Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | l1₹38.8 LAccepted-AOC 76 21 GURUDWARA ROAD NAKA HINDOLA LUCKNOW | LUCKNOW | LUCKNOW | UTTAR PRADESH | ₹38.8 L | l1 | Accepted-AOC lowest bid |
| 2 | l2₹40 L+₹1.2 L (3.03%)Rejected-Finance | ₹40 L+₹1.2 L (3.03%) | l2 | Rejected-Finance higher rates |
| 3 | l3₹46.6 L+₹7.8 L (20.1%)Rejected-Finance 4TH FLOOR 4B P 118 PS PHOOL BAGAN CIT ROAD SCHEME VI M KOLKATA KOLKATA WEST BENGAL 700034 | KOLKATA | WEST BENGAL | 700034 | ₹46.6 L+₹7.8 L (20.1%) | l3 | Rejected-Finance higher rates |
Tender Value
Refer Docs
EMD Value
₹79,000
Closing Date
6 Dec 2024, 5:00 pmClosed
Executive Engineer E/M
Executive Engineer E/M Division pwd bazpur
Illumination and Electrification work of Kuber Temple near Shree Jageshwar Dham, Almora.
2024_pwd_78109_1
1353/nividasoochnaDt20/11/2024
Open Tender
Electrical Works
Item Rate
180 days
JAGESWAR ALMORA
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,950
Executive Engineer E/M Division PWD Bazpur
₹79,000
17 Mar 2025
22 Nov 2024
7 Dec 2024
22 Nov 2024
6 Dec 2024
29 Nov 2024
22 Nov 2024 - 28 Nov 2024
Amount
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door
Supplying and fixing the following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required 40 A(Incomer in DB)
Supplying and fixing following rating, four pole, 415 V,isolator in the existing MCB DB complete with connections,testing and commissioning etc. as required. 40 A ,Isolator
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for the inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required. Single pole
Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, Incoming - 1 no. 4 core 4.0/2.5 sq mm copper armoured cable Outgoing - 2 nos. 3 core 2.5/1.5 sq mm copper armoured cable. Built-in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm dia.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25 mm dia.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supply installation testing & commissioning of 6.0-meter height 75mm dia, C class MS pole, anthracite grey paint, with plate mounting arrangement, plate size 450mm X 450mm X 20mm suitable for bracketless direct lighting fixture installation.
Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of the following size in the existing RCC/ HUME/ METAL/DWC pipe as required. Upto 35 sq. mm
Supply of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground/DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required. 4C x 16 Sq.mm. Aluminium XLPE armoured cable
Supply, connection, testing and commissioning of heavy duty, medium voltage,XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified.The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge.The scope shall include: 1) Supply of Cables.(With Non Returnable Drums)2) Delivery of the cables at site.3) Unloading at site store. 4) Shifting of cable from site store to place of installation.5) Connection of cable with proper tagging as specified ni specifications.6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely.7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar.8) Testing of insulation and continuity of cable and submission of reports to the client's representative.9) To prepare submission drawing and to take approval of consultant at each stage.10) To prepare & submit as-built drawing and handing over document to end user.11) Rate shall be inclusive of route markers at 15mtr intervals12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written.Approved Makes- FINOLEX / LAPP / POLYCAB / RR KABEL / KEI / HAVELLS 3C x 2.5 Sq.mm. CU XLPE armoured cable
Supply and Providing heavy duty double compression brass gland and lugs end terminations,IP 66 complete,SIBG type, for the cable specified under above item with Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland. 3C x 2.5 Sq.mm. CU XLPE armoured cable
…..Do…. But Size 4C x 16 Sq.mm. Aluminium XLPE armoured cable
DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
1000mm ±15% Linear LED 25W, 1500 lumens - 2400K-5000K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 1000mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 25 watts, 1500 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, Tunable from 2400K-5000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
1000mm ±15% Linear LED 15W, 750 lumens- 2400K-5000K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 1000mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 15 watts, 750 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, Tunable from 2400K-5000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
500mm ±15% Linear LED 13W, 750 lumens- 2400K-5000K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 500mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 13 watts, 750 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, Tunable from 2400K-5000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
500mm ±15% Linear LED 8W, 450 lumens- 2400K-5000K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 500mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 8 watts, 450 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, Tunable from 2400K-5000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
300mm ±15% Linear LED 8W, 450 lumens- 2400K-5000K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 300mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 8 watts, 450 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, Tunable from 2400K-5000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
300mm ±15% Linear LED 5W, 300 lumens- 2400K-5000K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 300mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 5 watts, 300 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, Tunable from 2400K-5000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Neon Flex LED 20W/M, 1200 lumen/M- RGBW: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, Neon flex light mouting climps (as per application). The power consumption should be 20 watts per meter, 1200 lumens per meter delivered, diffused, CCT-RGBW. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Ring Flex Washer LED 20W/M, 1200lumen/M- RGBW: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 1000mm dia ring flex light mouting climbs (as per application). The power consumption should be 20 watts per meter, 1200 lumens per meter delivered, diffused, CCT-RGBW. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Flood Light LED 50W, 4000lumens- 3000K/4000K: Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot complete with adjustable mounting brackets/clamps (as per application). The power consumption should be 50 watts, 4000 delivered lumens, 30° beam angle with a tolerance of ±15%, CCT-3000K/4000K. The housing material should be extruded aluminum, a powder-coated finish, anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be integral non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP67 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified. This includes all the required hardware & software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Flood Light LED 100W- Blue color: Supply installation testing & commissioning of exterior rated architectural floor/wall mounted IP66, flood light with antiglare snoot complete with adjustable mounting brackets/clamps (as per application). The power consumption should be 100 watts, 40° beam angle with a tolerance of ±15%, CCT-Blue color. The housing material should be extruded aluminum, a powder-coated finish, anti-aging and anti-UV high optical efficiency PMMA lenses, Clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be integral non dimmable with PF>0.9 & THD<20%. Leader cables, jumper cables, IP67 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified. This includes all the required hardware & software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
1000mm ±15% Linear LED 10W- 2700K: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 1000mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 10 watts, 600 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, CCT-2700K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC non dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
500mm ±15% Linear LED 25W, 1500lumens- RGBW: Supply installation testing & commissioning of exterior-rated architectural floor/wall mounted IP67 or better, 500mm ±15% long linear light complete with visor and adjustable mounting brackets/clamps (as per application). The power consumption should be 25 watts, 1500 lumens delivered, 10 x 30° beam angle with a tolerance of ±15%, CCT-RGBW. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC dimmable (IP67) with PF>0.9 & THD<20%. Leader cables, jumper cables, IP68 connectors are inclusive. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware, DMX controller and software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
150W GOBO Projector: Supply installation testing & commissioning of exterior rated floor/wall/pole mounted IP66, high-definition customized image gobo projector, and adjustable mounting brackets/clamps (as per application). The power consumption should not be more than 150 watts, Narrow beam angle, CCT 3000K/4000K. The housing material should be extruded aluminum, a powder-coated finish, Minimum IK06. The operating temperature should be of -20°C to 50°C range. Lifetime of luminaire (L70 @ Ta-35deg C L80B10) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS certified. This includes all the required hardware DMX controller & software for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Supply installation testing & commissioning of Outdoor rated surface mounted powder coated aluminium alloy having wall thickness of minimum 3MM on all sides, with width limited to 140 MM or less & height limited to 60 MM or less, to house IP67 rated two light fixtures as per the BoQ, wiring management and IP68 GEL connectors for internal connections, and to withstand load of 20 MM to 50 MM thick stone on top, for walkover application. It should have proper end caps to cover and protect the wiring. as per detail drawing given.
Supply installation testing & commissioning of Outdoor rated floor recessed stainless steel as per IS-277, Powder Coated, and SS-202/304/316. Width 100mm, Height 50mm, this includes all types of hardware and accessories.
Comprehensive Annual Maintenance Contract Charges of entire project for 5 Years
M/S TRADING ENGINEERS (BID ID -349049)
Leksa Lighting Technologies Private Limited (BID ID -348484)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_93242.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .