| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹84.9 LAccepted-AOC 4578 STREET 15 15A AGGARWAL ROAD DARYAGANJ CENTRAL DELHI DELHI 110002 | CENTRAL DELHI | DELHI | 110002 | L1 | Accepted-AOC L1 | |
| 2 | L2₹87.9 L+₹2.6 L (3.04%)Rejected-AOC A 04 ADGNJ CHANDAN NAGAR OPP IOCL PETROL PUMP RAMPUR ROAD BAREILLY U P 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | L2 | Rejected-AOC L2 | |
| 3 | L3₹98.6 L+₹13.3 L (15.6%)Rejected-AOC 2 2407 GILL COLONY NARAINPURI SAHARANPUR UP | SAHARANPUR | SAHARANPUR | UTTAR PRADESH | 247001 | L3 | Rejected-AOC L3 | |
| 4 | L4₹1.0 Cr+₹15.4 L (18.1%)Rejected-AOC 301 TULSI TOWER KHADAKPADA KALYAN THANE MAHARASHTRA 421301 | THANE | MAHARASHTRA | 421301 | L4 | Rejected-AOC L4 |
Tender Value
₹86.6 L
EMD Value
₹1.6 L
Closing Date
3 Sept 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Dehradun
HQ CWE Dehradun
SPL REPAIR TO HT ELECTRIFICATION SYSTEM AND ALLIED WORKS IN MRS GARHI CANTT DEHRADUN
2022_MES_541939_1
9742/DDN/E8
Open Tender
Civil Works
Item Rate
120 days
Dehradun
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,000
GE Dehradun
₹1.6 L
Yes
1 Nov 2022
29 Jul 2022
5 Sept 2022
29 Jul 2022
3 Sept 2022
20 Aug 2022
Amount
Taking down Out Door HT 33 KV VCB from MRS Garhi Cantt, carefully duly disconnecting the existing connection with out damaging any other connection parts and deposit to MES store yard.
Supply, Install, Testing and commissioning Vacuum Circuit Breaker(VCB) Out Door Type tested, factory made HT 33 KV, 1250 Amps , 25 KA (With required structure) with 1Nos of Microprocessor based digital and compatible for SCADA operation Relay for 3 phase, 50 cycles totally enclosed metal clad switchgear complete with VCB having rupturing capacity 350 MVA , overload and earth fault protection, ammeter, voltmeter and of rating up to 1250 Amp, and all connecting and measuring accessories including foundation etc complete all as specified and directed by Engr-in-Charge with following components :- Note :- HT Panel shall be manufactured and inspected at Principle manufacture only.
Basic Unit
Housing for 33kV Indoor C&R Panel 01 No.
Meters
Digital Ammeter with S/S -96 sq mm Cl. 1 Accuracy 01 No.
Digital Voltmeter with S/S -96 Sq mm Cl. 1 Accuracy 01 No.
Electronic Tri Vector Meter (TVM) ( Acc. 0.5), L&T-ER300P - Projection type 01 No.
Multi Function Meter - Communicable 0.5 Accuracy 01 No.
LED Indicating Lamps
Breaker On Red 01 No.
Breaker Off Green 01 No.
Spring Charged Blue 01 No.
Trip Circuit Healthy White with Push Button 01 No.
Auto Trip Indication Amber 01 No.
R/Y/B Phase Indication 01 No.
Accessories
Trip Neutral Close (TNC) Switch 01 No.
Heater with Thermostat & Switch 01 No.
Illumination Lamp with Switch 01 No.
3 Pin Plug Socket with Switch 01 No.
Hooter
Schemes
Common Alarm Scheme 01 No.
Annunciation window - Per window 08 No.
Protection Relay & Auxiliary relays of Electromechanical / Static type
TFR Differential Relay Communicable Type having MODBUS protocol Aegis T 01 No.
2 Nos. Auxiliary Relay for Buchollz A/T, Winding Temp Indicator (WTI) A/T and Oil Temp Indicator (OTI) A/T .
1 No., Trip Circuit Supervision Relay type XR351 of ER .
1 No., Master Trip Relay type B24 of ER.
Taking down indoor HT 11 KV VCB along with indoor CTs& PTs from MRS Garhi Cantt, carefully duly disconnecting the existing connection with out damaging any other connection parts deposit to MES tore yard.
Supply, Install, Testing and commissioning HT 11 KV, indoor, IP 4X, 630 Amp, 25 to 40 KA,3 phase 50 Hz, Copper Bus bar of Rating not less than 800 Amps for 3 Phase, Air insulated withdraw able Vacuum Circuit Breaker (VCB) in powder coated steel enclosure Structure .
Note for srl item No. 2 & 4.
Power & control cable termination kits, glands, lugs, etc is included in the scope work and the cost of same shall be included in the quoted rates.
Cost of any extra item which is essential requirement for the functioning of VCB is deemed to included in the quoted rates.
HT panels and connected switch gear, VCBs shall be the of same make/manufacturers or as approved by AO from the make specified in particular specification.
HT panels and connected switch gear, VCBs shall be tested at OEM factory by the rep of Accepting officer. The Accepting Officer, has to detail his representative to witness the factory testing (routine tests as per IS) of VCB including HT panel at the OEM, manufacturer’s factory premises. For this the contractor shall give one months notice to the GE and Accepting officer for consideration by AO and detailing the rep. Quoted rate shall be inclusive of testing charges and the testing charges shall be borne by contractor.
VCB and numerical Relay in Panel shall be of same make of principle manufacture only.
Test certificate, Purchase vouchers, Factory Inspection Report & Guarantee Card shall be submitted to GE along with RAR & Final Bill.
Approval of technical drawing of equipment shall be obtained from GE as per site requirement and technical specification laid down in CA
Supply, Install, Testing & Commissioning of Battery Bank 110V/50A FCBC battery charger with 110V/200 Ah battery bank with rack should be designed by the OEM of VCBs and connection, installation and commissioning should included to feed all new indoor & Out door VCBs, & Control Panels and all accessories complete all as specified and directed with the following specifications :-
(i) Environmental conditions- 1. Max ambient temp - 45deg.c 2. Designed ambient temperature - 50deg.c 3. Relative humidity -95%
(ii) Mains input parameters:- 1. Input voltage :- 415V , 3phase ,4 wire +/-10% 2. Input voltage variation :- 373-456vac 3. Input supply frequency :- 50hz 4. Input supply frequency variation :- 50hz+/-5% (47.5hz-52.5hz) 5. Input current at no load :- less then 1.0a 6. Input power factor at 100% load & nominal input voltage :- batter than 0.85 (leg) 7. Over all efficiency at 100% load & nominal input voltage :- batter than 90%
(iii) Output parameters( fcbc charger) :-1. Output voltage max. :- 130 vdc max. float mode :- 124v(adjustable-80-125v) boost mode :-129v (adjustable-80-130v) 2. Output current :- 30a max 3. Output ripple ( at nominal .input volt.) :- 1% RMS (max.) 4. Output regulation: - 1%.
(iv) General parameters :- 1. Topology :- full bridge 6 pulse thermistor digital controller 2. Cooling :- natural air flow 3. Designed ambient temp. :- 50 deg. c 4. Panel enclosure :- 2mm/1.5mm CRCA sheet enclosure, with powder coated dimensions (+/-10mm) :- hight-1375mm, width-700mm, depth- 600mm
(v) Controls & indications:- 1. Input & output indication :-colour code d r (for ac ) and green (for output ) 2. Output voltage & current setting :- respective potentiometers will be provided on the door. 3. Metering :- AC mfm with rs 485 dc voltmeter with s/sw DC ammeter (total current) dc ammeter for battery charger /discharge current.
(vi) Protections:- 1. Mains input side :- MCB 2. Output battery side :- MCB , current limiting, blocking diode ,dropper dodes 3. Enclosure protection class :- IP-42
(vii) DC –DC converter: - 1. DC input - 110v DC(80-140VDC)
Supply, Laying at existing cable duct, connecting up and testing control cable 12 core 2.5 Sqmm electric power cable with stranded copper complete all as specified and directed.
Supply, Laying at existing cable duct, connecting up and testing cable XLPE insulated galvanised steel strip or wire armoured electric power cable with stranded aluminium conductor 11000 V grade (Earthed) of size 185 sqmm 3 core complete all as specified and as directed.
All as per item No 7 here-in-above but cable of size 300 sqmm 3 core
S&F Cable Jointing Kit for 11 KV grade for indoor termination, heat shrink type joint with complete jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 Sqmm complete all as specified and as directed.
S&F Cable Jointing Kit for 11 KV grade for outdoor termination, heat shrink type joint with complete jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 Sqmm complete all as specified and directed.
M&L for earthing complete with GI earth plate electrode 600x 600x 6mm thick, buried directly and preferably vertically in ground, earth pit not less than 2.25 m below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI wire 4 mm dia by means of nuts, bolts, check nuts and washers made of GI or steel earthing lead to be protected by GI pipe 20 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch all as shown in electrical plate No 3 of SSR Part-I 2009 including providing funnel with 20mm bore GI pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded stone aggregate), 50mm thick precast RCC (1:2:4) type B-1 using 20mm graded stone aggregate cover slab (reinforced with 8mm dia TMT bar @ 15 cm C/C both ways and suitable handle made of 10mm dia), with 40x40x6mm MS angle iron frame including necessary earth work and testing on completion complete all as specified and directed.
M&L for Earth Continuity Conductor or main earthing strip fixed to wall on batten or porcelain insulators or recess or chases or buried in ground or drawn in GI pipe 40 mm or fixed with poles or any other indicated situation for loop earthing etc as required using GI strip of size 25x4 mm complete all as specified and directed.
Supply and laying synthetic Rubber insulated mats 2.5 mm thick for voltage up to 11 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
M&L for PCC 1:3:6 type C2 (using 40mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed.
BHARAT ELECTRICAL TRADERS
RAMAPATI ENGINEERING SERVICES
Diamond Electric Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .