Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.6 LAccepted-AOC 362 SUBHASH NAGAR PO CLEMENT TOWN DEHRADUN UTTARAKHAND | L1 | Accepted-AOC Accepted Being Lowest. | |
| 2 | L2₹41.4 L+₹2.9 L (7.39%)Rejected-AOC | L2 | Rejected-AOC Rejected Being Lowest. | |
| 3 | L3₹42.5 L+₹3.9 L (10.2%)Rejected-AOC 4578 STREET 15 15A AGGARWAL ROAD DARYAGANJ CENTRAL DELHI DELHI 110002 UDYAM DL 01 0031798 | CENTRAL DELHI | DELHI | 110002 | L3 | Rejected-AOC Rejected Being Lowest. | |
| 4 | L4₹43.8 L+₹5.2 L (13.4%)Rejected-AOC | L4 | Rejected-AOC Rejected Being Lowest. |
Tender Value
₹46.3 L
EMD Value
₹92,580
Closing Date
6 Feb 2020, 5:00 pmClosed
CWE No 2 Meerut
Commander Works Engineer No 2 Military Engineer Services Boundary Road, Near Supply Depot Meerut Cantt-250001
SPECIAL REPAIR REPLACEMENT OF OCB TO VCB AT MRS ROORKEE UNDER GE ROORKEE
2019_MES_310083_1
95083/RKE/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Roorkee
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE Roorkee
₹92,580
Yes
5 Mar 2020
30 Dec 2019
8 Feb 2020
30 Dec 2019
6 Feb 2020
11 Jan 2020
Amount
Taking out after disconneting electrically and mechanically carefully, unserviceable existing OCB (Oil circuit breaker) any make and type with all connected items/ accessories and deposit to E&M Store yard including trasportation, loading and unloading upto EM Yard complete all as directed by Engr in charge.
M & L Design, manufacture, testing, supply, receiving, unloading, storing, inspection, handling, assembling, installing in correct assigned position, effecting proper connections, testing and commissioning of HT panel 1 way consisting of 11 KV, 800 Amps, 18/18.4 kA extensible Indoor type VCB's, metal clad drawout type , The VCB shall be enclosed in CRCA sheet enclosure, copper bus bar enclosed in robotically welded and tested as per latest IEC standard incl connecting to existing VCB/OCB any Make available at site all as specified and as directed by Engr in charge. The unit shall include the following with all necessary standard fitting required at site:- Note 1: Contractor shall visit site to access existing system of VCB/OCB's before quoting rate for above item. Note 2: Rep of accepting officer will visit factory of manufacturer and all expenses shall be borne by contractor and these are deemed to be inclusive of quoted rate. Incomer VCB :- (a) Fabrication. 11 KV 1000 A Copper bus bar indoor panel board with following jumpers 1000 A and adaptor box for connecting existing panel complete all as specified and directed by EIC - 01 No (b) VCB- 11 KV, 18/18.4kA/1Sec electronic draw out VCB of rating 800Amp incl earthing truck Make: Schneider Model HVX or Equivalent in ABB/Seimens.
Item No 2 Continue....... (g) Misc (i) Breaker control switch, Make : Salzer/Eqvt - 01 No (ii) L/R switch, Make : Salzer/Eqvt - 01 No (iii) Emergency push button, Make : Schneider/L&T - 01 No (iv) LED, Make : Reputed - 01 Nos (v) 3 Pin Plug - Socket, Make : Reputed - 01 No (vi) Toggle switch, Make : Reputed - 01 No (vii) Hooter , Make : Reputed - 01 No (viii) Door Switch, Make : Reputed - 01 No (ix) Space heater with thermostat - Make : Reputed - 01 No (x) Control MCB , Make : Schneider/Eq - 01 No (h) Earthing Truck for Cable Side and bus side - 01 No.
M & L Design, manufacture, testing, supply, receiving, unloading, storing, inspection, handling, assembling, installing in correct assigned position, effecting proper connections, testing and commissioning of HT panel 1 way consisting of 11 KV, 800 Amps, 18/18.4 kA extensible Indoor type out going VCB's, metal clad drawout type , The VCB shall be enclosed in CRCA sheet enclosure, copper bus bar enclosed in robotically welded and tested as per latest IEC standard incl connecting to existing VCB/OCB any Make available at site all as specified and as directed by Engr in charge. The unit shall include the following with all necessary standard fitting required at site:- Note 1: Contractor shall visit site to access existing system of VCB/OCB's before quoting rate for above item. Note 2: Rep of accepting officer will visit factory of manufacturer and all expenses shall be borne by contractor and these are deemed to be inclusive of quoted rate. Out going VCB :- (a) Fabrication. 11 KV 800 A Copper bus barm indoor panel board with following jumpers 800 A and adaptor box for connecting existing panel complete all as specified and directed by EIC - 01 No (b) VCB. 11 KV, 18.4kA/1Sec electronic draw out VCB of rating 400Amp, Make: Schneider Model HVX or Equivalent in ABB/Seimens. (c) CTs. 11 KV dual Ratio dual core CTs with following ratio : 200-100/5-5A, Core CI1: 1.0, 5Va and Core CI2: 5P10,15VA , Make : Savio/AVCON/Tushar - 03 Nos
Supply and fixing of cable jointing kit 11 KV (earthed) grade cable for indoor Termination (Cold shinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm sqmm complete all as specified and directed.
Supply and fixing of cable jointing kit 11 KV (earthed) grade cable for Out door Termination (Cold shrinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120Sqmm to 185 Sqmm complete all as specified and directed.
M & L for Chemical earthing complete with 900x 600 x 5 mm size brazed copper plate burried directly in ground vertically in pit of size 120 x 120 cm depth not less than 5.30 metre below normal ground level with top edge of the earth plate at a depth not less than 4.70 metre below normal ground level surrounded from all sides with mixture of one layer each of MgSO4 of size 120 x 120 x 5 cm at bottom & 120 x 120 x 5 cm at top, in remaining portion 15 layers of charcoal (each layer of 0.23 cu. m) and 14 layers of salt (each layer of 0.23 cu. m) in alternate layers and electrode connected to earth lead of copper earth strip of size 50 x 6 mm by means of brass bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore dia (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 50 mm bore medium grade GI pipe with holes of 1 to 2 cm dia on all four sides at an interval of 15 cm for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified. NOTE: (i) The unit rate includes earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point.and earth repaort shall be submitted by Contractor to EIC. (ii) Additional Chemical compound is deemed to be included in the above item no extra payment will be made in this account to achieve earth resistance less than 1 ohm.
M & L Copper strip 32 x 6 mm including provision of copper nut and bolts for fixing on wall at intervals of one metre apart, including taking down existing copper strip, complete all as directed and as specified.
Supply laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 3 core 150 sq mm complete all as specified and directed.
Supply laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 3 core 185 sq mm complete all as specified and directed.
Taking down old rusted galvanized iron pipe and providing galvanized pipe 100 mm bore light grade in trenches / road / nallah or fixed along wall/ pole including mild steel clamps, screws etc, complete all as specified and directed.
Excavation in trenches/post holes in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for laying of pipes and for poles/stay and struts not exceeding 10 Sqm on plan and getting out, excavated earth, forming bottom surfaces to required level complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in soft/loose soil complete all as specified and directed.
Removing surplus soil to a distance not exceeding 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point complete all as specified and directed.
Supply and laying sand river for cushioning with layers of sand 8 cm before lying of cable and 15 cm after lying of cable (total 23 cm) in trenches complete all as specified & directed. ( Note: Thickness after punning shall be measured for payment )
Supply & Laying in replacement of reinforced precast concrete cable cover class HV, flat size 300x180x40mm complete all as specified and directed.
Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for removing of existing cable and rerouting in underground the same cable and returning filling (including old bricks/cable covers) the same after rerouting/same trenches in any type of soil complete all as specified and directed. Note :- Old retrieved reusable bricks will be used for laying of cable.
SHRI RAM ENTERPRISES
M/s Kamal Traders
Amit Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .