Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.0 LAccepted-AOC 894 NEAR 132 KV POWER HOUSE SINDHARI ROAD BALDEV NAGAR BARMER RAJ 344001 | BARMER | RAJASTHAN | 344001 | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹14.3 L+₹81,170 (6.03%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹14.6 L+₹1.1 L (8.13%)Rejected-Finance SHOP NO 13 MOHINI MARKET KISHORE BAGH MANDORE JODHPUR RAJ | JODHPUR | RAJASTHAN | 342001 | L3 | Rejected-Finance Not lowest bidder | |
| 4 | L4₹15.3 L+₹1.8 L (13.5%)Rejected-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L4 | Rejected-Finance Not lowest bidder |
Tender Value
₹16 L
EMD Value
₹32,000
Closing Date
30 Sept 2024, 6:00 pmClosed
Garrison Engineer Banar
Garrison Engineer Banar, Jodhpur-342027
REPAIR REPLACEMENT OF UNSV LIGHTENING CONDUCTOR EARTHING TEST POINT AT ESH AND OTHER STORAGE SHED IN A A BANAR UNDER GE BANAR
2024_MES_669744_1
8824/27/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Banar
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer Banar
₹32,000
Yes
19 Nov 2024
2 Sept 2024
7 Oct 2024
2 Sept 2024
30 Sept 2024
16 Sept 2024
Amount
M&L for earthing in replacement with galvanized steel earth plate of size 60x60x6 mm thick electrode and 32x6mm GI strip length up to 7.5 mtr as earth lead, buried directly in ground protected by GI pipe 40 mm dia medium grade (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate should not less than 1.5 mtr below normal ground level and connected to galvanized iron earth, GI strip of size 32X6 mm dia by means of bolts, nuts, washers of galvanized iron all as shown in electrical plate No.3 of MES SSR Part I connected to earth test terminal point all asa specified or as indicated including testing on completion (Rates inclusive of neccessary excavation in any type of soil,earth work,PCC pit,PCC cover,funnel with watering pipe, wire mesh, common salt, charcoal etc.all as required at site for complete earthing Note :- (i)The earth pit shall be refilled by boulders free from vegetable soil. (ii)Testing of Earthing shall be carried out after completion of earthing and tested by contractor in presence of JE /Engr-in-Charge.
Taking out carefully existing aluminum strip of any size including porcelain / PVC insulators and air termination rods from roof/wall of height upto 10mtr and seperating the serviceable/unserviceable material complete all as specified.
Labour only for re-fixing aluminum strip as retrieved from item No 2 in position including provision of new insulators & nut,bolts,screws and proper layout on roof/wall at a height upto 10mtr complete all as specified.
S&F of aluminum strip of size 25x3.15 mm incl saddles / supporting insulators to run over the roof complete all as specified.
Taking out carefully existing GI strip of any size including porcelain / PVC insulators and air termination rods from roof/wall of height upto 10mtr and seperating the serviceable/unserviceable material complete all as specified.
Labour only for re-fixing GI strip as retrieved from item No 5 in position including provision of new insulators & nut,bolts,screws and proper layout on roof/wall at a height upto 6 mtr and burried in ground depth not less than 60 cm complete all as specified.
S&F of GI strip of size 32x6 mm incl mounting on including PVC/Porcelain insulators on wall and burried in ground depth not less than 60cm in ground complete all as specified.
M&L in repairs for air termination single pointed aluminium rod 12mm dia 300mm long fixed proper on GI pipe/pcc by drilling,nut,bolt etc complete all as specified.
Supply and fixing in replacement test point terninal block made of gun metal or phasphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hex head screw fixed on wall complete all as specified.
Supply and fixing in replacement of GI tubing 50mm dia medium grade in incl necessary fittings for lowering in borewell of depth upto 30mtr and grouting at roof top in cement concrete to mount the air termination rod complete all as specified. Note: PCC work for grouting on roof shall be measured and paid seperately under relevant item of Schedule.
M&L PCC (1:3:6) type C-I using 20mm graded stone aggregate for coping of GI pipe at roof top with form work as required complete all as specified.
Material and labour for replacement of unserviceable existing earthing with bore well earthing with the help of mechanical boring machine of 150 mm dia, 30 mtr depth with 50mm dia medium GI pipe duly drilled all around 150 mm dia hole at a distance of 200 mm from hole to hole upto min 20 mtr depth upto water level including supply and fix 150 mm dia (O.D), UPVC pipe 6 kg/sqcm rating -06 mtr long with the help of suitable size clamp with nut bolt and washer -01 No. including charcoal dust, Salt fill in bore well for earth conductivity ,M&L for providing 32x6 mm GI strip upto 7.5 mtr protected by GI pipe 40mm dia medium grade in ground and connected to terminal block,grounding of borewell with PCC (1:2:4) type B-1 / Brick masonry pit of size 45x45x45cm complete and give the minimum earth test result below 1 Ohm complete all as specified and directed by Engineer-in-charge. Note :- (i) The charge for mechanical boring machine,upvc pipe 150 mm dia length 6 mtr ,GI strip 32x6mm up to 7.5 mtr & pcc work is deemed to be include in above quoted rate. (ii) GI tubing 50mm dia medium grade shall be measured and paid separately items of schedule. (iii) Earthing shall be tested by contractor in presence of JE/Engr-in-Charge.
Anil Builders (BID ID -3100238)
Sachiyay maa Electricals (BID ID -3108366)
Shri Electrical Enterprises (BID ID -3122361)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .