Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹29.9 L+₹4.9 L (19.8%)Rejected-AOC OPPOSITE VIPUL GAS AGENCY HOSPITAL ROAD SOLAN H P | SOLAN | SOLAN | HIMACHAL PRADESH | L2 | Rejected-AOC L2 | |
| 3 | L3₹33.3 L+₹8.4 L (33.6%)Rejected-AOC | L3 | Rejected-AOC L3 |
| Sl No | Description | Qty | Unit | ROYAL ENGINEERING WORKS L2 | M/S THAKUR ELECTRICAL & HARDWARE STORE L1 | Ajay Sharma L3 |
|---|---|---|---|---|---|---|
| 1.00 | LWSS Namhol 1st Stage
Supply and errection of horizontal spindle horizontal split casing/ multistages centrifugal/reciprocating pumps of standard make such as KSB/Mather platt / Kirlosker by the Department conforming to BIS-1520-1980 approprite IS/ISO 9001-2000 code ( with upto date ammendments ), read with IS: 9137-1978 or latest to handle clear water having turbidity 50 ppm.with impellers , casing ring &shaft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity where ever applicable coupled directli through a flexible coupling on a common base plate to Motor of Kirloskar/NGEFl/Crompton/Marathan/Jyoti and suitable for operation on 400 (+)/(-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with upto date ammendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discharge:-14.70 LPS, Total Dynamic Head :-330mtrs
Suction lift:-Positive, Dia of Rising Main :-125mm ,Length of R/Main :-1320mtrs, Pumping Hours:-16 Hours. | 1 | Per Set | 9,25,000 ₹9,25,000 | 8,00,000 ₹8,00,000 Lowest | 9,75,000 ₹9,75,000 |
| 2.00 | Supply, Installation, Testing and Commissioning of suitable electrical control Pannel cubical type powder coated with star-Delta-Starter push button type, main incomer MCCB of required capacity, Volt meter 0-500 volts,Ampare meter 100/5 Amp., ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB, power capacitor of required capacity under voltage/over voltage release, over current earth fault relays,suitable to operate all 415 volatage +,- 10% AC supply all equipments shall be of make of L&T/ Havells make complete in all respects including all required accessories of required capacity & any other fittings required as per site conditions & as per directions of Engineer-in-Charge. | 2 | Nos | 2,25,000 ₹4,50,000 | 1,95,000 ₹3,90,000 Lowest | 2,15,000 ₹4,30,000 |
| 3.00 | Providing and laying copper PVC insulated armoured power Multi core cable (one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor & as per directions of Engineer-in-Charge.
a) Motor side: suitable capacity/ size Min length = 20 mtrs.
b) Supply side:suitable capacity/ size Min. length =20 mtrs. | 1 | Job | 55,000 ₹55,000 | 47,000 ₹47,000 Lowest | 50,000 ₹50,000 |
| 4.00 | Supply of Kirloskar/Kilburn/Leader/of reputed make of suitable size cast iron flanged sluice valve confirming to IS 780, size equal to dia of suction pipe PN 1 Provided with hand wheel/Cast iron Cap. | 2 | Nos | 15,000 ₹30,000 | 11,000 ₹22,000 Lowest | 13,500 ₹27,000 |
| 5.00 | Supply of Kirloskar/Kilburn/Leader/ make cast iron flanged screwed type foot valve with strainer of dia equal to dia of suction pipe conforming to BIS 4038-1986 or latest with upto date ammendments. | 2 | Nos | 2,500 ₹5,000 | 1,000 ₹2,000 Lowest | 3,500 ₹7,000 |
| 6.00 | Supply & erretion of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually, of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.) | 2 | Nos | 7,500 ₹15,000 | 6,500 ₹13,000 Lowest | 8,000 ₹16,000 |
| 7.00 | Supply of standard make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with upto date ammendments. | 2 | Nos | 1,500 ₹3,000 | 1,475 ₹2,950 | 500 ₹1,000 Lowest |
| 8.00 | Errection of all equipments i/c cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge. | 1 | Job | 45,000 ₹45,000 | 40,000 ₹40,000 Lowest | 55,000 ₹55,000 |
| 9.00 | LWSS Namhol IIIrd Stage
Supply and errection of horizontal spindle horizontal split casing/ multistages centrifugal/reciprocating pumps of standard make such as KSB/Mather platt / Kirlosker/WASP by the Department conforming to BIS-1520-1980 approprite IS/ISO 9001-2000 code ( with upto date ammendments ), read with IS: 9137-1978 or latest to handle clear water having turbidity 50 ppm.with impellers , casing ring &shaft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity where ever applicable coupled directli through a flexible coupling on a common base plate to Motor of Kirloskar/NGEFl/Crompton/Marathan/Jyoti and suitable for operation on 400 (+)/(-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with upto date ammendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discharge:-6.16 LPS per set, Total Dynamic Head :-267.64mtrs 2 sets (1No Working+ 1 Std by )
Suction lift:-Positive, Dia of Rising Main :-80mm ,Length of R/Main :-1435mtrs, Pumping Hours:-16 Hours. | 2 | Per Set | 4,65,000 ₹9,30,000 | 3,70,000 ₹7,40,000 Lowest | 5,95,000 ₹11,90,000 |
| 10.00 | Supply, Installation, Testing and Commissioning of suitable electrical control Pannel cubical type powder coated with star-Delta-Starter push button type, main incomer MCCB of required capacity, Volt meter 0-500 volts,Ampare meter 100/5 Amp., ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB, power capacitor of required capacity under voltage/over voltage release, over current earth fault relays,suitable to operate all 415 volatage +,- 10% AC supply all equipments shall be of make of L&T/ Havells make complete in all respects including all required accessories of required capacity. | 2 | Nos | 1,15,000 ₹2,30,000 | 90,000 ₹1,80,000 Lowest | 1,35,000 ₹2,70,000 |
Tender Value
₹26.3 L
EMD Value
₹52,550
Closing Date
11 Dec 2025, 2:00 pmClosed
EE JSV Division Jagatkhana
EE JSV Division Jagatkhana
Restoration of rain Damages of LWSS Namhol in Tehsil Sadar District Bilaspur (H.P) (SH Replacement of Old Pumping Machinery with allied accessories of LWSS Namhol 1st 3rd stage and laying jointing testing of rising main of 80mm dia)
2025_HPIPH_122262_1
8047-8146 Dated 29-11-2025
Open Tender
Civil Works - Others
Item Rate
Namhol
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,500
₹52,550
17 Mar 2026
1 Dec 2025
11 Dec 2025
1 Dec 2025
11 Dec 2025
1 Dec 2025
Amount
LWSS Namhol 1st Stage Supply and errection of horizontal spindle horizontal split casing/ multistages centrifugal/reciprocating pumps of standard make such as KSB/Mather platt / Kirlosker by the Department conforming to BIS-1520-1980 approprite IS/ISO 9001-2000 code ( with upto date ammendments ), read with IS: 9137-1978 or latest to handle clear water having turbidity 50 ppm.with impellers , casing ring &shaft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity where ever applicable coupled directli through a flexible coupling on a common base plate to Motor of Kirloskar/NGEFl/Crompton/Marathan/Jyoti and suitable for operation on 400 (+)/(-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with upto date ammendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:- Discharge:-14.70 LPS, Total Dynamic Head :-330mtrs Suction lift:-Positive, Dia of Rising Main :-125mm ,Length of R/Main :-1320mtrs, Pumping Hours:-16 Hours.
Supply, Installation, Testing and Commissioning of suitable electrical control Pannel cubical type powder coated with star-Delta-Starter push button type, main incomer MCCB of required capacity, Volt meter 0-500 volts,Ampare meter 100/5 Amp., ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB, power capacitor of required capacity under voltage/over voltage release, over current earth fault relays,suitable to operate all 415 volatage +,- 10% AC supply all equipments shall be of make of L&T/ Havells make complete in all respects including all required accessories of required capacity & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Providing and laying copper PVC insulated armoured power Multi core cable (one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor & as per directions of Engineer-in-Charge. a) Motor side: suitable capacity/ size Min length = 20 mtrs. b) Supply side:suitable capacity/ size Min. length =20 mtrs.
Supply of Kirloskar/Kilburn/Leader/of reputed make of suitable size cast iron flanged sluice valve confirming to IS 780, size equal to dia of suction pipe PN 1 Provided with hand wheel/Cast iron Cap.
Supply of Kirloskar/Kilburn/Leader/ make cast iron flanged screwed type foot valve with strainer of dia equal to dia of suction pipe conforming to BIS 4038-1986 or latest with upto date ammendments.
Supply & erretion of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually, of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.)
Supply of standard make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with upto date ammendments.
Errection of all equipments i/c cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
LWSS Namhol IIIrd Stage Supply and errection of horizontal spindle horizontal split casing/ multistages centrifugal/reciprocating pumps of standard make such as KSB/Mather platt / Kirlosker/WASP by the Department conforming to BIS-1520-1980 approprite IS/ISO 9001-2000 code ( with upto date ammendments ), read with IS: 9137-1978 or latest to handle clear water having turbidity 50 ppm.with impellers , casing ring &shaft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity where ever applicable coupled directli through a flexible coupling on a common base plate to Motor of Kirloskar/NGEFl/Crompton/Marathan/Jyoti and suitable for operation on 400 (+)/(-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with upto date ammendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:- Discharge:-6.16 LPS per set, Total Dynamic Head :-267.64mtrs 2 sets (1No Working+ 1 Std by ) Suction lift:-Positive, Dia of Rising Main :-80mm ,Length of R/Main :-1435mtrs, Pumping Hours:-16 Hours.
Supply, Installation, Testing and Commissioning of suitable electrical control Pannel cubical type powder coated with star-Delta-Starter push button type, main incomer MCCB of required capacity, Volt meter 0-500 volts,Ampare meter 100/5 Amp., ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB, power capacitor of required capacity under voltage/over voltage release, over current earth fault relays,suitable to operate all 415 volatage +,- 10% AC supply all equipments shall be of make of L&T/ Havells make complete in all respects including all required accessories of required capacity.
Providing and fixing of double flanged GI/GMSERW piping network for suction and delivery pipes situable to pump offered and common header as per the rising main respectively complete with all special such as rappers, flanges, rubber gasket minimum 3 mm in thickness as per IS:2712-1979, nuts and bolts as per IS:1364-1983, bends, tees reducers/increaser with with companion flanges matching with the relevant specifications of the accessories as per drawing up to 5 mtr away from the outer wall of pump houses. The pipes shall be as per relevant IS code and to withstanb 1.50 times total head stipulated. The size of various components are as under:- Suction pipe one step higher then delivery of pump minimum length= 12 Metre Delivery pipe equal to dia of pump delivery minimum length= 12 Metre Common header equal to dia of pump delivery minimum length= 10 Metre The GMS tube confirming to IS:1239-1979 part-I medium class flanged with MS Flanges of table 5 in suction pipe and heavy class flanged with MS Flanges of table 17in delivery side and common header.
Providing and laying copper PVC insulated armoured power Multi core cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/ make from metre of HPSEB to MCB and from MCB to bus bar switch and starter including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. a) Motor side: suitable capacity/ size Min length = 20 mtrs. b) Supply side:suitable capacity/ size Min. length =20 mtrs.
Supply of Kirloskar/KSB/Leader/ of reputed make of suitable size cast iron/cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52 Kg/cm²
Supply of Kirloskar/KSB/Leader of suitable size cast iron/Cast Steel double flanged swing check type reflux valve having bye pas arrangement & size equal to delivery of Pump for withstanding nominal seat pressure of 52Kg/cm²
Supply of Kirloskar/KSB/Leader of suitable size Cast Iron/Cast Steel double flanged swing check type reflux valve having bye pass arrangement & size equal to dia of R/Main for withstanding nominal seat pressure of 52 Kg/cm²
Supply of Kirloskar/KSB/Leader/of reputed make of suitable size cast iron flanged sluice valve confirming to IS 780, size equal to dia of suction pipe PN 1 Provided with hand wheel/Cast iron Cap.
Supply of Kirloskar/KSB/Leader make cast iron flanged screwed type foot valve with strainer of dia equal to dia of suction pipe conforming to BIS 4038-1986 or latest with upto date ammendments.
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt, G.I. Pipes, thimbles, nuts & bolts, digging of pits, G.I.wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments for above motors & other electrical equipment.
Supply & erretion of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually, of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.)
Supply of standard make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with upto date ammendments.
Providing/Laying suction, delivery pipe considering site requirements, NPSH required & available & common header having area equal to two times the area of delivery branch of pump including tapers, flanges, rubber gaskets, 3mm thick as per BIS-2712-1978 nuts & bolts as per 1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings approved by Engineer-in-Charge. The pipes shall be capable of with standing 1.5 times the total pressure indicated in item No. 1e(ii).
supply of antivibration pads conforming to BIS 6337-1971 or latest with upto date ammendments of suitable size for above machinery.
Errection of all equipments i/c cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Excavation in foundation, trenches ( for pipes & pits) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing and pumping out water, blasting soft/ hard rock or chieselling soft/hard rock where blasting is prohibited in all lifts including trimming and dressing of sides, leveling of beds to correct grade i/c shoring /strutting , planking, timbering & dewatering wherever required, stacking the useable & unuseable material /soil separately & after laying jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposoited layer by ramming & watering & then disposing of all surplus excavated soil /unusable material as directed with in all leads & lifts including restoration unmetalled surfaces to its original condition & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with in all leads & lifts as per directions of engineer-in-charge. (Pick Work)
Laying, Jointing and testing galvanized mild steel tube screwed and socketed in trenches of following dia. including tube fittings such as bends, tees, reducers, unions etc. complete and to the entire satisfaction of the Engineer-in-charge (earth work in trenches to be measured and paid for separately).
80 mm dia (Medium Class)
Providing circumferential butt welded joints by electrical arc welding of GMS/ MSERW welded in requiste number of weld runs so as to achieve the minimum effective throat thickness of weld conforming to IS: 816-1969 specifications by using welding electrodes of 2.5mm to 6.3mm of Advani Orelon (Adore)-CITOJET/ESAB make, conforming to IS: 814-1991 at site of work complete in all respect, including manual/ mechanical handling of pipe in all leads and lifts and to the entire satisfaction of the Engineer-in-charge.( Butt welding joints of various dia).
80 mm dia (Medium Class)
65 mm dia ( Light Class)
ROYAL ENGINEERING WORKS (BID ID -592690)
Ajay Sharma (BID ID -593110)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
PWD6.pdf
Tender Documents • 0.42 MB
PWD8.pdf
Tender Documents • 1.32 MB
Termsconditions.pdf
Tender Documents • 0.67 MB
BOQ_179419.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .