| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Preventive maintanace contract of 2000 KVA DG set | |||||
| 1.001 | OD102242/2024-2025:Charge for carrying out periodical performance inspection, preventive maintenance, urgent repairs of Engine and Alternator side of 2000 KVA capacity Diesel generator set as per the standard preventive maintenance scope & conditions, including labour charge for replacing minor faulty components of DG set / standard control panel exist in the DG set etc...(excluding spares). Attending Emergency calls on Report, excluding cost of major maintenance works ( 4 preventive maintenance service per year)
Conditions of periodical preventive maintenance services
I Check Level And Top up
(a) Oil in engine
(b) Oil in air cleaner
(c) Oil in FIP
(d)Fresh water level in heat exchanger
(e) Water / coolent in radiator
(f)Electrolyte in battery
ii Check Tightness Of
(a) Battery terminal & apply Vaseline
(b) Fan belt
(c) Hose connections in cooling system
(d) Fuel piping connections
(e) Exhaust piping connections
(f)Engine mountings
(g)Engine drive unit coupling
(h) Electrical connections at instrument panel
iii Start And Run The Engine 10 Minutes
(a)Check and recording RPM
(b) Check and record oil pressure
(c) Check battery charging
(d) Check and record max.operating temperature
iv Check Leak From
(a) Fuel piping & injector high pressure lines
(b)Exhaust manifold flange & connections
(c) Engine oil filter and other areas
v Checking And Rectification of all safety controls indication and alarms such as
(a) Low lube Oil pressure gauges
(b)High cylinder head temperature cut off
(c) High water temperature gauges
(d) over speed relay
(e) low fuel alarm And indication
vi Checking of battery charger and its functioning like auto cut off, overcharging, reverse polarity, ammeter and voltmeter fuses, and rectify if found faulty. | - | each | - | - |
| 2Preventive maintanace contract of 1010 KVA DG set | |||||
| 2.001 | OD102234/2024-2025:Charge for carrying out periodical performance inspection, preventive maintenance, urgent repairs of Engine and Alternator side of 1010 KVA capacity Diesel generator set as per the standard preventive maintenance scope & conditions, including labour charge for replacing minor faulty components of DG set / standard control panel exist in the DG set etc...(excluding spares). Attending Emergency calls on Report, excluding cost of major maintenance works ( 4 preventive maintenance service per year)
Conditions of periodical preventive maintenance services
I Check Level And Top up
(a) Oil in engine
(b) Oil in air cleaner
(c) Oil in FIP
(d)Fresh water level in heat exchanger
(e) Water / coolent in radiator
(f)Electrolyte in battery
ii Check Tightness Of
(a) Battery terminal & apply Vaseline
(b) Fan belt
(c) Hose connections in cooling system
(d) Fuel piping connections
(e) Exhaust piping connections
(f)Engine mountings
(g)Engine drive unit coupling
(h) Electrical connections at instrument panel
iii Start And Run The Engine 10 Minutes
(a)Check and recording RPM
(b) Check and record oil pressure
(c) Check battery charging
(d) Check and record max.operating temperature
iv Check Leak From
(a) Fuel piping & injector high pressure lines
(b)Exhaust manifold flange & connections
(c) Engine oil filter and other areas
v Checking And Rectification of all safety controls indication and alarms such as
(a) Low lube Oil pressure gauges
(b)High cylinder head temperature cut off
(c) High water temperature gauges
(d) over speed relay
(e) low fuel alarm And indication
vi Checking of battery charger and its functioning like auto cut off, overcharging, reverse polarity, ammeter and voltmeter fuses, and rectify if found faulty. | - | each | - | - |
| 3Supply of Filter and oil for 2 nos 1010 KVA generators | |||||
| 3.001 | OD102235/2024-2025:supply of ELEMENT,LUB OIL FILTER | - | each | - | - |
| 3.002 | OD102236/2024-2025:supply of KIT,FUEL FILTER AND RING | - | each | - | - |
| 3.003 | OD102237/2024-2025:Supply of KIT SUPER BYP.FILTER ELEM | - | each | - | - |
| 3.004 | OD102238/2024-2025:supply of SEAL O RING | - | each | - | - |
| 3.005 | OD102239/2024-2025:Supply of VALVOLINE PREMIUM BLUE 7800PLUS 1/20 LTR | - | each | - | - |
stage.html
html • 0.02 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.04 MB
SBD.pdf
Tender Documents • 1.63 MB
AFFIDAVIT.pdf
Tender Documents • 0.03 MB
IP.pdf
Tender Documents • 0.02 MB
PRILIMI.pdf
Tender Documents • 0.64 MB
h.pdf
Tender Documents • 0.01 MB
SP.pdf
Tender Documents • 0.36 MB
LIST.pdf
Tender Documents • 0.19 MB
BOQ_1427125.xls
BOQ • 0.32 MB
T.pdf
Tender Documents • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .