Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 CrAccepted-Finance | ₹3.4 Cr | L1 | Accepted-Finance Accepted as L1 |
| 2 | L2₹3.4 CrAccepted-Finance | ₹3.4 Cr | L2 | Accepted-Finance Accepted as L2 |
| Sl No | Description | Qty | Unit | ELSTELLAR INTERNATIONAL PRIVATE LIMITED L2 | M/s SHREE BALA JI INFRATECH L1 |
|---|---|---|---|---|---|
| 1.00Note :- Rates should be filled with GST. | |||||
| 2.00LAYING PIPES | |||||
| 3.00 | Filling in foundation trenches as per drawing and technical specification Clause 305.3.9
Sand filling | 30.6 | Cum | 2,983.37 ₹91,291.12 | 2,977.39 ₹91,108.13 |
| 4.00 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size) | 6.3 | Cum | 9,852.76 ₹62,072.39 | 9,833 ₹61,947.90 |
| 5.00EARTHWORKS | |||||
| 6.00 | Excavation in foundation for retaining, breast walls etc, in all types of soils and rocks including all lead, lift and disposal of surplus material as per direction of engineer - in - charge, as per drawing and technical specifications Clause 305.1 of MORD Specifiction | 894.4 | Cum | 681.02 ₹6.1 L | 679.66 ₹6.1 L |
| 7.00 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. | 414 | Cum | 264.73 ₹1.1 L | 264.19 ₹1.1 L |
| 8.00 | Providing concrete for plain/ reinforced concrete in open foundations complete as per drawings and technical specifications Clause 802, 803, 1202 & 1203 P.C.C grade M 15 Nominal mix (1:2.5:5) | 115.81 | Cum | 8,796.69 ₹10.2 L | 8,779 ₹10.2 L |
| 9.00 | Providing and laying pitching on slopes laid over prepared filter media as per drawing and technical specifications Clause 1302 Stone/Boulder | 728.66 | Cum | 2,274.58 ₹16.6 L | 2,270 ₹16.5 L |
| 10.00 | Dry stone pitching 22.5 cm thick including supply of stones and preparing surface complete. | 420.73 | Sqm | 1,192 ₹5.0 L | 1,190.46 ₹5.0 L |
Tender Value
₹3.4 Cr
EMD Value
₹6.9 L
Closing Date
17 Jun 2025, 3:00 pmClosed
Superintending Engineer, 7th Circle PWD Gopeshwar
Office of Superintending Engineer, 7th Circle PWD Gopeshwar
Construction of Amphitheatre in Mana Haat under Mana Master Plan in District Chamoli
2025_pwd_84550_1
2063/544 Yata-07/2025 Dated 28.05.2025
Open Tender
Civil Works - Buildings
Mana
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,900
EE PIU PWD Badrinath
₹6.9 L
Yes
23 Dec 2025
2 Jun 2025
17 Jun 2025
2 Jun 2025
17 Jun 2025
3 Jun 2025
Amount
Note :- Rates should be filled with GST.
LAYING PIPES
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 Sand filling
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size)
EARTHWORKS
Excavation in foundation for retaining, breast walls etc, in all types of soils and rocks including all lead, lift and disposal of surplus material as per direction of engineer - in - charge, as per drawing and technical specifications Clause 305.1 of MORD Specifiction
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Providing concrete for plain/ reinforced concrete in open foundations complete as per drawings and technical specifications Clause 802, 803, 1202 & 1203 P.C.C grade M 15 Nominal mix (1:2.5:5)
Providing and laying pitching on slopes laid over prepared filter media as per drawing and technical specifications Clause 1302 Stone/Boulder
Dry stone pitching 22.5 cm thick including supply of stones and preparing surface complete.
REINFORCED CEMENT CONCRETE
Plain/reinforced cement concrete in substructure complete as per drawings and technical specification Clauses 802, 804, 805, 806, 807, 1202 and 1204 R.C.C. grade M 25
Supplying, fitting and placing TMT bar reinforcement (Fe 415) in substructrue complete as per drawings and technical specification Clauses 1002, 1005, 1010 & 1202 (The reinforcement steel shall be procured from original (primary) steel producers as per clause no. 2011.3.1 of MORD specifications (First revision'2014) and IS 1786:2008 clause no. 1.6)
MASONRY WORKS
Providing & making Gabion structure with Mechanically Woven Double Twisted Hexagonal Shaped Wire mesh Gabion Boxes as per IS 16014:2012,MORTH Clause 2500, of required size, Mesh Type 10x12 (D=100 mm with tolerance of 2%), Zinic+10% Al alloy+PVC coated, Mesh wire diameter 2.7/3.7 mm (ID/OD), mechanically edged/selvedged with partitions at every 1m interval and shall have minimum 10 numbers of openings per meter of mesh perpendicular to twist, tying with lacing wire of diameter 2.2/3.2 mm(ID/OD), supplied @3% by weight of Gabion boxes, filled with boulders with least dimension of 200 mm, as per drawing, all complete as per directions of Engineer-in-charge.
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement: 4 coarse sand)
Providing and fixing cramps of required size & shape in RCC/ CC I Brick masonry backing with cement mortar 1:2 ( 1 cement :2 coarse sand), including drilling necessary hole in stones and embedding the cramp in the hole (fastener to be paid separately). Stainless steel cramps
Providing and fixing expansion hold fasteners on C.C. /R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete. Fastener with threaded dia 6 mm
BASES AND SURFACE COURSES
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in- charge (length of finished kerb edging shall be measured to calculate volume for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
Granular Sub-base with Close Graded Material (Table:- 400-1) By Mix in Place MethodConstruction of granular sub-base by providing well graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with smooth wheel roller to achieve the desired density, complete as per Technical Specification Clause 401 for Grading- I Material
Wet Mix Macadam laying Using Mechanical Paver ( Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub?base / base course on well prepared surface and compacting with vibratory roller to achieve the desired
Dry Lean Cement Concrete Sub- base (Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per table 600-1, cement content not to be less than 150 kg/ cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, laid with a paver with electronic sensor, compacting with 8-10 tonnes vibratory roller, finishing and curing.)
Geotextile Filter (Laying of a geotextile filter between pitching and embankment slopes on which pitching is laid to prevent escape of the embankment material through the voids of the stone pitching/cement concrete blocks as well as to allow free movement of water without creating any uplift head on the pitching.)
Providing weepholes in brick masonry/stone masonry, plain/reinforced concrete abutment, wing wall, return wall with 100 mm dia AC pipe extending through the full width of the structures with slope of 1(V):20(H) towards drawing face complete as per drawing and technical specification Clauses 614, 709, 1204.3.7
Providing and laying filter media with granular crushed aggregates as per specification to a thickness of not less than 600 mm with smaller size towards the soil and bigger size towards the wall and providing over the entire surface behind abutment, wing wall, return wall to the full height, compacted to firm condition complete as per drawing and technical specification Clause 1204.3.8
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement: 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge: Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Stone work (machine cut edges) for wall lining etc. upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade : (To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately) : Himalayan stone - exposed face fine dressed with rough backing 50 mm thick ( 450mm x 200mm) (Wall Cladding Stone)
Providing & Laying 100 mm thick cobble stone flooring over 20 mm (average) thick base of cement mortar 1:5 (1 cement : 5 coarse sand), side buttered with cement mortar 1:2 (1 cement : 2 stone dust) admixed with pigment to match the shade of stone and pointing with same mortar. Rajasthan Black Granite Cobble Stone Machine Cut, Four sides machine cut and two sides Rough Surface. (100x100x100) mm (±5% of size)
HORTICULTURE
Spreading of Sludge Farm Yard Manure or/and good Earth (Spreading of sludge farm yard manure or/ and good earth in required thickness (cost of sludge, farm- yard manure or/and good earth to be paid for
Grassing with ' Doobs' Grass (Grassing with 'Doobs' grass including watering and maintenance of the lawn for 30 days or more till the grass forms a thick lawn free from weeds and fit for moving including supplying good earth if needed) In rows 7.5 cm apart in either direction
Making Lawns including Ploughing and Dragging with 'Swagha' Breaking of Clod (Making lawns including ploughing and breaking of clod, removal of rubbish, dressing and supplying doobs grass roots and planting at 15 cm apart, including supplying and spreading of farm yard manure at rate of 0.18 cum per 100
RCC MANHOLE :
Providing and fixing in position FRP Recessed Cover with frame 600mm x 600mm, Capacity 25 Ton of required Shape & approved quality. pre-cast R.C.C. manhole cover and frame of required shape and approved quality
ELECTRICAL MANHOLES
EM-AB-1100x1100x1500mm ELECTRICAL & ELV MANHOLE
EM-B-600x600x900mm ELECTRICAL MANHOLE
EM-C-450x450x500mm ELECTRICAL & ELV MANHOLE
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soils / ordinary rock
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note:- Cement content considered in this item is @ 330 Kgs/CuM. Excess/ less cement used as per design mix is payable/recoverable separately).
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size)
Form Work : Centring and Shuttering for Foundations, footings, bases of columns, etc. for mass concrete
Centering and Shuttering for Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Centering and Shuttering for Suspended floors, roofs, landings, balconies and access platform
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more.
External Water Supply Work
Providing and fixing of 25 mm Outer dia 3 layer PP-R (Poly propylene Random copolymer) pipes confirming to IS:15801 UV stabilized & anti - microbial fusion welded, having thermal stability for hot & cold water supply, including all PP-R plain & brass threaded polypropylene random fittings, including trenching, refilling & testing of joints complete as per direction of Engineer-in-Charge.
Providing and fixing of 32 mm Outer dia 3 layer PP-R (Poly propylene Random copolymer) pipes confirming to IS:15801 UV stabilized & anti - microbial fusion welded, having thermal stability for hot & cold water supply, including all PP - R plain & brass threaded polypropylene random fittings, including trenching, refilling & testing of joints complete as per direction of Engineer-in-Charge.
Supply, intallation, Testing and Commisioning of 20 mm diameter Garden Hydrant with gun metal Ball Valve, Flexinble hose Connection Provision and all required accessories etc.
Making connection to Water Supply line / existing tank including breaking them in a systematic way with suitable excavation, dewatering, dismantling of the RCC or masonry wall or pipe line, passing the plumbing water line in the existing structure either through masonry or CC and providing suitable "Y" tee to the connect to existing pipe line, Reconstructions of dismantled existing structure according to the original one to bring to the working conditions tasting etc. complete.
Fire Fighting System
ISI Marked portable fire extinguisher, 4.5 kg CO2 type fire extinguishers complete in all respect including initial fill and wall suspension brackets & shall conform to IS 2878 Providing & Fixing of fire extinguishers with necessary accessories, stand, trolley, etc.
ELECTRICAL PART
LT PANELS
Supply, Installation testing & commissioning of medium Voltage sheet steel metal clad, compartmented cubicle Panel board. Detail specification shall be followed.
Shifting of panels from site store to the suitable location.
Assembling and wiring of component supplied separately.
Earthing all components, frame etc. to a common internal earth bar.
Connection, testing & commissioning.
Electrical contractor shall carry out the insulation test at site & all the readings shall be submitted in duplicate to the consultant or engineer-in-charge.
Supply, installation, testing and commissioning all accessories, supporting structure, hard ware etc to complete the job.
Supply, installation, testing and commissioning of necessary tools, hard ware, testing hard ware, testing equipment etc.
The rates for the distribution boards apart from the Breakers and instruments shall also include the following :
This schedule of Quantities shall be read in conjuction with the technical specification, General & Special conditions as well as all tender drawings.
Supporting rigid steel framework.
Cubicle type, 14 gauge CRCA sheet steel enclosed.
Proper bonding to earth.
Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.
Providing cable clamps / supports within distribution boards cable alley.
If any TPN ACB’s / MCCB, it shall be with adequate size of neutral link.
All MCB’s shall be of minimum 10 KA breaking capacity.
The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic releases upto 250 amps and miroprocessor based above 250 amps capacity, unless specified otherwise.
All motor feeders MCCBs shall be of motor duty.
Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.
Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.
IP 4X for all Indoor panel.
IP 54 and double door.
All MCCB’s shall be provided with operating mechanism for door interlock.
All measuring instruments (Meters) shall be of digital electronic with LED of approved make.
All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
All panels shall have provision of the following:
Pad locking of Switch board doors.
Pad locking of MCCB’s handles in “OFF” Position.
All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic.
All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.
SPD as shown in SLD
Aprooved Makes-L&T/ABB/schnider/Legrand/SIEMENS
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door (IP43, IK09)
Supplying and fixing following rating, four pole, 415 volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 25A
Supplying and fixing following rating, Double pole, 240volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 32A
Supplying and fixing of weatherproof enclosure for four pole/DP, MCB (6A-32A) complete with connections, testing and commissioning etc. as required. Approved Makes-LEGRAND / SCHNIEDER / SIEMENS / L&T / ABB
Supply, installation, testing and commissioning 'B' series, SP MCB Supply, installation, testing and commissioning 5 amps to 32 amps rating, 240 volts, 'B' series, miniature circuit breaker suitable for lighting and other loads of folloeing poles int the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
MV CABLES
Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required.
Upto 35 sq. mm
Laying and fixing of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written. Approved Makes- FINOLEX / RAVIN / POLYCAB / RR KABEL / GEMSCAB /KEI / HAVELLS
4C x 6 Sq.mm. CU XLPE armored cable
4C x 4 Sq.mm. CU XLPE armored cable
4C x 4 Sq.mm. CU Flexible cable
3C x 4 Sq.mm. CU Flexible cable
3C x 2.5 Sq.mm. CU Flexible cable
CABLE TERMINATION
Supply and Providing heavy duty double compression brass gland and lugs end terminations,IP 66 complete,SIBG type, for the cable specified under above item with Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland. Approved Makes- DOWELL’S / 3D / HEX JAINSON / COMET / HMI/CCI
4C x 6 Sq.mm. CU XLPE armored cable
4C x 4 Sq.mm. CU XLPE armored cable
4C x 4 Sq.mm. CU Flexible cable
3C x 4 Sq.mm. CU Flexible cable
3C x 2.5 Sq.mm. CU Flexible cable
INTERNAL WORKS
POINT WIRING
Supply, installation, connection, testing & commissioning of following outlet points as per Specification & IS. The unit rate shall be complete with all necessory complete wiring from LDB to respective switchboard & switchboard to Point, including the outlet points with connector, sockets & all necessory items require to complete job. A point shall include in addition to phase & neutral wire, earth continuity wire from LDB to the final termination at outlet points.
Cost includes all the wiring, outlet points shall be done in a surface / concealed manner with ISI approved rigid FRLS PVC, conduit of minimum 25 mm. dia. using 650 V FRLS copper conductor wire, modular switches with suitable plate, MS back box with brass chromium / cadmium plated machine screws etc.The cost shall also include the cost of the GI back plate, switches, Sockets). Contractor to measure lenght of wiring as per drawing given. No extra cost to be given for wiring.
Wire Size for Lighting circuit
Lighting circuit = 2 x 2.5 mm2 (P+N), 1 x 2.5 mm²(E)(from LDB to Switch board)
From Switch Board to Light Point = 2 x 1.5 mm2 (P+N), 1 x 1.5 mm²(E)
Power circuit (for heater and geyser) =2x4.0 sqmm (P+N) ,1x4 sqmm(E)
Cost of MCB shall not be considered in point rate.
Wherever sensor require, wiring to be done accordingly.
Making of zari in wall using only electric cutter and finishing the surface as it was.
earthing of fitting
electrical connection to the fixture from the out let point/ceiling rose.
Wire breaded PVC flexible conduit from ceiling point to light fixture.
Supply and fixing of supporting frame, hardware and n/c tools and tackles etc For Exhaust fan
CONDUIT & OTHER
Supply, installation, testing and commissioning of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
SITC of 16A / 20A Single Phase IP66 industrial Plug Point with metal clad plug Socket / plug top with 20A DP MCB including weather proof box cover plate etc, complete in all respect, include switch, box, plate, etc. equivalent to Legrand Make Cat No. 056661
Supply, installation, testing and commissioning of following sizes of Heavy class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32mm
EARTHING
S/L SWG GI wire in ground: Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including soldering etc. as required
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Supply, Installation, Testing and Commissioning of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 25.0 mm with copper coating thickness of 250micron tested as per IEC 62561-2 + Universal clamp (SS), 25mm + Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested OEC 2 25 + The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Under floor earth inspection pit. Cost include to have earth pit cover, testing of all things, etc. in all complete manner. Approved Makes-OBO/ JEFF/ JMV
LIGHT FIXTURES
FIXTURE - 40-45W Power Module LED: Supply, Installation, assembling, connection, testing & commissioning of post top light fixture equivalent to LED FIXTURE - 40-45W Power Module LED, -MOUNTED AT 4 METER HEIGHT POST TOP POLE :it's - Upper frame made in die-cast and sheet aluminium (thickness: 2.5mm), with threaded coupling G3/4" for fixing,Bottom frame with ring made in die-cast aluminium and two arms made in hotgalvanized steel, with flange for fixing equipped of a hole (diam. 28 mm) .Gasket between the upper and bottom frames. Painted with polyester powder coating in Metallaic Grey (As per Architectural requirement). IP Rating - IP 66.Height –690mm, Dia - 550mm, Weight - 11.5Kg, Area Exposed to Wind(S) - 0.105 m2. Power LED's Module (with CREE/ NICHIA/ OSRAM/ SEOUL SMD type LED’s with ESD=>8kV & Ceramic package are accepted. LED manufacturers tech sheet with buying documents should be submitted for verification. Individual LED's Minimum Luminous Flux (lm) is 139lm @ 350 mA (@ 85 °C) same should be supported by LED manufacturer's tech sheet) in compliance with IEC 62031(supporting type test report should be submitted), on Printed Circuit Board with metal core plate. Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 1.5kv(an additional surge protection device of 10kV also provided in-built the fixture). Optics with refractive lens (Polycarbonate), UV Resistant & Shock Resistance IK10.LM80 Reported LED Lifetime is L90@ 50,000hours minimum. (same should be supported by LM 80 report from NVLAP accredited lab) & Estimated LED Lifetime is L80 @ 100,000 hours(Ta-25°C) minimum..LM 80 report & TM 21 calculation should be submitted to support the same.The Light fixture shall be in compliance with IEC 60598-2-3; IEC 60598-1.(Supporting Test Report from NABL accredited Laboratory should be submitted) .LM79 report should be submitted from NABL accredited Laboratory. * Colour of light fixture shall be as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.Approved Make - NERI / BEGA / HEPER
Supply, Installation, assembling, connection, testing & commissioning of ARCHITECTURAL POLE (FOR POST TOP LIGHTING) 3.3M height Pole (Total height of the pole is 4m including post top) Made in combination of hot dip galvanised mild steel pipe sections 114mm dia. & 140mm dia. Arch. cast iron Base design starts with min 322mm Dia. ring, radially tapers to 140 mm for a height of min 235 mm matching to the drawing. Total weight of the base is min 15 Kgs. Decorative Ring-1 (140/114mm dia. – min 3kgs.) & Top Ring (weight- 3kgs.) are made of cast iron. Entire pole shall be made to provide pleasing aesthetics as approved by Concerned Engineer in-charge. After Fabrication, Entire Pole is hot dip galvanized(60 microns Minimum ) for the effective corrosion resistance . The hot dip Galvanised pole should be provided with an inbuilt junction box (Concealed) to fix 32A connectors and 6A MCB (to terminate incoming and outgoing armoured cables with glands and lulgs), at the bottom -the inbuilt box should have a flush door of suitable size. The decorative pedastal to be mounted on a suitable size steel plate. This mounting steel plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed RCC foundation. wind pressure calculation as per IS 875(part-3) & structural calculation report as per EN40 should be submitted to verify the pole design. Pole & it's parts are painted in 3 layer coating(coating thickness-100 microns minimum) in which 1st layer with etch primer, 2nd layer with epoxy primer & 3rd final layer with PU paint- customised colour Metallaic Grey (As per Architectural requirement). Adequate size cutout with opeanable hinged door should be provided on pole with necessary gasket to ensure water tight arrangement for pulling cables and installation of mcb, connectors etc, complete in all respect as per requirement and instruction of engineer in charge. Scope also includes necessary foundation, cable termination, earthing as per requirement, cable entry pipes, 3 core round flexible wire from junction box to light fixture etc. all require to complete job. * Colour of Pole shall be as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture. Approved Make - NERI / BEGA / HEPER
Floor Recessed : (STEP LIGHT) Supply, Installation, assembling, connection, testing & commissioning of LED FIXTURE - NGB-M1A,1W,LED,3000k, IP 67 Light NGB-M1A: The housing in light weight, made of high strength die cast aluminium and coated by static powder making it weather resistant.Top AL diecast cap for two way light output . Premium thermal management by high heat conductivity aluminum alloy and thermal fins. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP67 rated. Height – 87mm, Dia.-110mm, Weight - 0.25Kgs. Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. CRI > 80,P.F>0.9,voltage input AC100-277V,50/60Hz. In- Built Electronic Power Supply for LED Module,which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection. Estimated LED Lifetime is 70,000 hours minimum. . Sample Should be submitted for concerned engineer incharge for approval of light fixture. * Colour of light fixture shall be as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture. Approved Make - NERI-LED FIXTURE - NGB-M1A,1W,LED,3000k, IP 67/Bega/DW Windsor
Wall Recessed LED Step Light : (FOOT LIGHT) Supply,Installation, Testing and Commmisioning of IP68, IK10 protected Step Light Fixture. Fixture made of powder coated die cast alluminium with Toughened Glass cover and appropriate beam angle lens to be used as per requirement. The System level Luminous efficacy must be >90 Lumen/W. High Power LEDs at 1W/2W per LED. The driving current should be Minimum 350 mA per LED. CRI>70, CCT: 3000/6500 K. The integral electronic driver must be constant current and surge protection of min. 4KV(L-N) and efficiency >85%, PF>0.95 and input Voltage range of 90-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained. Light should include quick connecting cable coupled with various mounting accessories. Light output in Cool white or Warm White Colour as per engineers choice. Fixture must be in compliance with BIS With Stainless Steel Bracket for Wall Recessed LED Step Light : (FOOT LIGHT) * Colour of light fixture shall be as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture. Approved Make - NERI/Bega/DW Windsor
Landscape Bollard Supply, laying, connection and testing of Landscape Bollards 15Watts Bollard LED, IP66, 800/100mm. * Colour of light fixture shall be as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture. Approved Make - NERI/Bega/DW Windsor
Catenary LIGHT 104, 80-100W, Power Module LED, 3000K,>12000Lumens Supply, laying, connection and testing of Light 104 Upper frame made in aluminium, with quick coupling threaded G 3/4" for fixing to support. Bottom frame in aluminium, removable for access to the wiring and optical compartment. .Gasket in silicone between the upper and bottom frames. Pure polyester powder coating in Grey Colour. IP Rating - IP 66. Height – 225mm,Diameter - 420mm,Weight - 6.5Kg, Power LED Module with Company /brand name printed on PCB with the metal core plate.LED Chips of CREE/NICHIA/OSRAM/LUMILEDS make - same should be supported by LED manufacturer's tech sheet . Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection (an additional surge protection device of 10kV also provided in-built the fixture). Optics with refractive lens in PMMA/PC which should offer Symmetrical light distribtuion LED Lifetime >1,00,000hours@Ts 85°C. LM80 report from LED Manufacturer should be submitted. Safety test report as per IEC 60598 from UL/UL authorised/Intertek should be submitted. LM79 report also should be submitted from UL/UL Authorised/Intertek Laboratory. Sample should be submitted for approval from concerned engineer-in charge. Bracket & Accessories for Suspension Bracket for suspension of light fixture is made of mild steel .Support frame composed of a plate and counterplate for coupling rope with a self-locking screw M8 in stainless steel, suitable for steel ropes with diameter from Ø6mm to 12mm. Central element with a threaded connection G3/4 “female and locking screw M6 in stainless steel. Through the top bend (180°) can be inserted a cable type SJT-W 3X (max. AWG14).Maximum load 44 lb (20 kg). Bracket & it's parts are painted in 3 layer coating(coating thickness-100 microns minimum) in which 1st layer with etch primer, 2nd layer with epoxy primer & 3rd final layer with PU paint - customised colour Metallaic NERI Grey. Approved Makes-NERI/DW Windsor/GHM
JUNCTION BOXES
Supply, Transportation, Installation, testing and commissioning of IP 67 weather proof Outdoor type junction boxes with terminal equivalent to Hensel catalogue no KF 1006 G/OBO/CAPE
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes (225mm(L) X 295mm(B) X 122mm(H) with connector & including GEL. Equivalent to Hensel catalogue no KF 3500 C/OBO/CAPE
DWC PIPES
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
SITC of 315 mm dia (OD-315 mm & ID-271 mm nominal)
Providing & Laying of HDPE Pipe 32mm PE-80,PN6 direct in ground; to be laid 75-100cm below the ground level for drawing of cables including excavation and refilling the trench etc.as required, but excluding sand cushioning and protective covering,or G.I. conduit 32 mm dia( Heavy Duty) with concrete block 15cm X 15cm 1:2:4 with complete curing with splicing complete in all respect complete in all respect. Make: Jain/Dutron/Supreme/reliance
ELSTELLAR INTERNATIONAL PRIVATE LIMITED (BID ID -387175)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tenderdocument.pdf
Tender Documents • 7.09 MB
BOQ.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid