, air and vacuum outlets HTM or NFPA compliant should be quoted along with 2 probes for each out let. Both imported and indigenous outlets and probes should be quoted separately. The outlets and probes should be as specific and non- interchangeable. The gas outlets have heavy duty constituents and smooth connection and disconnection. The outlets must be labeled and color coded. Imported units should have UL Listing and Indian units must be IS/CE certified. Makes:-Beacon Medeas, Greggersen, Dragger
Probes for Wall Outlets
OXYGEN FLOW METER WITH HUMIDIFIER BOTTLE (CE MARKED)
The oxygen manifold should comply with HTM 02-01/NFPA 99/ DIN / EN / ISO-7396-1 standards.Makes:-Beacon Medeas, Greggersen, Aktiv, Rajmed Wed Med
Back Pressure Compensated flow meter for accurate gas flow measurement with following features:
A)Control within a range of 0-15 LPM.
B) It should meet strict precision and durability standard.
C) The flow meter body should be made of brass chrome plated materials.
D) The flow tube and shroud components should be made of clear, impact resistant polycarbonate.
E) Flow tube should have large and expanded 0-15 LPM range for improved readability at low flows.
F) Inlet filter of stainless steel wire mesh to prevent entry of foreign particles
G) The humidifier bottle is made of unbreakable & reusable polycarbonate /polysulfone/polypropylene material autoclavable at 121 degree centigrade.
Vaccum System
Skid mounted vacuum system
Control System The central control system shall provide an intelligent human machine interface incorporating on board flash memory and real-time clock for recording operational parameters in the event log. The central control system shall operate at low voltage and include BMS connection for common fault. Visualization of plant inputs, outputs, and status through a web browser, using a simple. The central control unit shall incorporate a user friendly 4.3” high-definition touchscreen displays with clear pictograms and LED indicators, providing easy access to system operational information. The controller shall be equipped with an integrated 4G module for remote monitoring of the equipment.Cascading of vacuum pumps shall be achieved by measuring the vacuum level at the plant inlet with a pressure transducer. A mechanical back-up facility shall ensure continued operation in event of a control system malfunction. The control system shall normally employ automatic rotation of the lead pump to maximize pump life and ensure even wear.Makes:-AKTIV, PENLON, HISPL
Frame Mounted: Medical Vacuum Supply System. Plant Output (liters/minute) 630, System Flow (m3/hr) 101,System Flow (liters/minute) 1680 , Number of pumps 2 , Min Receiver volume recommended (liters) 1000 , Receiver connection(s) (mm) 54 , Inlet/service connection (mm) 54 , Exhaust connection (mm, per pump) 42 , Maximum exhaust back pressure (mbar) 500, Noise level/pump (dBA)* 65 , Motor rating per Pump (kW) 2.2 , Individual Pump control unit panel supply- (Voltage/Freq./ Phase) 415 V / 50 Hz / 3 phase, Individual Pump control unit panel supply cable size mm2 (Amps) 2.5 (17) Motor rated supply per pump (A) 4.9 , Full load current per pump (A) 5 , Starting current per pump (A) 28.8 ,
Vacuum Receiver(s) 1500 LTR Vacuum receiver(s) shall be supplied with relevant test certificates and have a total volume of at least 100% of the plant output in 1 minute in terms of free air aspired at normal working pressure. Each vacuum receiver shall be powder coated from inside and outside.Makes:-B-TECH ENGINEER,AKTIV,WEDMED,RAJMED
Duplex Vacuum Bacterial Filters
Bacteria Filters The duplex bacteria filter system shall incorporate high efficiency filter elements. A differential vacuum indicator shall be installed across the filter to indicate blockage. Additional pressure sensors shall be installed at the inlet and outlet of the filter to measure the pressure drop across the filters. Each filter shall be designed and sized to carry the full plant design flow capacity with a pressure drop not exceeding 33mbar (25mmHg). Bacteria Filter elements shall have penetration levels not exceeding 0.005% when tested by the sodium flame method in accordance with BS 3928:1969 and utilizing particles in the 0.02-to-2micron size range. Drain flasks shall be connected to each filter. Drain flasks shall be manufactured from transparent Pyrex® with a polymer coating on the inner and outer surfaces to maintain a seal in the event of inadvertent breakage of the Pyrex® flask. All drain flasks shall be suitable for sterilization and be connected via a manual isolating valve.Makes:-BEACON MEADAS, Tri Dennt, Greggersen, HISPL
Wall outlets Vaccum (Specs same as given for Oxygen Outlets)Makes:-Beacon Medeas, Greggersen, Dragger
Ward Vacuum Units ( CE Marked)- Makes:-AKTIV, Penlon, Wed Med, Raj Med, HSIPL
It should comply with HTM 02-01/NFPA 99/ DIN / EN / ISO-7396-1 standards.
It must consist of the following:-
1. 1 no of Suction Regulator and 1no of 1000 ml polysulfone /polycarbonate/polypropylene collection jar.
2. Suction Regulator: Suction regulator should be supplied with a safety jar, including and antibacterial filter and an anti-overflow safety device. Should have wide membrane continuous suction controller
3. Should have vacuum levels: 0-760 mm of Hg
4. Should have vacuum gauge fitted with a protective bumper device.
5. Should have on/off knob allowing for the quick restoration of a readjusted vacuum level.
6. Must have central adjustment knob with a color coded for 0 to 760 mm of Hg. Should have Polysulfone/polycarbonate 100cc safety jar, autoclavable at 121º C, unbreakable, fitted with an anti-overflow safety device and equipped with a plastic antibacterial filter. It should be totally transparent, to ensure perfect sucked liquid visibility.
H.P. antistatic rubber tube
SITC of Compressed air H.P. antistatic rubber tube, The high pressure tube should be made of antistatic rubberas per ISO standards and colour coded, etc. complete as required.
Thearter suction Trolly
Air System
Air Compressor
Design enhancements improve overall system efficiency, coupled with an incredibly simple unit to maintain that fits the most challenging space constraints, this next generation Scroll Medical Air Package is in a class of its own.Beacon Medeas, Greggersen, Chicargo Pneumatic, Air Net.
• Designed to ISO 13485 standards and procedures, fully NFPA 99 compliant. Incredibly small footprints.
Air dryer Duplex Including Dew point Monitoring System
• Dryer system for guaranteed dew point, minimal leak points, and ease of service.
• New fittings and connectors to reduce potential leak points and conserve energy.
• Single point connections for intake, outflow, electrical and drainage.
• Extremely low noise levels and no vibration.
Peace of mind High-tech Elektronikon® graphic controller with modified medical software to increase reliability in conjunction with ESMedical Central Controller
Minimal moving parts ensure a long operating life with
minimum number of service interventions.
• With no need for oil lubrication in the compression chamber,
you are guaranteed high-quality, oil-free air.
• The scroll elements are belt-driven, eliminating the need for
a gearbox. Oil-free in every way.
Clean, Dry Medical Air
The LifeLine medical air dryer delivers clean, dry medical air all the time. The unique aftercooler design ensures effective dryer operation even under heavy duty conditions, guaranteeing dew point performance. High efficiency coalescing filters remove particles and liquids from the air stream to protect the dryers and to protect your medical air delivery.
Dryer Efficiency – Dew Point Purge
The LifeLine heatless desiccant dryers utilize dew point dependent purge control to guarantee the lowest possible energy losses for desiccant regeneration while delivering a totally stable and reliable dew point. Purge air is minimized with tower switching based on dew point readings, so when the medical air demand is low, so is your energy consumption. The drying towers are sized specifically for peak calculated demand in medical air applications and capable of producing a -10 pressure dew point. Unlike industrial dryers applied to medical air applications, the LifeLine dryers don’t waste energy, footprint, or desiccant to achieve unnecessarily low dew points. With smaller towers, less purge air is required to regenerate the drying towers, saving you additional energy dollars. Scroll Towers While minimizing footprint, the tower design allows ease of access to all sides of the compressor, motor, belts, and aftercoolers. Belt adjustments are easy to make. Greasing bearings and tip seal changes are much more efficient and can be performed on site. Dryer Towers Desiccant towers are easy to reach and simple to remove for service. Inlet and outlet filter cartridges are easily reachable and removable without obstructions. Basic servicing does not require extra steps or items to remove. 10 HP 7.5 kw at 109 psig3 at 50 psig4 (scfm-l/m) 28.0 - 793 at 50 psig4 (icfm-l/m) 34.8 - 985 Noise Level5 of 63db.
AIR Receiver(s) 1500 LTR AIR receiver(s) shall be supplied with relevant test certificates and have a total volume of at least 100% of the plant output in 1 minute in terms of free air aspired at normal working pressure. Each Air receiver shall be powder coated from inside and outside.Make:-B-TECH ENGINEER,AKTIV,WEDMED,RAJMED
Wall outlets Air ( 4 bar)
Oxygen, air and vacuum outlets HTM or NFPA compliant should be quoted along with 2 probes for each out let. Both imported and indigenous outlets and probes should be quoted separately. The outlets and probes should be as specific and non- interchangeable. The gas outlets have heavy duty constituents and smooth connection and disconnection. The outlets must be labeled and color coded. Imported units should have UL Listing and Indian units must be IS/CE certified. .Makes:Beacon Medeas, Greggersen, Penlon,dragger
SITC of Compressedair H.P. antistatic rubber tube, The high pressure tube should be made of antistatic rubber as per ISO standards and colour coded, etc. complete as required.Makes:-Aktiv Penlon,Rajmed Wedmed
Wall outlets N2O
Oxygen, air and vacuum outlets HTM or NFPA compliant should be quoted along with 2 probes for each out let. Both imported and indigenous outlets and probes should be quoted separately. The outlets and probes should be as specific and non- interchangeable. The gas outlets have heavy duty constituents and smooth connection and disconnection. The outlets must be labeled and color coded. Imported units should have UL Listing and Indian units must be IS/CE certified. Make Becon Medas, Dragger, Allied USA.Beacon Medeas, Greggersen, Penlon
Pressure Reduction Station ( 4 bar )
Precise pressure reduction control for optimal performance. Compact design and easy installation. Robust construction ensures long-term durability. Filters and strainers. Suitable for medical air and surgical air. Pressure reduction station ensure high accuracy in outlet pressure cont.Make:-beacon medas, penlon,Rajmed,Wedmed, Aktive
Medical Grade Copper Pipeline With Tubings, Fittings, Pressure Gauges.Makes:-Mandev Tubes, Maxflow, Satyam,Nefton
The copper pipes shall be copper annealed ASTM B/75/B68 or equivalent standards.
The Diameter of the pipe should be suitable for 1000 LPM average flow and this pipeline will have to be divided into two in the oxygen supply plant and attached to two pipelines systems presently feeding the hospital.
Grossly the diameter should not be less than 38mm X 1.5mm or thicker so as to bear pressure of 10 -12 bar
All pipe work materials shall be manufactured by BS EN ISO 9001:2000 registered companies marking for sizes up to 108 mm, copper pipes shall be permanently and durably marked at regular intervals along its length with the following information
- The harmonised standard number EN 13348;
- Lloyds/BSI Kitemark or equivalent approved to EN 13348:2008
- Nominal dimensions, diameter x wall thickness;
- Temper designation to EN 1173;
- Manufacturer's identification;
- Date of production: year and month (1 to 12)
- Confirmation of degreasing for oxygen
Brazing shall be carried out flame source, temperatures and materials as per HTM/ NFPA recommendations
Brazed Pipeline Joints (Copper to copper) should be made using a silver-copper-phosphorous brazing alloy CP104 (5% Silver Brazing Filler metals Rod) to BS EN 1044-1999, no flux to be used.
Copper Fittings:
Medical Gas Pipeline Fittings shall be end feed type, manufactured from the same grade of copper as the pipes and be in accordance with the requirements of BS EN 1254-1:1998 Part 1. The manufacturing company should comply with BS EN ISO 9001:2000 and should be Kite Marked/Lyods or equivalent to EN 1254-1 (up to 54mm). Fittings should be factory degreased suitable for oxygen use and be supplied individually sealed in protective polythene bags. Fittings should be certified for medical use and accompany with oil analysis certificate and conformity certificate indicating suitability for medical use.
Protection for pipes
The pipelines in the bare area like space between buildings should be suitably protected and covered with fire resistant/ retardant insulation in such a manner that inner copper pipe does not come in contact with outer GI pipe. High Quality GI pipe quality covers which should be welded in such a way that only authorized person can open it using proper tools only. Further these should be of such a material and supported in such a manner so as to take load of monkeys/ langoors. Any such supports required should be quoted in the technical bid in the civil work.
Uncovered Sections of GI pipe will have to be protected with weather resistant stainless steel barbed wire.
The pipeline should be suitable for tolerating temperatures of (–) 10oC to (+) 30oC and high ambient humidity exceeding 90% and ice formation during winters. Given the length of the pipeline and climatic conditions, provision for expansion and shrinkage of metal should be incorporated.
All end connections, pressure gauges, valves and fittings of cascade shall be within tamper proof, see through and wire cage enclosure. These shall be on one side of cascade frame for ease of operation.
Parts of the pipe between the building blocks may have to be supported with columns/ beams of iron angle or concrete if necessary, which will have to be done by the firm laying down the pipeline.
The copper tube used for venting (if any) shall be of ASTM B75, B68.
Sizes of pipeline with above specification to be used.
O.D. 42mm x 1.2mm thick
O.D. 35mm x 1.2mm thick
O.D. 28mm x 0.9 mm thick
O.D. 22mm x 0.9mm thick
O.D. 15mm x 0.9mm thick
O.D. 12mm x 0.7 mm Thick
Pipes to be paid as per actual basis. Unused spare lengths will be returned
Pipe line Alarm with Area Isolation (AVSU)
AVSU is a modular Area Valve Service Unit (AVSU) with integrated Local Area Alarm. It is manufactured under : Quality Management Systems. It is designed to provide minimum 2 gas and maximum 5 gas service including vacuum.Makes:-Beacon Medeas, aktiv, Penlon,Rajmed solution, Dragger
Microprocessor based module Highly accurate “Heavy Duty” pressure transducer Powder coated aesthetically designed enclosure Enclosure separable from the base for ease of installation Reusable lock assembly Audio mute option PED: 2014/68/EU certified full port Ball Valve (PN 30) Long extension copper pipes to connect MGPS network Designed to serve 2, 3, 4 & 5 gas module Suitable for all medical Gases & Vacuum Adjustment & parameter setting by touch button Operational parameters can be set in-situ Digital & illuminated LED display of “Normal”, “High” & “Low” .Digital pressure unit display options - psi / bar or kg/cm
Ball Valves are used to start or stop a flow. In Medical Gas Pipeline System (MGPS), the valves are normally kept open i.e. allow the gas to flow unless it is required to shut-off the gas supply for scheduled maintenance or emergency situation. The importance of full bore ball valves is to reduce pressure drop to almost negligible in the pipeline distribution system so that the designed pressure is available at the outlet point.
3 GASES
4 GASES
Master alarm for Plant room.Makes:Beacon Medeas, Aktiv, Penlon,Rajmed solution, Dragger
Shut off Valves with Brass Fittings.Makes:-Penlon, Rajmed, wedmed, aktiv
HORIZONTAL BED HEAD PANEL (CE MARKED)Makes:-Beacon Medeas, Greggersen, Penlon,dragger Penlon
Bed Head Panel should conform to NFPA99/HTM-02-01/ISO-7396-1/DIN/EN.
• Efficient, safe &. Robust design in extruded aluminum section
• Smooth curved surfaces, and choice of base colour and fascia plates.
• Unit should have integrated rail system to mount accessories.
• The headwall system should be constructed of aluminum extrusions joined together to
form a carcass to suit the particular application. Unit shall be factory assembled for electrical and mechanical components.
• Segregation of services i.e. electrical wiring supply and Medical gasesshall be maintained throughout.
• Front fascia plate should be removable individually to access for respective service.
• Bed space management system with optional equipment rail.
• With all Equipment Rail mount Accessories.
• Should have built in light feature
• Medical gas pipe line outlets should be factory fitted by & tested by the manufacturer. Outlets configuration as per hospital requirement.
• Following accessories should be provided locally with HBHP;
i) 5/15 Amp Modular Electrical Sockets with switches = 6 sets
ii) IV Pole = 2nos
iii) Vacuum slide = 1no.
iv) Sliding blocks = 2nos.
v) Nurse call system module (cut out provision only) = 1No.
vi) ) Infusion Pump Mounts = 1 No
vii) Monitor Tray with Slider = 1 No.
viii) Utility Basket = 1 No.
Bed Head Panel should CE marked. (3 GASES )
Single arm Cealing Pendent Anaesthesia
Single arm pendants with 330 rotation should be quoted. It should have 5 gas outlets, 4 electricity outlets, I shelf for 15” monitor and a weight bearing capacity of 15 Kgs or more. The pendant should be sturdy and stable at all points of movement. Makes:-Beacon Medeas, Greggersen, Penlon,dragger
330° Utility console rotation-Utilitas C. 330° Utility console rotation+ 330° Arm rotation Utilitas C1. High Payload. True Versatility. Flexible Solution. Effortless maneuverability. Optimum functionality. Easy access to console facia. Bedside safety. User-friendly positioning of Medical Devices. -All services integrated into the pendant system ensuring optimal safety. -Convenient positioning of gas, equipment, electrical and specialty services. -Service head ergonomics – Shelves / Monitor mounting solutions. -Hose connection - Gas specific NIST connectors. -Power supply - Low smoke halogen cable through spiral conduit terminating at junction box. -Hygiene- Minimum visible screws, combined with smooth surfaces for easier cleaning and disinfection . -Configuration can be customized within the limits of applicable standards . --220V AC Electrical socket -Four shutter type multi-standard sockets compatible to 5-6-10-13A plugs and three 16A sockets will be provided. -Earthing - Protective Earth . -Body (Pendant) Alloy 6063 T6 : Extruded aluminium profile (T = not less than 2.5mm). -Suspension Assembly Pre-engineered Rust-proof (passivate) Trivalent Zinc plated (8-10µm) steel. -Finish (Pendant) Epoxy coating to RAL 7035 (Textured). -SEEB (Optional) Plug and socket for Supplementary Equipotential Earth Bonding. -Mounting Complete mounting system with NIST connection for gas & vac services and terminals for power connection. - Communication Ports 1 - RJ45 Data socket, 1 - RJ11 Telephonic socket
N20 Manifold and control panel.Make:Beacon Medeas, Greggersen, Aktiv Raj med, Wed Med
The manifold and control panel should comprise of two banks of 4+4 cylinders each In additional bank of 8 cylinders should be supplied and installed for emergency supply of N20.
The control panel should be meant for the supply of N20 at 500 litres per minute
The unit (control panel)should comply with international standards like NFPA/ HTM-2022/ BIS/CDSSO
The control panel will need to be adjusted at a pressure to ensure 4 bar pressure in the two blocks of the hospital
The control panel should be from reputed manufacturers like: Becon Maedas/Ohio Medical/ Penlon/ Medicop/ Drager/Atlas COPCO/Aktive EuCE or USFDA certified
Feed Gas:Medical grade oxygen as per Indian Pharmacopeia 99.5% at pressure 130 – 140 bar
Gas Delivery Temperature (–) 10oC to (+) 30oC and ambient relative humidity of exceeding 80%
Altitude above MSL: 2250 meters
Further more formation and pressure drop is common problem in winters and rainy season. Therefore heating arrangement for the control panel have to be provided and be documented and quoted.
Safety relief valves, pressure gauges, NRVs and Alarms etc should be provided with means to prevent tampering by Un-authorized persons.
Supply Installation and Testing commissioning of 1+1Emergency Manifold and piston operated regulator
Electrical control pannel with phase rectifier
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.28 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.43 MB
DECLARATION.pdf
Additional Documents • 0.01 MB
GCC.pdf
Tender Documents • 3.97 MB
BOQ_186170.xls
BOQ • 0.52 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .