Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹18.2 L+₹72,310 (4.14%)Rejected-Finance 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L2 | Rejected-Finance L2 | |
| 3 | L3₹18.5 L+₹98,758 (5.65%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹16.4 L
EMD Value
₹32,100
Closing Date
27 Jan 2022, 10:00 amClosed
Executive Engineer
Elect. Division HPPWD Palampur
Replacement of Existing addressable fire alarm system and PA system at HP Vidhan Sabha Tapovan Dharamshala Distt. Kangra (HP)
2022_PWD_55722_2
Elect. Division HPPWD Palampur
Open Tender
Electrical Works
Item Rate
365 days
Tapovan at Dharamshala in Distt. Kangra
Please refer Tender documents.
12 documents required · 12 mandatory
₹500
₹32,100
13 Mar 2023
15 Jan 2022
27 Jan 2022
15 Jan 2022
27 Jan 2022
15 Jan 2022
Amount
Supply, Installation, Testing and Commissioning of Microprocessor based Intelligent Addressable Main Fire Alarm Control Panel with Suitable Loops modules and each loop capable of supporting not less than 250 devices (detectors & modules should be in any combination) ; Loop length up to 1.5 km, 8" Color LCD touch screen display with bright colors to indicate alarms and events, 4 Nos of Integrated Ethernet Ports & 2 Nos of RS 485 for networking, 200 Nos of Soft programmable keys with status indicators for individual triggering of NAC Ouputs, evacuation speaker zones, AHU Modules, Damper switch, Smoke extraction Fans, Lifts.. etc. The Panel shall support 10000 history logs in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 24 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger.The panel should also have IP30 or better protection. The panel shall have seamless integration with EVAC certified Public Address System and shall be complete with all accessories . EN54 / Vds/UL Certification Make Autronica/ Notifire / Bosch/Siemens EN
Supply, Installation, Testing and Commissioning of Active and networkable repeater panel with 4x20 character LCD display complete system function keys for programming and control like system reset, alarm acknowledgement, alarm silence, trouble acknowledgement etc. Shall be UL/EN/VDS Listed Make Autronica/ Notifire / Bosch/ Siemens EN
Supply, Installation, Testing and Commissioning of addressable multisensor smoke detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values.Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Make Autronica/ Notifire / Bosch/Siemens EN
Supply, Installation, Testing and Commissioning of addressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Make Autronica/ Notifire / Bosch/Siemens EN
Supply, Installation, Testing and Commissioning of addessable Single ACTION manual pull station & necessary fixing arrangements with key complete as required. MCP should have IP40 or better protection rating Shall be UL/EN/VDS Certified. Make Autronica/ Notifire / Bosch/ Siemens EN
Supply, Installation, Testing and Commissioning of Addressable Monitor Module with 1 input, which shall monitor normally open or normally closed contacts.The module shall have an LED to indicate module status.It Shall be UL/EN/VDS Certified. Make Autronica/ Notifire / Bosch/ Siemens EN
Supply, Installation, Testing and Commissioning of Response Indicaters Make Autronica/ Notifire / Bosch/Siemens EN
Supply, Installation, Testing and Commissioning of Addressable Control Relay Module with inbuilt isolators as per NFPA 72 style 7 wiring requirements .Relay Control module shall be used for emergency control functions including shutting down Fire dampers in AHU's, tripping of AHU's, Fresh air fans, Ventilation fans, tripping of Access control doorsetc.. Shall be EN54/ Vds Certification/UL Make Autronica/ Notifire / Bosch/ Siemens EN
Supply, Installation, Testing and Commissioning of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class – 1 material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work Make PES/Giolite/ OMEX
Supply, installation, testing & commissioning of wall mounted cabinet speaker of 6W RMS power with multi taps 3''of 6W/3W/1.5 W, handling capacity, inbuilt 100 volt line matching transformer, wide opening angle, optimized for music and speech application complete with mounting clamps.Make Autronica/ Honeywell/ Bosch/Siemens EN
Supply, Installation, Testing and comissioning of 2 core multistrand 1.5 sq mm annealed copper conductor speaker cable in existing pipe/ channel I/C connection etc.Make Finolex/Polycab/havel's
Supply, Installation, Testing and comissioning of single core multistrand 1.5 sq mm annealed copper conductor speaker cable in existing pipe/ channel I/C connection etc.Make Finolex/ Polycab/ havel's
Insat Techno Services
AVNET SOLUTIONS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .