| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAccepted-AOC CHENNAI 600 095 | CHENNAI | TAMIL NADU | 600001 | ₹1.2 Cr Quoted ₹1.3 Cr | L1 | Accepted-AOC Lowest negotiated bid approved by Chief Engineer, TNUHDB |
| 2 | L2₹1.4 CrRejected-AOC NO 15 3 BREEZE APARTMENT SERVICE ROAD NOLAMBUR CHENNAI 600037 | CHENNAI | TAMIL NADU | 600037 | ₹1.4 Cr | L2 | Rejected-AOC Rejected |
| Sl No | Description | Qty | Unit | SRP CONSTRUCTION COMPANY L2 | PTM PROJECTS PVT LTD L1 |
|---|---|---|---|---|---|
| 1.00 | Providing stucco plastering with CM 1:3 (one of cement and three of HBG stone chips) using HBG stone chips of size not grater than 10mm of thick 12 thick over plastered surface including cost of materials, labours, scaffolding, finishing and curing etc., completed in all respects as directed by tha departmental officer. (In all floors) | 516.73 | M2 | 405 ₹2.1 L | 400 ₹2.1 L |
| 2.00 | Providing Vertical Expansion Joint filler dura board (closed cell, compressible, pre-moulded polyethylene based polymer joint filler board) 40mm thickness having density of 95Kg/m3 conforming to IS 1838(Pt 3) non staining with less than 1% water absorption and compression recovery of 93% minimum as per the specifications for RCC structures etc., including closing the expansion joint on either ends with suitable dura rod and finishing with polyurethane sealants for 12mm deep etc., complete as directed by the departmental officers. | 37.81 | M2 | 1,662 ₹62,840 | 1,500 ₹56,715 |
| 3.00 | Providing Horizontal Expantion joint of 40 mm thickness and 20 mm wide in between parapet walls at top of roof sarface finished with polysulphide sealant and weather proof finished with GI Sheet of 70 cm width per m length of 30 cm wide and 1.60 mm thickness using phill plugs, GI Screws etc., for the complet position as directed by the departmental officers. | 6.73 | RM | 750 ₹5,048 | 700 ₹4,711 |
| 4.00 | Supply and erection of 125 Amps capacity floor mounting type metering panel board (cubical type) with bus bar chamber made up of 16 swg CRCA sheet fully powdered coated for 3 phase 4 wire system with 25 x 3 mm copper bar for phases and neutral; cable chamber, switch chamber and with 2nos 25 x 3 mm Copper flat for the earth bus on the rear side of the panel board; necessary inter connections by copper flat of suitable sizes; suitable PVC colour sleeves for the inter connecting flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylem sheet separation between bus bar and switches, 3 nos of LED pilot lamps with switches,fues units, suitable angle iron frame of size of 37.5mm x 37.5mm x 6mm with powder coated painting over one coat of red oxide and numbering; superscription of cables sizes, capacity of switches etc., and incorporating the following. Outgoing:1.SINGLE PHASE SERVICES42 Nos, 25A 30 MA DP ELCB, 42 Nos of 32 A fuse unit,25mm x 3mm Copper flats for neutral and earth for outgoings, space provision for TNEB, Energy meter with glass coverBus capacity: A3 phase 4 wire copper Nos. Dummy provision Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 25A 30 MA DP ELCBNo Nos dummy provision all complete internal connection by 3 runs of 4 sq.mm PVC insulator usheathed copper conducter of 1100 V grade from TNEB cut out to the meter and and from the meter to the 25A 30 MA DP ELCB 3nos of LED Pilot lamps with fuse unit , switches and inter connection; inter connection to the bus bar by 25mm x 3mm Copper flats for phases and neutral from 100 A TPN SDF to the bus; inter connection by 8 SWG copper for the phases and neutral from the 25A 30 MA DP ELCB switch to the bus; 6mm thick hylem sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscribing on the panel board of the size capacity of cables, switches, location etc. 2 Nos of metallic danger boards as directed by the departmental officer in all complete. including lettering, erection and transportation charges. | 1 | Nos | 1,73,106 ₹1.7 L | 1,60,000 ₹1.6 L |
| 5.00 | Supply and erection of 125 Amps capacity floor mounting type metering panel board (cubical type) with bus bar chamber made up of 16 SWG CRCA sheet fully powdered coated for 3 phase 4 wire system with 25 mm x 3 mm copper bar for phases and neutral; cable chamber, switch chamber and with 2nos 25mm x 3mm copper flat for the earth bus on the rear side of the panel board; necessary inter connections by copper flat of suitable sizes; suitable PVC colour sleeves for the inter connecting flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylem sheet separation between bus bar and switches, 3 nos of LED pilot lamps with switches,fues units, suitable angle iron frame of size of 37.5mm x 37.5mm x 6mm with powder coated painting over one coat of red oxide and numbering; superscription of cables sizes, capacity of switches etc., and incorporating the following. Outgoing:1.SINGLE PHASE SERVICES48+1 Nos, 25A 30 MA DP ELCB 48 Nos , 32 A fuse unit,25mm x 3mm copper bar for neutral and earth for outgoings, space provision for TNEB, Energy meter with glass coverBus capacity: A3 phase 4 wire copper Nos. Dummy provision Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 25A 30 MA DP ELCBNo Nos of dummy provision all complete internal connection by 3 runs of 4 sq.mm PVC insulator usheathed copper conducter of 1100 V grade from TNEB cut out to the meter and and from the meter to the 32A DP MC Switch / 32A KA DP MCB 3nos of LED Pilot lamps with fuse unit , switches and inter connection; inter connection to the bus bar by 25mm x 3mm copper flats for phases and neutral from 100 A TPN SDF to the bus; inter connection by 8 SWG copper for the phases and neutral from the 25A 30 MA DP ELCB switch to the bus; 6mm thick hylem sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscribing on the panel board of the size capacity of cables, switches, location etc. 2 Nos of metallic danger boards as directed by the departmental officer in all complete. including lettering, erection and transportation charges. | 1 | Nos | 1,91,396 ₹1.9 L | 1,70,000 ₹1.7 L |
| 6.00 | Supply and erection of 125 Amps capacity floor mounting type metering panel board (cubical type) with bus bar chamber made up of 16 SWG CRCA sheet fully powdered coated for 3 phase 4 wire system with 25mm x 3 mm copper bar for phases and neutral; cable chamber, switch chamber and with 2nos 25mm x 3mm copper flat for the earth bus on the rear side of the panel board; necessary inter connections by copper flat of suitable sizes; suitable PVC colour sleeves for the inter connecting flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylem sheet separation between bus bar and switches, 3 nos of LED pilot lamps with switches,fues units, suitable angle iron frame of size of 37.5mm x 37.5mm x 6mm with powder coated painting over one coat of red oxide and numbering; superscription of cables sizes, capacity of switches etc., and incorporating the following. Outgoing:1.SINGLE PHASE SERVICES36 Nos, 36 Amps 25A 30 MA DP ELCB switches 36 Nos , 32 A fuse unit,25mm x 3mm copper flats for neutral and earth for outgoings, space provision for TNEB, Energy meter with glass coverBus capacity: A3 phase 4 wire copper Nos. Dummy provision Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 25A 30 MA DP ELCB2 Nos of dummy provision all complete internal connection by 3 runs of 4 sq.mm PVC insulator usheathed copper conducter of 1100 V grade from TNEB cut out to the meter and and from the meter to the 25A 30 MA DP ELCB 3nos of LED Pilot lamps with fuse unit , switches and inter connection; inter connection to the bus bar by 25mm x 3mm copper flats for phases and neutral from 100 A TPN SDF to the bus; inter connection by 8 SWG copper for the phases and neutral from the 25A 30 MA DP ELCB switch to the bus; 6mm thick hylem sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscribing on the panel board of the size capacity of cables, switches, location etc. 2 Nos of metallic danger boards as directed by the departmental officer in all complete. including lettering, erection and transportation charges. | 1 | Nos | 1,50,804 ₹1.5 L | 1,35,000 ₹1.4 L |
| 7.00 | Supply and erection of 100 Amps capacity floor mounting type metering panel board (Cubical type) with bus bar chamber made up of 16 SWG CRCA sheet for 3 phase 4 wire system with 25mm x 3mm tin coated copper flats for phases and neutral; cable chamber, switch chamber and with 2 Nos. 25mm x 3 mm tinned copper flat for the earth bus on the rear side of the panel board; necessary interconnections by copper flat of suitable sizes; suitable PVC colour sleeves for the interconnecting copper flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylum sheet separation between bus bar and switches; 3 nos of LED pilot lamps with switches, fuse units, suitable angel iron frame size of 37.5mm x 37.5 mm x 6mm with powder coated painting over one coat of red oxide and with numbering; superscription of cables sizes, capacity of switches etc and incorporating the following: Outgoings: 1. Three phase services 6 Nos.63A 4P MCB 63A fuse units 25mm x 3mm x 15mm copper flats for neutral and earth Space provision for TNEB energy meter with glass cover. Bus capacity: A3 phase 4 wire copper Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 6 Nos.63A 4P MCB 63A fuse units 3 Nos of LED pilot lamps with fuse units, switches / and interconnections; inter connection to the bus bar by 25mm x 3mm T C copper flats for phases and neutral from 100A TPN SDF to the bus; interconnection by No. 8 SWG copper for the phases and neutral from the 63A 4P MCB switch to the bus; 6mm thick hylum sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscripting on the panel board the size, capacity of cable, switches, location etc. 2 nos. metallic danger boards. | 1 | Nos | 49,153 ₹49,153 | 45,000 ₹45,000 |
| 8.00 | Supplying and laying of 3-1/2 x 70 sq. mm pvc armoured Aluminium LT UG cable of approved brand having ISI mark on post or wall with M.S clamps etc., complete in all respects | 138 | RM | 801 ₹1.1 L | 700 ₹96,600 |
| 9.00 | Supplying and fixing brass cable gland for 3 1/2 x 70 sq. mm PVC armoured LT UG cable with earth connection etc., complete in all respects. | 5 | Nos | 745 ₹3,725 | 700 ₹3,500 |
| 10.00 | Supplying and fixing cable end termination for 3 ½ x 70 sq.mm PVC armoured LT UG cable with earth connection etc., complete in all respects. | 5 | Nos | 455 ₹2,275 | 400 ₹2,000 |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
30 Oct 2025, 12:00 pmClosed
The Superintending Engineer, West Circle, TNUHDB
No.397A North Housing Unit, Selvapuram, Coimbatore - 641026.
Providing elevation works, panel board arrangements, expansion joint, erection and commissioning of lift arrangements for 125 nos of tenements G plus 5 at Kolanthakoundanur in Karur Corporation under AHP PMAY- HFA
2025_TNUHB_614521_1
SE/WC-CBE/01/2025
Open Tender
Civil Works - Buildings
120 days
Karur
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹70,000
13 Feb 2026
16 Oct 2025
31 Oct 2025
16 Oct 2025
30 Oct 2025
16 Oct 2025
Amount
Providing stucco plastering with CM 1:3 (one of cement and three of HBG stone chips) using HBG stone chips of size not grater than 10mm of thick 12 thick over plastered surface including cost of materials, labours, scaffolding, finishing and curing etc., completed in all respects as directed by tha departmental officer. (In all floors)
Providing Vertical Expansion Joint filler dura board (closed cell, compressible, pre-moulded polyethylene based polymer joint filler board) 40mm thickness having density of 95Kg/m3 conforming to IS 1838(Pt 3) non staining with less than 1% water absorption and compression recovery of 93% minimum as per the specifications for RCC structures etc., including closing the expansion joint on either ends with suitable dura rod and finishing with polyurethane sealants for 12mm deep etc., complete as directed by the departmental officers.
Providing Horizontal Expantion joint of 40 mm thickness and 20 mm wide in between parapet walls at top of roof sarface finished with polysulphide sealant and weather proof finished with GI Sheet of 70 cm width per m length of 30 cm wide and 1.60 mm thickness using phill plugs, GI Screws etc., for the complet position as directed by the departmental officers.
Supply and erection of 125 Amps capacity floor mounting type metering panel board (cubical type) with bus bar chamber made up of 16 swg CRCA sheet fully powdered coated for 3 phase 4 wire system with 25 x 3 mm copper bar for phases and neutral; cable chamber, switch chamber and with 2nos 25 x 3 mm Copper flat for the earth bus on the rear side of the panel board; necessary inter connections by copper flat of suitable sizes; suitable PVC colour sleeves for the inter connecting flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylem sheet separation between bus bar and switches, 3 nos of LED pilot lamps with switches,fues units, suitable angle iron frame of size of 37.5mm x 37.5mm x 6mm with powder coated painting over one coat of red oxide and numbering; superscription of cables sizes, capacity of switches etc., and incorporating the following. Outgoing:1.SINGLE PHASE SERVICES42 Nos, 25A 30 MA DP ELCB, 42 Nos of 32 A fuse unit,25mm x 3mm Copper flats for neutral and earth for outgoings, space provision for TNEB, Energy meter with glass coverBus capacity: A3 phase 4 wire copper Nos. Dummy provision Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 25A 30 MA DP ELCBNo Nos dummy provision all complete internal connection by 3 runs of 4 sq.mm PVC insulator usheathed copper conducter of 1100 V grade from TNEB cut out to the meter and and from the meter to the 25A 30 MA DP ELCB 3nos of LED Pilot lamps with fuse unit , switches and inter connection; inter connection to the bus bar by 25mm x 3mm Copper flats for phases and neutral from 100 A TPN SDF to the bus; inter connection by 8 SWG copper for the phases and neutral from the 25A 30 MA DP ELCB switch to the bus; 6mm thick hylem sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscribing on the panel board of the size capacity of cables, switches, location etc. 2 Nos of metallic danger boards as directed by the departmental officer in all complete. including lettering, erection and transportation charges.
Supply and erection of 125 Amps capacity floor mounting type metering panel board (cubical type) with bus bar chamber made up of 16 SWG CRCA sheet fully powdered coated for 3 phase 4 wire system with 25 mm x 3 mm copper bar for phases and neutral; cable chamber, switch chamber and with 2nos 25mm x 3mm copper flat for the earth bus on the rear side of the panel board; necessary inter connections by copper flat of suitable sizes; suitable PVC colour sleeves for the inter connecting flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylem sheet separation between bus bar and switches, 3 nos of LED pilot lamps with switches,fues units, suitable angle iron frame of size of 37.5mm x 37.5mm x 6mm with powder coated painting over one coat of red oxide and numbering; superscription of cables sizes, capacity of switches etc., and incorporating the following. Outgoing:1.SINGLE PHASE SERVICES48+1 Nos, 25A 30 MA DP ELCB 48 Nos , 32 A fuse unit,25mm x 3mm copper bar for neutral and earth for outgoings, space provision for TNEB, Energy meter with glass coverBus capacity: A3 phase 4 wire copper Nos. Dummy provision Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 25A 30 MA DP ELCBNo Nos of dummy provision all complete internal connection by 3 runs of 4 sq.mm PVC insulator usheathed copper conducter of 1100 V grade from TNEB cut out to the meter and and from the meter to the 32A DP MC Switch / 32A KA DP MCB 3nos of LED Pilot lamps with fuse unit , switches and inter connection; inter connection to the bus bar by 25mm x 3mm copper flats for phases and neutral from 100 A TPN SDF to the bus; inter connection by 8 SWG copper for the phases and neutral from the 25A 30 MA DP ELCB switch to the bus; 6mm thick hylem sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscribing on the panel board of the size capacity of cables, switches, location etc. 2 Nos of metallic danger boards as directed by the departmental officer in all complete. including lettering, erection and transportation charges.
Supply and erection of 125 Amps capacity floor mounting type metering panel board (cubical type) with bus bar chamber made up of 16 SWG CRCA sheet fully powdered coated for 3 phase 4 wire system with 25mm x 3 mm copper bar for phases and neutral; cable chamber, switch chamber and with 2nos 25mm x 3mm copper flat for the earth bus on the rear side of the panel board; necessary inter connections by copper flat of suitable sizes; suitable PVC colour sleeves for the inter connecting flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylem sheet separation between bus bar and switches, 3 nos of LED pilot lamps with switches,fues units, suitable angle iron frame of size of 37.5mm x 37.5mm x 6mm with powder coated painting over one coat of red oxide and numbering; superscription of cables sizes, capacity of switches etc., and incorporating the following. Outgoing:1.SINGLE PHASE SERVICES36 Nos, 36 Amps 25A 30 MA DP ELCB switches 36 Nos , 32 A fuse unit,25mm x 3mm copper flats for neutral and earth for outgoings, space provision for TNEB, Energy meter with glass coverBus capacity: A3 phase 4 wire copper Nos. Dummy provision Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 25A 30 MA DP ELCB2 Nos of dummy provision all complete internal connection by 3 runs of 4 sq.mm PVC insulator usheathed copper conducter of 1100 V grade from TNEB cut out to the meter and and from the meter to the 25A 30 MA DP ELCB 3nos of LED Pilot lamps with fuse unit , switches and inter connection; inter connection to the bus bar by 25mm x 3mm copper flats for phases and neutral from 100 A TPN SDF to the bus; inter connection by 8 SWG copper for the phases and neutral from the 25A 30 MA DP ELCB switch to the bus; 6mm thick hylem sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscribing on the panel board of the size capacity of cables, switches, location etc. 2 Nos of metallic danger boards as directed by the departmental officer in all complete. including lettering, erection and transportation charges.
Supply and erection of 100 Amps capacity floor mounting type metering panel board (Cubical type) with bus bar chamber made up of 16 SWG CRCA sheet for 3 phase 4 wire system with 25mm x 3mm tin coated copper flats for phases and neutral; cable chamber, switch chamber and with 2 Nos. 25mm x 3 mm tinned copper flat for the earth bus on the rear side of the panel board; necessary interconnections by copper flat of suitable sizes; suitable PVC colour sleeves for the interconnecting copper flats / rigid copper wire; earth connections to all switches / bus bar by copper flats of suitable sizes from the earth bus; hylum sheet separation between bus bar and switches; 3 nos of LED pilot lamps with switches, fuse units, suitable angel iron frame size of 37.5mm x 37.5 mm x 6mm with powder coated painting over one coat of red oxide and with numbering; superscription of cables sizes, capacity of switches etc and incorporating the following: Outgoings: 1. Three phase services 6 Nos.63A 4P MCB 63A fuse units 25mm x 3mm x 15mm copper flats for neutral and earth Space provision for TNEB energy meter with glass cover. Bus capacity: A3 phase 4 wire copper Internal connections by 2 runs of 4 sq.mm PVC insulator unsheathed copper contactor of 1100 V grade from TNEB cutout to the meter and from the meter to the 6 Nos.63A 4P MCB 63A fuse units 3 Nos of LED pilot lamps with fuse units, switches / and interconnections; inter connection to the bus bar by 25mm x 3mm T C copper flats for phases and neutral from 100A TPN SDF to the bus; interconnection by No. 8 SWG copper for the phases and neutral from the 63A 4P MCB switch to the bus; 6mm thick hylum sheet separation between bus bar chamber and switches chamber; insulators for the support for the bus; superscripting on the panel board the size, capacity of cable, switches, location etc. 2 nos. metallic danger boards.
Supplying and laying of 3-1/2 x 70 sq. mm pvc armoured Aluminium LT UG cable of approved brand having ISI mark on post or wall with M.S clamps etc., complete in all respects
Supplying and fixing brass cable gland for 3 1/2 x 70 sq. mm PVC armoured LT UG cable with earth connection etc., complete in all respects.
Supplying and fixing cable end termination for 3 ½ x 70 sq.mm PVC armoured LT UG cable with earth connection etc., complete in all respects.
Supply and fixing of 50mm dia GI pipe of approved brand having ISI mark etc., complete in all respects
Supplying and fixing of 3 Nos., of 100 A porcelain fuse units 500 volt of approved brand having ISI mark in T.W. Board of suitable size etc., complete in all respects.
Design, Engineering, Supply, Fabrication, Erection, Testing, commissioning and handing over of 1 no of 10 passenger lift as per the following specifications including taxes and duties. (Gearless lift without machine room)1.Location: Kolanthakoundanur Scheme 2.No of lift: 1 no. (Gearless) 3.Type of lift: passenger lift 4.Capacity of lift: 10 persons /1020 kg conforming to 14665 (part 1) 2000 5.Speed: 1.5 M / Sec 6.Type of drive: V3F drive with enhanced ride comfort and near zero level functions 7.No of floors: G+5 Floor 8.Total travel: 2.9 mts x 6 Landing = 17.40 mts 9.Leveling accuracy: high level accuracy with smooth and jerk free stopping 10. Construction of CAR: No. 4 hardened sheet high quality stainless steel car and hand rail granite flooring and Perspex false ceiling. 11. Position of machine: directly above the lift well. 12. No of landing service: One in the front side- 1 no. 13. No. of car entrance: one in the front side only 14. Car entrance door: power operated automatic V3F drive center opening sliding SS door 15. Landing entrance door: power operated V3F drive center opening sliding SS door with provision for emergency exit key at all landings.16.Lift well : As per structural design conforming to IS 14665(part1) 2000 to be constructed by the Building contractor 17.Lift pit depth: conforming to 14665 (part 1)2000 18. Car inner size, Total weight of person and Overhead height : conforming to 14665 (part 1)2000 19. Car clear opening: 900 mm wide x 2000 mm height as per IS 14665 (part 1)2000 20.Lift machine room size: as per ISI 14665 (part 1) 2000 to be constructed by the building contractor 21. Power supply: 400 / 440 v three phase 50 Hz AC supply for power and 230 V 50 Hz single phase power supply for light. 22.Control: micro computer (micro processor):based simplex collective control with / without attendant 23. Car fittings: CFL lighting with 1 no 300 mm sweep cabin fan. 24. Lift well: RCC construction with brick masonry to be constructed by the building contractor 25. Induction: UP / DOWN digital direction and floor position indicator for all landings in all floors and inside the car. 26.Emergency alarm bell: battery operated bell to be provided with automatic charging device 27.Emergency light: battery operated light to be provided with automatic charging device 28.Fire mans switch: to be provided at the GF 29. Minor builder works: to be provided by the lift contractor.(S&F of bulk head, 5A switch, light point, wiring 2 of 2.5 sqmm at every floor and machine room lighting, 4way/8way/12 way TPN DB, fuses of required capacity) and other requirements.
30. Scaffoldings: to be provided by the lift contractor. 31. Sill angles and facia plates: SS to be provided by the lift contractor. 32. Steel for lift machinery: to be provided by the lift contractor. 33. Servicing and maintenance: free comprehensive servicing and maintenance for one year Guarantee period to be provided by the lift contractor. 34. Automatic rescue device: to facilitate the landing of the nearest floor at the time of power failure this shall consist of suitable battery system with charger inverter under voltage protection system etc. complete with all accessories and single phase preventor specifying to IS norms 35. Provision for intercom with phone: to be provided by the lift contractor. 36.Lift license: preparation of drawings payment of charges to CEIG and insurance policy for both lift & body if any and obtaining CEIG approval for the lift as per lift act should be done by the lift contractor 37. Floor position announcer: to be provided by the lift contractor. 38.Special features a) Infra red door sensor with full height screen b) Full width half height rear panel mirror c)Tubular SS hand rail in car d) Stainless steel signal features e) Vandal proof SS button with SS cover f) SS door frames for landing doors g) V3F door operator h) Call register signal i) Stainless steel facia plates for car operating panel and landing fixtures j) Steel ladder for lift machine room k) On / off switch for fan and light l) Over load warning indicator with audio announcer m)Voltage stabilizer for control circuits n)Braille button o) Precautionary measures etched in SS plate 39.Over speed governor phase failure and phase reversal relay alarm bell T guide brackets for car and counter weight rubber padding under the winding unit motor of adequate capacity signal reduction worm gear electromagnetic brake with compression springs car safety gears buffers electro mechanical locks emergency key side supporting angles motor over load protection devices final limit switch main suspension ropes counter weight lifting joist for mounting the machineries 40. Guarantee: guarantee at least for one year for the material and workman ship of equipments should be offered by the lift contractor. 41. Site testing in accordance with IS 14665 should be carried out at the time of handing over to the user department 42. Supply operation and maintenance manual and necessary tools for operation and a set of Spare parts required for one year 43.All the features as per differently abled person Act should be provided. 44. 2 hrs.fire retardent landing doors . Passenger lift 10 person capacity
Earthing as per ISI Specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm and with 20mm dia copper earth flat of size125mm x 50mm x 6mm, with funneling arrangement using charcoal, common salt, G.I.reducer, check nuts etc., and mansonry work and providing RCC cover slab 38mm thick for the Brick mansory including costof steel and fabrication of reinforcement etc.,complete in all respectes as directed by the departmental officers.
Supply and run off 25mm x 6mm GI strip Flat Down Condutor with necessary clamps/ supports on wall / floor /ground for earth connection etc., complete in all respectes as directed by thedepartmental officers.
Supply, erection testing, commissioning and handing over of diesel generator set 0.80 P.F, 3phase, 415v/420 Volts, 50c/s, 1500 RPM complete in all respects as detailed below. CPCB IV complaint DG set . 58.5 kVA, with Standard panel A. Engine Liquid Cooled / Water cooled diesel engine suitable for generator application with a shaft out put of ( 84HP/50KW with respect to the make of generator) suitable at 1500 RPM under NTP conditions as per BSS 5414-ISO 10000. The engine shall comprise the following standard scope of supply: (Make Kirloskar/ Cummins/ Ashok Leyland/ Greaves/ Equivalent) 1) Dry type Air cleaner 2) Expansion bellow 3) Radiator, radiator fan and mounting 4) Air to air charge cooler 5) Exhaust gas turbo charger 6) Lube oil cooler and lube oil filter filter 7) Fuel filter (pre and micro) 8) In-line mono-block fuel injection pump with governor and fuel feed pump 9) Mechanical / Electronic governor 10) 12V / 24V battery charging alternator 11) 12V / 24V Volt electric starter motor 12) Engine test certificate 13) Residential Mufler 14) Fly wheel with starter ring. (C)ENGINE INSTRUMENT PANEL MOUNDING: Engine instrument panel /mounted engine control panel consisting of ON/OFF/START/KEY, lube oil pressure gauge, oil temperature gauge, high water temperature gauge and electronic hour Mtr and RPM indicator. Safety system of Engine: The engine shall trip for the following conditions with Visual alarm device. 1) Low lubricating oil pressure 2) High water temperature 3) Vee- belt failure and over speed 4) Low battery indication. The Engine should be capable of Providing 10% over load for one hour for every 11 hours Continuous Running at full load. (D) ALTERNATOR: 58.5 KVA capacity of brushless alternator AC 3 phase 50 c/s 415 volts, 0.8 PF 1500 RPM under NTP conditions confirming to IS 13364 (part II) 1992 to be means of coupling. (H)ACOUSTIC ENGLOSURE : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS Sheet . The silent canopy shall be of nut bolt type construction. Critical processes of punching are done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm . Power coating is done after seven – tank surface preparation process of sheet metal canopy panel and doors shall have inside lining of Fire Retardant 64 Kg / Cu Mt Density Mineral wool of 100 mm thick ness as acoustic material . Four hinged doors shall be provided to canopy.
The maximum permissible sound pressure level should be as per the norms prescribed by the central pollution control board/state pollution control Board/Competent Authority concerened or shouble be 75 db (A) at 1 mtr from the enclosure surface whichever is advantageous to the department.The emergency stop should be available on the enclosure panel The Engine Manufacturer of the Engine provided for diesel Generator sets mounted inside and should be to the satisfaction of inspection / testing authority concern.SURFACE TREATMENT – PAINTING: The enclosure surface hall be suitably treated for degreasing . degusting and posphating . The canopies are passed thought seven – tank treatment thoroughly. ADDITIONAL FEATURES OF CANOPIES :- Canopy fabricated on CNC machine with dimensional accuracy of 0.1 mm so as to increase its durability . special designed supporting rips / structures are used in canopies so as to give sturdiness and to reduce the vibrations of the DG sets if any.WORLD CLASS COOLING PACKAGE:- Canopies shall have cooling package for which it can also perform at 45 deg c / ambient Temperature. No grouting required on the ground , only a level surface capable of with standing the DG weight . Lifting hooks shall be provided for the acoustic enclosure , which should unloaded independent of the DG set . the Gen set base frame shall also provided with hooks for unloading TEMPERATURE RISE INSIDE THE CANOPY: Canopies shall be designed so as to maintain the temperature difference between ambient and air inlet at air cleaner with the enclosure well within 5 – 7 Degree Centigrade. (G)BASS FRAME: Base frame should be fabricated MS Channel sheet Metal , The base frame is rigged in construction and designed for mounting engine and brush less alternator closely coupled . with cross members mounted on AVM . The base frame shall have provision for mounting of acoustic enclosure on it . The supply of Gen set includes loading , unloading and transportation charges .6) Fuel Tank: 100 Ltrs. and above (with respect to the make of generator) Removable Fuel tank shall be fabricated out of 14 SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet an outlet connections and mechanical fuel gauge. Fuel tank can be easily removed for cleaning or any maintenance. 7) Battery: 12V 100 AH battery-1 NO
Supplying and laying of 3-½ x 70 sq.mm PVC armoured aluminium LT UG cable of approved brand having ISI mark in a trench to be excavated to a depth of 0.75 meter, putting 0.15 m layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good etc., complete in all respects.(Below G.L)
Supplying and run off 8 SWG copper wire on walls or below ground level with necessary 'U' nail,earth work excavation and refilling inclusive of the costll materials etc complete in all respects as directed by the departmental officers
Open Earthwork excavation for foundation in all soils and subsoils and to the required depth as may be directed except hard rock requiring blasting inclusive of shoring, strutting and bailing out water wherever necessary depositing the surplus earth in places shown and levelling the site with all leads and lifts etc., complete in all respects as directed by the departmental officers. Initial lead of 10m and initial lift of 2.0 m
Filling in foundation and basement with M sand in landyers not exceeding 15 cms thick well watered rammed and consolidated complying with relevant standard specification including the cost of supplying M sand etc., complete in all respects as directed by the departmental officers.
Cement concrete 1:5:10 (one of cement, five of sand and ten of hard broken stone) using 20mm size hard broken stone for foundation inclusive of shoring, strutting, bailing out water, ramming, curing, etc complete as directed by the departmental officers
Providing and laying in position, Standardised Concrete Mix M-30 Grade in accordance with IS 456-2000, using 20mm and down graded hard broken granite stone jelly for all RCC tems of works with minimum cement content of 400 kglm3 and maximum water cement ratio of 0.45, including admiture (plasticiser super plasticiser) recommended proportions as per IS:9103 to accelerate, retard seting of concrete, improve workability without impairing strength and durability with about (5.0 cu.m.) 7730 kg. of 20mm machine crushed stone jelly and with about (3.3 cu.m.) 5156 kg of 10-12mm machine crushed stone jelly and with about (4.79 cu.m.) 7670 kg of M-Sand, but excluding cost of reinforcement gril and fabricating charges, centering and shuttering and also including laying. vibrating with mechanical vibrators, fnishing. curing. etc. and providing fixtures like fan clamps in the RCC floor roof slabs wherever necessary without claiming extra, etc complete complying with standard specification and as directed by the departmental officers. The coarse and fine aggregates to be used should comply with the requirements of IS Standards. (No separate payment will be made by the Department for the excess usage of materials).
Providing form work for centering, shuttering etc for all reinforced concrete work as plinth beam, raft beam, raft slab, grade beam etc, including shuttering. 3.00mm high using MS sheet of size 90cm x 60cm and BG 10, stiffened with MS angle of size 25mm x 25mm x 3mm laid over silver oak (Countrywood) joists of size 10cm x 6.5 cm (Spaced about 91cm center to center) distance and supported by casurina props of size 10cm-13cm dia (spaced at 75 cm center to center) and removing the same after a specified period without damaging RCC works in all foors etc, complete as directed by the departmental officer.
Fabricating and placing the following kinds of steel grills Fe 550 D grade steel reinforcement bars as per IS 786-1979 for all reinforced cement concrete works such as plinth beam, lintels, beams, sunshade, roof and floor slabs etc., including cost of steel and fabricating the reinforcement grills in position etc., complete in all floors (The rate to include the cost of binding wire steel also)
Supply and fixing of Fire fighting application oblique type stainless steel Hydrant Valve of size 63mm – dia with oblique type instantaneous coupling with rotating wheel to open and close the valve including MS flange of table “E”, bolts & nuts with washer as per IS 5290 at ring main around the building and wet riser inside the building including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. (Make; OMEX/KARTER/LIFE GUARD/SAFE GUARD/EQUIVALENT.
Supply, Installation of Fire fighting application 180 degree swinging type, hose reel drum with 20 mm dia braided thermoplastic hose of 30 meters long so as to extent to necessary distance by self rolling spindle wheel including necessary 20mm dia ball valve & open & close spray nozzle, warm clip, etc., as perthe standard pattern of any reputed make at every floor nearer to hydrant valve, including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. Make:OMEX/KARTAR/LIFEGUARD/SAFE GUARD/EQUIVALENT.
Supply, and fixing in position of Fire fighting application Hose of 63mm dia of 15mts length binded by copper wire with 63mm dia Stainless steel male and female instantaneous fire fighting special coupling as per IS 901 as directed by the department officers Near every hydrant points including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers.(Make:OMEX/KARTAR/LIFEGUARD/SAFE GUARD/EQUIVALENT.
Supply, and fixing in position of Fire fighting application 63mm dia stainless steel short length Branch Pipe with hexagonal type spray nozzle of 15mm (or) 20mm jet bore. Near every hydrant points including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. (MAKE: OMEX/KARTAR/LIFE GUARD/SAFE GUARD/EQUIVALENT.
Supply and Fire fighting application M.S. Hose Box to keep two numbers of Hoses and one number of branch pipes with nozzle. having proper glass window type double door with universe open key, painted inside white and outside PO red. Near every hydrant point including conveyance, all incidental charges, necessary scaffolding and re- doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. (Make: OMEX/KARTAR/LIFE GUARD/ SAFE GUARD/ EQUIVALENT.
Supply, erection, testing and commissioning of MS ‘C’ Class heavy duty pipe as per IS 1239,to withstand a developing pressure of 10kg/sq.cm including necessary fittings like MS flange of table ‘E ‘ Elbows, reducers, gaskets, both, nuts with washers & Joints as per standard method of arc welding .Including one coat metal primer and two P.O RED painting including conveyance ,all incidental charges ,necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. Make; JINDAL/EQUIVALENT.
100 mm dia
80 mm dia
Supply ,erection, testing and commissioning of Cast iron body and bronze internal non-rising spindle sluice valve of 100 mm dia size at required places to control the flow of water including necessary MS flange of table ‘E’ gaskets , bolts & nuts including conveyance all incidental charges ,necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers.Make:NORMEX/KARTAR
Supply, erection, testing and commissioning of Cast iron body and Gun metal or stainless steel internal Non-return valve of 100 mm dia sizes to control one way flow of water to be installed pump room at delivery line and near overhead, tank at terrace level near to jockey pump and motor including necessary MS flange of table ‘E’, gaskets, bolts & nuts, etc. as per IS 5312. including conveyance, all incidental charges, necessary scaffolding and re-doing dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers.
Supply and laying of following sizes of armoured Aluminium/Copper cables for electrical motor. control Panel, Pressure switch, jockey motor etc. all incidental charges necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc. Make.POLYCAB/PARACON/FINLOEX/EQUIVALENT
3 core 10 sqmm armoured copper cable
2 core 2.5 sqmm armoured copper cable
Supply, erection, testing and commissioning of pressure Gauge with 0 to 14 kg range of reputed make with necessary value, milling thread Ms coupling fixed at delivery pipe line in pump house to read the developing pressure including conveyance. All incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc. complete as per standard specification and as directed by the departmental officers. Make: H-GURU/ISIMARK/EQUIVALENT.
Supply, erection, testing and commissioning of suitable Pressure switch of reputed make line indfoss or Donfoss including necessary values, couplings etc. connected with electrical main control panel and setup at proper differential so as to auto start& auto stop the electrical motor. Jokey motor including conveyance. all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary metering protections & indications complete as per standard specification and as directed by the departmental officers. Make: DONFOSS/INFOSS/ISIMARK/EQUIVALENT.
Supply erection testing and commissioning of fire fighting application mono block motor pump set of 900 LPM at 40 meters head to develop 3.5 kg/sq.cm at the highest and farthest hydrant point to make 30m water jet the time of fire fighting emergency circumstances, coupled with 11 KW/15 HP rated three phase 414 v,50 Hz ,2880 rpm electrical motor the pump with cast iron body, bronze impeller, rope gland packaging, suction size of 80 mm dia, delivery size of 65 mm dia, including the cost of foundation concrete anti vibration mounting, rain safety hood and etc..(Make: kirloskar)
Supply, erection, testing and commissioning of Fire fighting 4 way fire brigade inlet with necessary Gun metal 63 mm dia non return spring shutter arrangements so that to control one way flow at the time of emergency water supply by fire and rescue service fire engine entry, including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. Make : KIARTAR/OMEX/ EQUIVALENT
Supply and fixing of stored pressure ABC (Mono Ammonium Phosphate) powder type Fire Extinguisher of 6 kgs capacity as per IS: 15683 with pressure gauge, discharge hose & control nozzle, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary etc complete as per standard specification and as directed by the departmental officers. Make: EXCELLENT/SAFETY FIRST/ EQUIVALENT
Added GST of 18% (All Items)
SRP CONSTRUCTION COMPANY (BID ID -1499305)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
Ter_Doc_Kolantha_Dev.pdf
Tender Documents • 1.79 MB
BOQ_734203.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid