Loading…
Loading…
Tender Value
₹1.2 Cr
EMD Value
₹2.3 L
Closing Date
28 May 2026, 11:00 amClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
45 days
Expenditure
Capital (Works)
GSPGT
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' which ever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Appendix-J, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet
Statement showing Annual Contractual Turnover Data (as per Annexure - J of Tender Document) for the Previous 3/4 Years (Contractual Payment only) supported by Audited Balance Sheet duly certified by the Chartered Accountant shall be enclosed alongwith the bid. Non-submission of the same by the bidder shall result in summarily rejection of his/their bid
The tenderer must have successfully completed or substantially completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: 1. Three similar works each costing not less than the amount equal to 30% of advertised value, or 2. Two similar works each costing not less than the amount equal to 40% of advertised value or 3.One similar work each costing not less than the amount equal to 60% of advertised value Note: Separate completed works of minimum required values for each component can also be considered for fulfillment of technical eligibility criteria for different components. *Similar Single work is defined as "Works involving supply, installation, testing and commissioning of outdoor/indoor substation equipments of 11kV or above voltage".
The tenderer shall submit along with the tender document, documents in support of his/their claim to fulfill the eligibility criteria as mentioned in the tender document. Each page of the copy of documents/certificates in support of credentials, submitted by the tenderer, shall be self- attested/digitally signed by the tenderer or authorized representative of the tendering firm. Self-attestation shall include signature, stamp and date (on each page). Only those documents which are declared explicitly by the tenderer as "documents supporting the claim of qualifying the laid down eligibility criteria" will be considered for evaluating his/their tender. Note- The tenderer shall attach a summary of documents submitted for satisfying the eligibility criteria either duly self attested or digitally signed
22 conditions · 3 needing a document upload
The Supply of Goods and Services would be subject to GST Act and Rules applicable from time to time.
I/We have read the various conditions to tender in the attached tender document and agree to abide by the said conditions.
I/We agree to keep this tender open for acceptance for a period of 45 days from the date of closing of this tender and in default thereof I/We will be liable for forfeiture of my/our Bid Security. I/We offer to do the work for Railway, at the rates quoted in the attached Schedule and hereby bind myself/ourselves to complete the works in all respects.
I/We also hereby agree to abide by the updated Regulations of Tenders and Contracts and General Conditions of Contract issued by the Engineering Department of Indian Railways along with correction slips issued from time to time and to carryout the work according to the Special Conditions of Contract and specifications of materials and works as laid down by Railway in the Annexed Special Conditions / Specifications, Schedule of Work for the present contract.
All rates quoted in the tenders shall be deemed to be inclusive of CGST, SGST, IGST etc., payable by the contractor to the Government or any public body and no additional amount/rate or claim will be entertained on this account by the Railways. Also no claim whatsoever will be accepted by Railways on account of revision of tax rates, new taxes of statutory nature by State/Central Govt.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The tenderer shall go through the entire tender documents thoroughly and strictly adhere the instructions and directions given at different pages.
Deployment of Qualified Engineers at Work Sites by the Contractor - The Contractor shall employ 1 No. of qualified Graduate Engineer for works Rs. 200 Lakh or more and 1 No. of Diploma Engineer for works costing more than Rs. 25 Lakh, but less than Rs 200 Lakh
MEMU Shed/PGT - Supply, Erection, Testing and Commissioning of 11kV/433 kV substation for MEMU Shed
J-E-4-2026-27-W
J-E-4-2026-27-W
Open
Works - General
9 Months
Palakkad, Kerala
₹0
₹2.3 L
28 May 2026
6 May 2026
14 May 2026
139 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,16,08,337 | ||
| — | 1000.00 | — | — | ||
| "Transportation &Laying / clamping / threading of 4 Core XLPE cable (Size up to & Including 70 Sq.mm) through trench, Cable protection pipe, Wall/shelters, FOB, etc as directed at site, with suitable clamps, Aluminium sockets, etc., Note: - Cable will be supplied by Railway from the Office of SSE/Electrical/W/PGT." | — | — | — | 50,000 | |
| — | 500.00 | — | — | ||
| "Transportation &Laying / clamping / threading of 2Core/4 Core XLPE cable (Size above120 Sq.mm upto and including 300Sq.mm) through trench, Cable protection pipe, Wall/shelters, FOB, etc as directed at site, with suitable clamps and termination duly supplying required cable glands, Aluminium sockets, etc., Note: - Cable will be supplied by Railway from the Office of SSE/Electrical/W/PGT." | — | — | — | 45,000 | |
| — | 250.00 | — | — | ||
| Supply,Transportation & Laying/ clamping /threading of HT XLPE cable 3x300 Sq mm Aluminium including stacking place to work site and laying it carefully using cable rollers, taking through stone ware/ G.I.pipes at road crossing/ culverts /bridges etc. whereever necessary, providing identification tags at 5m intervals, filling the space around the cable with riddled soil, providing cable route markers at 100m intervals, inclusive of cost of all materials (other than cost of GI/HDPE pipe & UG Cable), labour, transport and crane charges. | — | — | — | 4,27,750 | |
| — | 12.00 | — | — | ||
| "End termination using single brass compression gland of Size from 4 core 70 Sq.mm up to & Including 4 Core 95 Sq.mm with required aluminium sockets, etc.., Note:- 1) Scope of work including supply and Fixing of said glands 2) PVC type glands may be used for cable termination in the poly carbonate box as directed by site engineer incharge." | — | — | — | 6,000 | |
| — | 12.00 | — | — | ||
| "End termination using single brass compression gland of Size from 4 core 120 Sq.mm up to & Including 4 Core 185 Sq.mm with required aluminium sockets, etc.., Note:- 1) Scope of work including supply ad Fixing of said glands 2) PVC type glands may be used for cable termination in the poly carbonate box as directed by site engineer incharge." | — | — | — | 7,416 | |
| — | 12.00 | — | — | ||
| "End termination using single brass compression gland of Size from 4 core 240 Sq.mm up to & Including 4 Core 300 Sq.mm with required aluminium sockets, etc.., Note:- 1) Scope of work including supply ad Fixing of said glands 2) PVC type glands may be used for cable termination in the poly carbonate box as directed by site engineer incharge." | — | — | — | 11,136 | |
| — | 12.00 | — | — | ||
| "Supply and Fixing of Cable protection pipe of 50mm dia B class GI pipe with suitable clamps and sealing compound shall be provided on the top of the GI pipe as per standard. | — | — | — | 8,400 | |
| — | 6.00 | — | — | ||
| Supply and fixing of 'B' class 150mm Dia GI pipes for cable leading / protection including one number of clamp made out of MS flat of 40mmx6mm size, one per metre length including applying of end sealing compound on top etc | — | — | — | 11,922 | |
| — | 10.00 | — | — | ||
| "Provision of Inspection pit of 0.6m x 0.6 m x 0.6 m depth (Inner dimensions) for laying of cable with brick wall of 0.20 m thick on all the four sides with plastering and top cover shall be of Concrete slab/ heavy duty FRP/ cast iron as directed by site Engineer in charge. Note :- 1) Edges of the Top cover and top of the Inspection pit shall be protected by Suitable MS / GI ""L Angle"" as directed by site Engineer in charge." | — | — | — | 50,000 | |
| — | 600.00 | — | — | ||
| "Transportation and laying /fixing of HDPE pipe 50mm dia pressure rating up to 4PN (Material Grade-PE 63) in the excavated cable trench/building wall/FOB etc.., With suitable GI fixing hardware like T-Joints, L-Joints, shall be used at appropriate locations. So that cable can be easily inserted and removed wherever need arises. Note: HDPE pipe will be supplied by Railway from the Office of SSE/Electrical/Works/PGT." | — | — | — | 21,000 | |
| — | 600.00 | — | — | ||
| "Transportation and laying /fixing of HDPE pipe 90mm dia pressure rating up to 4PN (Material Grade-PE 63) in the excavated cable trench/building wall/FOB etc.., With suitable GI fixing hardware like T-Joints, L-Joints, shall be used at appropriate locations. So that cable can be easily inserted and removed wherever need arises. Note: HDPE pipe will be supplied by Railway from the Office of SSE/Electrical/Works/PGT." | — | — | — | 28,200 | |
| — | 600.00 | — | — | ||
| "Transportation and laying /fixing of HDPE pipe 160mm dia pressure rating up to 4PN (Material Grade-PE 80) Under Railway track/Road Crossing/ in the excavated cable trench with suitable fixing hardware. Note: HDPE pipe will be supplied by Railway from the Office of SSE/Electrical/Works/PGT." | — | — | — | 31,200 | |
| — | 210.00 | — | — | ||
| Excavation of cable trench in all kinds of soil up to a depth of 1.0 Mtr. & Width of 0.3 Mtr duly clearing the roots of trees etc. and refilling with the excavated soil up to normal level. Depth and Width can be varied based on site Condition as directed by site engineers in charge. Concerned Measurement will be taken in Cubic meters. | — | — | — | 1,05,000 | |
| — | 8.00 | — | — | ||
| Breaking of cement concrete flooring and finishing to original level by cement concrete in an approved manner | — | — | — | 40,000 | |
| — | 4.00 | — | — | ||
| Excavation and refilling of cable trench along/across Tarred Road up to a depth of 1.0 meter and width of 0.3mtrs duly breaking the tarred surface, removing soling stones and soil and finishing back to the original level with bituminous macadam using crushed stone aggregates as per standards. Depth and width can be relaxed by site Engineer and Measurement will be recorded based on the Proportionate reduction in length of trench/meter. | — | — | — | 22,596 | |
| — | 9.00 | — | — | ||
| Excavation and refilling of cable trench across the Railway track 30cm width and depth of 1.2m from the foundation level. This includes removal and relaying of ballast without contamination of soil and rearranging the formation to original level. Depth can be relaxed by the site engineer as per the site condition and measurement will be recorded based on the volume of the trench under the formation. | — | — | — | 4,500 | |
| — | 10.00 | — | — | ||
| "Supply at site & placing of flat type cable route indicator at regular intervals on straight route and one each at every route diversion from straight line as directed by site engineer. The said cable Route Indicator has to be grouted in a concrete mix of ratio 1:3:6with 300mmX200mmX300mm size." | — | — | — | 8,160 | |
| — | 5.00 | — | — | ||
| "Supply and erection of Dwarf Rail pole with suitable foundation. Note:-The Rail poles will be supplied by Railway at nearest location same has to be cut in to suitable size as directed by site engineer." | — | — | — | 10,995 | |
| — | 5.00 | — | — | ||
| "Supply and fixing of Poly carbonate box of similar to model No. Mi 0800/Mi 0801 on the Dwarf Rail poles for cable termination with the following 1) 2 No. of 200A 4 Way Connector. " | — | — | — | 1,56,625 | |
| — | 8.00 | — | — | ||
| Supply and fixing of heat shrinkable straight through cable joint kits suitable for 4 Core / 3.5 Core PVC/XLPE LTUG cables of size 50sq.mm to 95sq.mm | — | — | — | 28,880 | |
| — | 8.00 | — | — | ||
| Supply and fixing of heat shrinkable straight through cable joint kits suitable for 4 core/3.5Core PVC/XLPE LTUG cables of size 120sq.mm to 185sq.mm | — | — | — | 41,256 | |
| — | 1.00 | — | — | ||
| "Supply, Erection, Testing and Commissioning of 9m Double Pole (Rail pole) structure inclusive of 11kV, 200A/400A D/B GOS, Post Insulator, Pin Insulator, Disc Insulator, 1set of Lightning Arrester, 0SWG Electrolytic Solid Copper Rods, Anticlimbing Devise, Channel cross arms and angle cross bracings etc,,. confirming to Electricity Board /KSEBL Standards inclusive of all accessories such as clamps, bolts, nuts, washers etc.., as per Detailed Sketch Enclosed and painting with two coats in each of primer zinc chromate and aluminium paints. (Rail pole will be supply by railway at nearest depot) Note:- Necessary drawing approval may be obtained before commencement of work. " | — | — | — | 51,575 | |
| — | 2.00 | — | — | ||
| Transportation of 9 meter Rail pole from the nominated locations as directed by site engineer incharge. | — | — | — | 6,188 | |
| — | 1.00 | — | — | ||
| Supply, Erection, Testing and Commissioning of Outdoor Type 11kV, 3 Phase Metering Panel with Trivector Meter (Bi directional), CT of Suitable Ratio, PT of Ratio 11kV/110V and all other Standard accessories as per enclosed detailed specification, relevant standards and requirements of KSEB | — | — | — | 2,26,930 | |
| — | 25.00 | — | — | ||
| Supply and provision of mass concrete for plinths of transformers, panel boards, kiosks and as instructed by Engineer-incharge with 1:2:4 ratio using 20 mm blue metal | — | — | — | 1,80,500 | |
| — | 2.00 | — | — | ||
| Supply, fixing and commissioning of outdoor heat shrinkable type end termination kit for 11kV, 3 core, 300sq.mm XLPE UG cable | — | — | — | 27,850 | |
| — | 7.00 | — | — | ||
| Supply, fixing and commissioning of indoor heat shrinkable type end termination kit for 11kV, 3 core, 300sq.mm XLPE UG cable | — | — | — | 75,810 | |
| — | 3.00 | — | — | ||
| Supply, Erection, testing and commissioning of Drop Out Fuse unit complete to work on AC, 11 KV, three phase, 50 Hz supply, 200 A capacity, channel mounting and expulsion type with fuse elements of appropriate current rating inclusive of all accessories, all conforming to IS No: 2692, 5792 & IS No: 9385 with all accessories | — | — | — | 31,539 | |
| — | 225.00 | — | — | ||
| Supply and Spreading of quarry dust of approximate 100mm thick in the substation yardto avoid growth of grass/Bushes. | — | — | — | 57,825 | |
| — | 16.00 | — | — | ||
| Supply and spreading of Blue metal of 40mm size around the Double Pole Structure and transformer plinth structure as per standard | — | — | — | 40,992 | |
| — | 1.00 | — | — | ||
| "Supply at site, Erection, Testing and Commissioning of 400kVA, 11kV/433V out door type Compact sub station with ONAN Transformer, HV side RMU and LV side 800A ACB as per detailed Specification enclosed, Confirming to relavant IS/IEC and KSEBL Standards. Make: -ABB, Schneider, Siemens, or any other Reputed makes" | — | — | — | 37,47,090 | |
| — | 1.00 | — | — | ||
| "Supply at site, Erection, Testing and Commissioning of 400kVA, 11kV/433V out door type Compact sub station with Oil filled Transformer (Without HV side RMU), with LV side 800A ACB as per detailed Specification Enclosed and Confirming to relavant KSEBL Standards. Make: -ABB, Schneider, Siemens, or any other Reputed makes" | — | — | — | 29,05,750 | |
| — | 100.00 | — | — | ||
| Supply, fabrication and fixing of frame work made of 50x50x6mm MS angle for laying chequered MS plate to cover cable duct to suit site requirements and as instructed by Engineer-in- charge | — | — | — | 51,500 | |
| — | 24.00 | — | — | ||
| Supply and laying of chequered MS plate of 6mm thickness in sizes and shapes required for covering cable duct as instructed by the Engineer-in-charge. Floor and MS plate should be in the same level | — | — | — | 61,872 | |
| — | 38.00 | — | — | ||
| Supply and laying of electrolytic tinned copper flat of 40mmx6mm (1 1/2"x1/4") size as per standard | — | — | — | 90,136 | |
| — | 1.00 | — | — | ||
| "Supply, erection, testing and commissioning of contactor switched standard Automatic Power Factor Correction Panel of 75kVAr capacity as per enclosed detailed specification and relevant standards Note:- 6 Number of physical steps may be nsured for the said APFC panel. " | — | — | — | 2,92,989 | |
| — | 1.00 | — | — | ||
| Supply and fixing of 2Nos. of 800/5A, CL 1.0,10VA, Resin cast CTs and 1No.5+5/5A summation CT in the existing Non essential MV panel (for APFC panel) | — | — | — | 10,252 | |
| — | 180.00 | — | — | ||
| Supply and fixing of 2Core 2.5 Sqmm Copper Armoured UG cable for Interconnection between APFC Panel and CT . | — | — | — | 22,140 | |
| — | 60.00 | — | — | ||
| "Supply and fabrication of fencing panel of 2.4mtr Height and 1m Width made with 8SWG (Nominal Size ) GI Chain Link Mesh 50X50mm inner size of the diamond design, 40X40X5/6mm MS angle Outer frame in 2mtr wide and Vertical T section support with 40X40X5/6mm MS angle iron and 40X5/6mm MS flat at middle , Horizontal brazing at Centre with 40X5/6mm MS flat etc.., In welded Construction, Install the Fencing panels on the channel poles already erected by welding,Suitable door and locking Arrangements , painted with approved enamelShade/AL paint after Applying epoxy Primer etc., as Required. Note:- Fencing to be done as per the drawing enclosed." | — | — | — | 2,78,460 | |
| — | 40.00 | — | — | ||
| fabrication, Supply and Erection of approximate 2.9m long channel pole of size 100X50mm with MS base plate of size 200X200X5mm, painted with approved enemal Shade/AL pain after epoxy primer for welded mesh fencing of the substation including concreting. | — | — | — | 1,85,640 | |
| — | 1.00 | — | — | ||
| "Fabrication, supply and erection of stand of fire buckets as per Standards along with Six Numbers of fire buckets each of 10litre capacity, filled with Coares, River sand and painted in red with white letters. Note :- Drawing approval may be obtained before fabrication work." | — | — | — | 6,704 | |
| — | 2.00 | — | — | ||
| Providing and fixing of 6kG DCP type fire extinguiher Cofirming to IS 28781976 complete with discharge swivel bend , horn & hose, screwed valve, mounting bracket and cylinderfully charged. | — | — | — | 4,538 | |
| — | 1.00 | — | — | ||
| Supply of earth discharge rod with suitable length of flexible copper wire for earthing | — | — | — | 2,888 | |
| — | 1.00 | — | — | ||
| Supply of fuse link rod of suitable length for fixing and removing of DO fuses | — | — | — | 2,888 | |
| — | 1.00 | — | — | ||
| Supply of First Aid Box [FAB] containing medicine as presdribed by St.john ambulance Brigade of indian re cross society Confirming to IS:-2217-1963 | — | — | — | 773 | |
| — | 1.00 | — | — | ||
| Artificial Resuscitator in a portable case ready for use with adult face piece | — | — | — | 2,372 | |
| — | 1.00 | — | — | ||
| Shock treatment chart duly framed and written in englih, Hindi & Regional language. | — | — | — | 1,031 | |
| — | 2.00 | — | — | ||
| Supply of 15kV grade rubber hand gloves pair of 15" size as per IS :4770-1991. | — | — | — | 1,030 | |
| — | 8.00 | — | — | ||
| Supply and fixing of Danger Board suitable for 11 KV /22 KV/33 KV systems, as per IS.No: 2551, along with one number of clamp made out of 25mm X 4 mm size including bolts & nuts for fixing on structures and painting | — | — | — | 2,472 | |
| — | 14.00 | — | — | ||
| Supply, erection and testing of earthing arrangements duly stencilling of earth resistance value along with date as per drawing number CEE/CN/MS/37-2004 with Cast Iron pipe of 100 mm diameter, LA class, including supply and spreading of 10 kgs in each of salt and charcoal for earth treatment | — | — | — | 2,63,676 | |
| — | 4.00 | — | — | ||
| Supply and Installation of earthing arrangements as per RDSOSpecification No. RDSO/SPN/197/2008 or latest | — | — | — | 1,13,464 | |
| — | 2.00 | — | — | ||
| "HT Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. Note :- 1) The work has to be done as per the drawing enclosed. 2) Drawing Approval may be obtained before Commerncent of work. " | — | — | — | 23,146 | |
| — | 40.00 | — | — | ||
| Supply, fixing and laying of 6SWG copper wire for earthing purpose on structures/ground as instructed by the Engineer-in-charge | — | — | — | 5,360 | |
| — | 130.00 | — | — | ||
| Supply, fabrication and laying of 50mmx6mm GI flat for earthing purpose as per relevant standard and as instructed by the Engineer-in-charge | — | — | — | 60,320 | |
| — | 6.00 | — | — | ||
| Supply and spreading of chequered electrical rubber mat of 2 m long and 1.0 m wide and 12 mm thick to withstand 40 kV(rms) as per IS No: 5424 | — | — | — | 12,378 | |
| — | 5.00 | — | — | ||
| Supply and fixing of Protected area Board of Size 750X300X1.6mm as per Drawing No.EERE/TSS/16-Enamel type | — | — | — | 3,350 | |
| — | 1.00 | — | — | ||
| Provision of printing the substation Electrical Drawing in the viniyal (Approx. Size 6 X 4 feet) and same has to be fixed in the suitable location as directed at site Engineer. | — | — | — | 3,094 | |
| — | 12.00 | — | — | ||
| Fabrication, supply and fixing of MS Channels of size 75 x 40 x 3.7 mm (web) including fixing clamps, bolts and nuts and painting with two coats of primer zinc chromate paint and aluminium paints | — | — | — | 14,328 | |
| — | 16.00 | — | — | ||
| Fabrication, supply and fixing of MS Channels of size 100 x 50 x 4.0 mm (web) including fixing clamps, bolts and nuts and painting with two coats of primer zinc chromate paint and aluminium paints. | — | — | — | 22,208 | |
| — | 1.00 | — | — | ||
| "Design, fabrication, supply, erection, testing and commissioning of medium voltage main distribution board (Non Essential) with the followings Incoming 1) 2 Nos. of MCCB 4 Pole 800A, 50kA similar to L&T Model No. CM96111OOOOX1 with Microprocessor Based, adjustable over load, adjustable Short circuit with mechanical interlock. Outgoing 1) 1 Nos. of MCCB 4 Pole 400A, 36kA similar to L&T Model No. CM93003OOOOX1 with Microprocessor Based, adjustable over load, adjustable Short circuit 2) 4 Nos. of MCCB 4 Pole 250A, 36kA similar to L&T Model No. CM92151OOOOX1 with Microprocessor Based, adjustable over load, adjustable Short circuit 3) 3Nos. of MCCB 4 Pole 100A, 25kA similar to L&T Model No. CM91712OOKOOG with Thermal Magnetic Release, adjustable over load, adjustable Short circuit 4) 3 phase KWH meters (L&T model WL400010OOOO or similar) -2 Nos., 5) 3 phase Digital Voltmeters (L&T model WL132010OOOO or similar) - 2 Nos., 6) 3 phase Digital Ammeters (L&T model WL131010OOOO or similar)- 2Nos., 7) Earth Faut Relay (similar to L&T Model MC12) -2Nos., 8) Suitable length of electrolytic copper busbar of 65mm x 10mm (main) and other standard fittings as per enclosed detailed specifications and relevant IS Note:- 1) Approximate size of the panel - 2000mm x 2000mm x 500 (L x H x D) 2) All MCCB has to be fixed with Ground fault protection arrangements, Spreader & ROM" | — | — | — | 10,50,000 | |
| — | 200.00 | — | — | ||
| Supply, laying and provision of 6 SWG GI wire as earth continuity including termination | — | — | — | 7,000 | |
| — | 26.00 | — | — | ||
| Supply and laying of country bricks of size 200mm X 100mm X 50mm (width wise) in an approved manner | — | — | — | 3,588 | |
| — | 35.00 | — | — | ||
| Providing Brick work (In width 250mm or Less) in cement Mortar for masonary open cable trenches, fencing Kerb wall. | — | — | — | 2,86,300 | |
| — | 180.00 | — | — | ||
| Providing 12mm thick Cement plastering for masonry open trenches, fencing kerb wall, brick foundation etc.., | — | — | — | 27,540 | |
| — | 5.00 | — | — | ||
| supply and provision of 100mm thick Concrete for base flooring of masonry open trench and instructed by Engineer in charge with 1:3:6 ratio using 20mm blue metal | — | — | — | 33,125 | |
| — | 30.00 | — | — | ||
| Providing and laying of 50mm thick RCC slab in suitable size with 10mm MS rod Re- inforcement 100mm C/C metal etc.., for covering the open cable duct out side. | — | — | — | 21,450 | |
| — | 300.00 | — | — | ||
| Fabrication, supply and fixing of clamps of various sizes made out of MS flat of 25x3mm size including painting suitable for clamping/fixing of GI pipe/LTUG cable on walls of buildings/sheds, shelter etc. using bolts and nuts of suitable sizes | — | — | — | 21,600 | |
| — | 40.00 | — | — | ||
| "Supply and Three phase wiring by means of 4 nos. of 10.0 Sq.mm (P&N) and 1No. of 16.0Sq.mm (Earth) size Flame Retardant Low Smoke & Halogen (FR- LSH) PVC insulated single core multistranded flexible copper cable with ISI mark of approved make with coded color for Three Phases, Neutral and Earth Respectively through already erected PVC casing and capping or pipes, junction boxes, distribution boards etc., " | — | — | — | 57,160 | |
| — | 40.00 | — | — | ||
| Supply and wiring to pre-Cooling Plug socket by means of 4 Runs of Flame Retardant (FR) PVC insulated single core multistranded flexible copper cable of size 25 sq.mm drawn through 50mm dia PVC pipe including clamping of PVC pipe along the rail post/PF Shelter/Pillar with suitable MS painted fixing hardware (1m = 4 Runs of 25 Sq.mm copper wire) | — | — | — | 93,480 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC April 2022
ATTACHMENT
Tender Document
ATTACHMENT
GeneralConditionsofContractGCC-April-2022.pdf
ATTACHMENT
TenderDocument-MEMEShed11kVSubstation.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .