Tender Value
₹14.5 L
EMD Value
₹29,000
Closing Date
29 Oct 2021, 6:00 pmClosed
Garrison Engineer Kota
Dadwara Complex, Military Station, Kota - 324001
SPL REPAIR/REPLACEMENT OF LT PANEL ALONGWITH CONNECTED WORK OF ELECTRIC SUPPLY AT WATER PUMP HOUSE AT SOUTHERN SECTOR AT MIL STN KOTA
2021_MES_478816_1
8567/E8
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
Kota
Class E category b(i)
8 documents required · 8 mandatory
₹500
GE Kota
₹29,000
Yes
16 Nov 2021
30 Sept 2021
6 Nov 2021
30 Sept 2021
29 Oct 2021
14 Oct 2021
1 Oct 2021 - 7 Oct 2021
Amount
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth or n exc 10 Sqm on plan and n exc 1.5 m in depth & getting out, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes or for laying underground cable, pipe lines etc. in soft/ loose soil, complete all as specified & directed.
Returning, filling in soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed.
Removing excavated material (soil) n exc. 50m distance and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and directed.
Cutting of road / hardstanding upto a size not exceeding 20 cm in width and not exceeding 60 cm in depth for laying of LT UG cable protection pipe line, making good the disturbed portion so as to match existing finishing or with PCC 1:2:4 type B1 complete all as specified and directed.
M&L dry clean sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover complete all as specified and directed. Note:- Thickness after punning shall be considered for payment.
M&L for pulverized fuel Ash-lime bricks (Fly ash bricks - non modular size), class 10, laid dry and flat adjoining each other over sand cushion in trenches as protection to UG cable, complete all as specified and directed.
M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized earth strip of 25x4 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: - (a) Irrespective of whatever is shown in plate No 3 of SSR, earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b) Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m.
S&F in renewal of 50 mm bore Steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed.
S&F in renewal of 80 mm bore Steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed.
Supplying, laying, jointing, testing and commisioning XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 1100 Volt grade (ISI marked), laid in trenches / ducts / encased in GI pipe / fixed to pole/wall with necessary angle iron support, clamp, nut , bolts etc and including taking down old unserviceable existing XLPE LT UG cables complete all as specified and directed for following cross sectional areas of cables :- Cross Sectional area of cable 150 Sqmm, 3.5 core
Cross Sectional area of cable 120 Sqmm, 3.5 core
Cross Sectional area of cable 70 Sqmm, 3.5 core
Cross Sectional area of cable 50 Sqmm, 3.5 core Notes for Srl item Nos. 20.10 to 20.70 :- (i) Excavation, earth work, sand cushioning, cable protection cover & GI pipes shall be measured and paid for separately under respective items of BOQ. (ii) Rate deemed to be inclusive of connecting up with control gear including cable glands and cable lugs.
Supplying, installation, commissioning and testing (including CPRI type test certified) of outdoor type, weather proof, factory made LT feeder pillar box (Kiosk) of approx size 1.0x1.2x0.5m (as per Indian Electricity Rules), protection class IP-65 made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated aluminium bus bar of 400 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including 40x40x6mm thick angle iron frame work at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: - (A) INCOMING: - (a) Aluminium bus bar of rating 150 Amps for four pole & including PVC heat shrink sleeves (RYB&N) - 01 Set (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 36 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
Supplying, installation, commissioning and testing (including CPRI type test certified) of outdoor type, weather proof, factory made LT feeder pillar box (Kiosk) of approx size 1.0x1.2x0.5m (as per Indian Electricity Rules), protection class IP-65 made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated aluminium bus bar of 400 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with FRLS cable, IS-694 marked of adequate size but not less than 4 Sqmm with new lugs, gland to be provided at cable entries and including 40x40x6mm thick angle iron frame work at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: - (A) INCOMING: - (a) Aluminium bus bar of rating 100 Amps for four pole & including PVC heat shrink sleeves (RYB&N) - 01 Set (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 36 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
Item 14.00 Contd........ (B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 250 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 02 Nos. (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 200 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 02 Nos. (c) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 02 Nos. (d) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 02 Nos. (e) MCB, 415 volts, AC, three pole & neutral, 32 Amp, breaking capacity 16 KA – 01 No. Note :- (i) Necessary approval of drawings of cubical type LT panel board shall be approved by GE before placing order by the Contractor. (ii) Cost of above aspects is deemed to be included in quoted rates.
Item 15.00 Contd........ (B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 03 Nos. (b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 03 Nos. (c) Security light timer - 01 No. Note :- (i) Necessary approval of drawings of cubical type LT panel board shall be approved by GE before placing order by the Contractor. (ii) Cost of above aspects is deemed to be included in quoted rates.
Disconnection of electric connection from existing LT Panel, dressing of cable ends including repair of body of LT panel, repair/welding work of gates, hinges of the door including rewiring by copper conductor control cables of suitable size, replacement of burnt out aluminium lugs and fixing new lugs, nuts bolt etc, replacment of unserviceable accessories/components of LT Panel such as MCCB, voltmeter, ameter, indicator lamp etc including painting of LT panel complete with inner & outer with two coats of synthetic enamelled paint using spray painting machine, necessary excavation & earth work required for taking out & refixing the incoming and out going cables etc, complete all specified and directed. Note :- Renewal of unserviceable accessories/components like MCCBs, Bus bar, Volt meter, Ameter & Indicator lamp etc shall be measured and paid separately under appropriate items as supply only. However cost of fixing the same shall be deemed included in the unit rates of this item.
Renewal of following unserviceable accessories/components of LT panel (Compatible for BOQ serial item No 17.00 here-in-before), complete all as specified and directed: - Supply only MCCB, 4 pole, 415 volts, 50 Hz, AC, 400 Amp rating with rupturing capacity 36 KA, adjustable thermal and adjustable magnetic setting, confirming to IEC: 60947-II /IS - 13947-II, complete all as specified and directed.
Supply only MCCB, 4 pole, 415 volts, 50 Hz, AC, 250 Amp rating with rupturing capacity 36 KA, adjustable thermal and adjustable magnetic setting, confirming to IEC: 60947-II /IS - 13947-II, complete all as specified and directed.
Supply only MCCB, 4 pole, 415 volts, 50 Hz, AC, 200 Amp rating with rupturing capacity 36 KA, adjustable thermal and adjustable magnetic setting, confirming to IEC: 60947-II /IS - 13947-II, complete all as specified and directed.
Supply only MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KA, fixed thermal and fixed magnetic setting, confirming to IEC: 60947-II /IS - 13947-II, complete all as specified and directed.
Supply only MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA, fixed thermal and fixed magnetic setting, confirming to IEC: 60947-II /IS - 13947-II, complete all as specified and directed.
Supply only aluminium bus bar of 400 amps rating, complete all as directed.
Supply only phase indicator LED type indicating lamp (RYB) with copper control wiring, complete all as specified and directed.
M/s Prem Associates
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .