EXECUTIVE ENGINEER,ELECTRICAL (R & B) DIVISION, JUNAGADH
Providing & Erecting Passenger Lift in Taluka court at Gir Gadhada, Dist. Gir Somnath.
355713
E-Tender Notice No.07 of 2026-27
Open
Electrical - All
Works
Junagadh
15 documents required · 15 mandatory
₹900
Executive Engineer, Electrical (R&B) Division, Junagadh
₹11,000
15 Oct 2026
15 Oct 2026
15 Oct 2026
29 Oct 2026
15 Oct 2026
Name of work :- Providing & Erecting Passenger Lift in Taluka court at Gir Gadhada, Dist. Gir Somnath
Sr. Qty Unit Item of work Net Rate Rate in word Per Amount
1 2.00 Nos Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C Curve) having 10KA breaking capacity & 811.03 Rupees Eight Hundred Eleven Ea
confirms to IS :8828 in existing box having following capacity (c)63 Amp. Cat-III Paise Three Only
2 1.00 Nos Sheets steel powder coated enclosure suitable for incorporating One/Two nos. MCB. 176.75 Rupees One Hundred Ea
SeventySix Paise SeventyFive
3 3.00 Nos Plastic enclosure fitted with DIN rail suitable for incorporating Three /Four nos. MCB 108.07 Rupees One Hundred Eight Ea
Paise Seven Only
4 1.00 Nos providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit 2166.45 Rupees Two Thousand One Ea
withstand capacity of 10 KA and suitable for operation on single phase 240 V,50Hz. having characteristic of quick action & Hundred SixtySix Paise
tripping with all advance feature & do not incorporate any electronic component. for following Max. rating erected as
FourtyFive Only
directed (i) 25 Amps.DP Cat-III
5 1.00 Nos Providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit 3344.11 Rupees Three Thousand Ea
withstand capacity of 10 KA and suitable for operation on 3 phase and neutral 415V,50Hz. having characteristic of quick Three Hundred FourtyFour
action & tripping with all advance feature & do not incorporate any electronic component for following Max. rating erected
Paise Eleven Only
as directed.(iii) 63 Amps. FP Cat-III
6 0.80 Kgs. Providing and erecting required size Copper strip for earthing of H.T. OCB / ACB/ Transformer, LT panel board, Motors 794.87 Rupees Seven Hundred Kg.
etc. using copper clamp. NinetyFour Paise
EightySeven Only
7 2.00 Nos Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in- 4591.46 Rupees Four Thousand Five Ea
Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm Hundred NinetyOne Paise
having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising, connection terminal dia of
12mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for
following type of applications with chamber and heavy duty cover. (A)(approved make OEM has to submit test certificate
including value of earth resistance of installation duly stamped and signed by agency and officer Incharge has to ensure
the value of earthing resistane mentioned in test Certificate) & having back filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form,
Sulphar content:- <2%(C) Back fill Compound :- Earthing compound should be capable to retain moisture for long time
Necessary test report must be submitted by Agency. (a) For Electrical Installation up to 440V in normal soil Length of pipe -
1 Mtr Back filling compound - 1 Nos Bag of 15 Kg.
8 50.00 Mtrs Providing and erecting FRLS-XLPE (IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 kV. to be 184.83 Rupees One Hundred Mtr
laid on wall with necessary clamps or in existing trench / pipe of following size of cables (A) 4 core 16 Sq. mm EightyFour Paise EightyThree
9 2.00 Nos Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable 47.47 Rupees FourtySeven Paise Ea
complete with out going tails, insulating tape etc for following size of cables.(D) 2 to 4 core 16 Sq. mm FourtySeven Only
10 8.00 Nos Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high 15.15 Rupees Fifteen Paise Fifteen Ea
pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (C) 16/25 Only
[1] GEAR LESS LIFT DRIVE (with Machine Room) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent
Magnet Synchronous motor of proper rating with high efficiency shall be used.[2] Micro processor based / PLC, ACVVVF,
vector control drive with encoder feedback closed loop system shall be used for lift car and door operation which shall be
full collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with
overload and phase reversal relay and safety controls.
[3] Car with M S platform with bracings of adequate size and to sustain the impact load cabin + passenger with safety
factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car ceiling will be S.S. finishes with
aesthetic appearance with LED ceiling lights. Car flooring shall be of s/s 304 chaker plate design suggested of engineer in
charge. of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety
device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language as per lift
[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside [5] Appropriate
battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should
start immediately without any Time Delay as soon as power fails.[6] Digital scrolling indicator system for up-down arrow
along with floor position indicator shall be provided inside the car and at all floors.[7] Full height infra red curtain with
multiple cross / crossing light beams shall be provided.
[8] Automatic Rescue Device (ARD) shall be provided accordingly of passenger capacity with Manual Rescue Operation (
Manual Cranking Facility). [9] Audio visual indication in the lift car showing over loading shall be provided such that doors
kept open till excess load is removed.
[10] Spring buffers/PU Buffers shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.
[12] Voice annunciator with suitable music shall be provided in lift car. [13] Self diagnostics system for operational and
safety parameters shall be provided in control panel.[14] Mechanical over speed governor with governor calibration as per
actual site parameters and submission of calibration certificate submission, door key holes in the floor doors, fireman
switch shall be provided.[15] Lift machine hoisting arrangement in the lift machine room and monkey ladder for lift pit
should be provided by the lift agency, along with the other steel structure works, foundations for the machine etc…[16] In
the hoist way fascia plate shall be provided without any extra cost, where ever required as / if directed by engineer in
[17] Permanent wiring with necessary safety devices like RCCB in all circuit, Over Voltage Under Voltage protection and
THD eliminator in circuit for lift machine room and lift well with proper numbers of light points, with fixtures, exhaust fan
and plug points shall be provided by the agency. Only 3 phase Power Supply shall be made available by department in lift
machine room. Necessary Earthing as per Lift Act/Rules shall be arranged by Lift Agency.
[18] Any civil/ electrical works for additional and alteration in lift shaft and machine room related to erection of lift shall be
made by lift agency without any extra cost. (granite/marble fixing around all landing door openings are not in lift agency’s
scope.)[19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary
permission from lift inspector and other authorities. [20] acrylic transparent licence/display A4 size holder in lift car
[20A] As per statutory requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide 1. Car top safety
barricade2. Push & talk communication system.3. Fireman's switch operation at Ground Floor. 4.carrying out third party
lift inspection during/after lift erection and provide report by third party authorized by concern licensing authority
5.agency has to provide third party insurance up to completion of free maintenance period and submit the document for
[21] Car Panel Operating Buttons at an accessible height from wheelchair for handicapped person and raised numbers
with brail mark with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin.
[22] For Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at
appropriate 900mm height on the Rear & Side Wall Panels in Lift Car. [23] With Necessary kVA rating voltage
controlled Stabilizer suitable for your controller, drive and all equipments of lift. [24] Necessary rating of DP Elcb and FP
Elcb required for lift is in scope of work which rating is sugested by CEICED Department (electrical Inspector)
(B) SPECIAL FEATURES DESCRIPTION OF LIFTS for PREMIUM category
1. Advanced control system dual 64 bit embedded microprocessor with CANBUS Serial Communication mode including
Regenerative power efficient operation,on site programming facility, Anti nuisance, Pte-opening, BMS/RMS with necessary
online real time monitoring system having necessary connectivity for remote monitoring & other suitable supporting
hardware & software devices to fulfil the purpose.
2. Floor Indication LCD Display with call registration & brail mark with arrival gong and hall lantern & TFT Screen in the car
with MP3 Voice Announcer.
3. CAR Panel should be Scratch resistive SS Moonrock finish / Hair Line / Honeycomb for car and all Doors, All landing
doors must have fire rating up to 2 hours and car door must have multi-level crisscross beam door protection.
4. To & fro communication system & wiring (i.e. car , control room & guard room ) and Each elevator are equipped with
remote monitoring system.agency has to provide mobile app and user id and password for monitoring
11 1.00 Nos Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:4/5/6 995546.90 Rupees Nine Lakh NinetyFive Ea
Passengers, Ground plus 1 upper floor with Rated Speed of 1.0 m/sec,(C) With General PLUS ADDITIONAL SPECIAL Thousand Five Hundred
FEATURES attached herewith. Prem. Cat.(For Machine room Lifts, rate for Rs. 1,50,000/- is deducted in Total Cost for the
FourtySix Paise Ninety Only
Lifts from 4 to 13 Passenger Lift.)
Amount put to tender Rs
Rupees Ten Lakh TwentyTwo Thousand Four Hundred FiftySix Paise NinetyFour Only
(A) Total Tendered Amount Rs..…..……………….…………...…………….
(B) Rebate on above tendered amount (if any)………………..…..%(in Figure) Rs….………………….………………………...
(C) Net tendered amount (A-B) Rs……………………………………………….
All work shall be carried out as per Public Works Department Handbook and other specification of Division or as directed
Rates quoted include clearance of site (prior commencement of work and at its close) in all respects and hold good for work under all conditions, site, moisture, weather
Signature of Contractor Deputy Executive Engineer
Electrical R&B Sub Division
Executive Engineer
Electrical ( R & B ) Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Schedule-A.pdf
Schedule-B.pdf
E- Tender Notice No.07 of 2026-27.pdf
General Specification of lift.pdf
Standard Bidding Document.pdf
Pq latest.pdf
Notice Inviting Online Tender.pdf
Year Wise Amount Details.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .