Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.1 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹12.1 L+₹2.1 L (20.4%)Admitted-Finance | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | IMPERIAL ENGINEERING SERVICES L2 | M/s ELITE ELECTRICALS L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Frequency Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :100-50/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make) | 1 | Job | 5,30,000 ₹5,30,000 | 4,75,000 ₹4,75,000 Lowest |
| 2.00 | Supply, Carriage upto site (including Loading/Unloading), Testing and Erection of Steel Tubular Pole, 9 Mtr. Long Pole(ST-410 SP33) with planting depth of 1/6 th of the height of the pole, (9 mtr. Long ) as per approved drawings/standards | 2 | No. | 17,500 ₹35,000 Lowest | 18,000 ₹36,000 |
| 3.00 | Carriage upto site (including Loading/Unloading), Laying ,Stringing, Tensioning & Binding of ACSR Conductor, (100mm2 ACSR Conductor) (Conductor to be provided by the department) as per approved drawings/standards | 60 | Mtr | 30 ₹1,800 Lowest | 30 ₹1,800 Lowest |
| 4.00 | Supply, Carriage upto site (including Loading/Unloading),Testing,Fabrication & Fixing of GI Channel/Angle/Flat of sizes including clamps as per approved drawings/standards | 300 | Kg. | 125 ₹37,500 Lowest | 136 ₹40,800 |
| 5.00 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm as per approved drawings/standards | 3 | No. | 195 ₹585 Lowest | 200 ₹600 |
| 6.00 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting as per approved drawings/standards | 3 | No. | 500 ₹1,500 | 400 ₹1,200 Lowest |
| 7.00 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, Horizontal mounting Type, with Earth Switch (Reputed Make, Sample to be approved before installation) as per approved drawings/standards (1 Set- 3 Pieces) | 1 | Set | 30,000 ₹30,000 Lowest | 45,000 ₹45,000 |
| 8.00 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type (Reputed Make) as per approved drawings/standards (1 Set-03 No.) | 1 | Set | 3,800 ₹3,800 | 3,000 ₹3,000 Lowest |
| 9.00 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip 25x3mm as per approved drawings/standards | 2 | No. | 600 ₹1,200 Lowest | 600 ₹1,200 Lowest |
| 10.00 | Supply,Testing,Loading,Carriage,Unloading and fixing of Galvanised Nuts & Bolts of sizes | 30 | Kg | 115 ₹3,450 Lowest | 143 ₹4,290 |
Tender Value
₹12.3 L
EMD Value
₹24,580
Closing Date
11 Aug 2025, 11:00 amClosed
EXECUTIVE ENGINEER STD Sopore
EXECUTIVE ENGINEER STD Sopore
Supply,Installation,Testing and Commissioning of 11 KV Indoor Switchgear to be installed at Receiving Station Achabal for Construction of Dedicated Outgoing 11 KV Feeder for Achabal Hatchery.
2025_PDD_281008_1
STDS/07 of 2025-26
Open Tender
Electrical Works
Turn-key
45 days
STD Sopore
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,003
Yes
Executive Engineer STD Sopore
₹24,580
Yes
18 Aug 2025
11 Jul 2025
11 Aug 2025
11 Jul 2025
11 Aug 2025
13 Jul 2025
11 Jul 2025 - 13 Jul 2025
Amount
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Frequency Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :100-50/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make)
Supply, Carriage upto site (including Loading/Unloading), Testing and Erection of Steel Tubular Pole, 9 Mtr. Long Pole(ST-410 SP33) with planting depth of 1/6 th of the height of the pole, (9 mtr. Long ) as per approved drawings/standards
Carriage upto site (including Loading/Unloading), Laying ,Stringing, Tensioning & Binding of ACSR Conductor, (100mm2 ACSR Conductor) (Conductor to be provided by the department) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing,Fabrication & Fixing of GI Channel/Angle/Flat of sizes including clamps as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, Horizontal mounting Type, with Earth Switch (Reputed Make, Sample to be approved before installation) as per approved drawings/standards (1 Set- 3 Pieces)
Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type (Reputed Make) as per approved drawings/standards (1 Set-03 No.)
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip 25x3mm as per approved drawings/standards
Supply,Testing,Loading,Carriage,Unloading and fixing of Galvanised Nuts & Bolts of sizes
Supply,Testing,Loading,Carriage,Unloading and fixing of Danger Plates with Clamps as per approved drawings/standards
Supply,Testing,Loading,Carriage,Unloading and fixing of Anti-Climbing Device with Clamps as per approved drawings/standards
Providing & Painting of Poles with one coat of Red Oxide and two coats of aluminium paint and as per approved drawings/standards
Supply,Carriage upto site (including Loading/Unloading), Laying & Testing of Cement bottoming for ST Poles 9 Mtr in the mixture of 1:2:4 0.48 cum/pole as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 36 V,200 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply of reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Battery Bank 36 V,200 AH , of 18 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant of reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 11kV Three core 240 mm2 Aluminium wound wire Armoured XLPE FRLS Cable (KIE/Havells/Polycab make)as per approved drawings/standards
Providing & Construction of 500 m Cable Trench by laying of Reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size including centring shuttering works, 15mm plastering (1:6), fabrication & fixing of 8 mm thick chequered plates, TMT Bars 10 mm dia along along rings for RCC & Loading/Carriage/Unloading of required material as per the drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11 kV Heat Shrinkable Outdoor Cable Termination Kit suitable for 240 mm² ( 3 Core) cable (3M/VIKCHEM/Denson make) as per standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 11 kV Heat Shrinkable Indoor Cable Termination Kit suitable for 240 mm² ( 3 Core) cable (3M/VIKCHEM/Denson make) as per standards
CONTENGENCIES /T&P/Spares
Supply, Carriage upto site (including Loading/Unloading),Testing of 12 KV Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :400-200/5-5A as per standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing of Complete Charging/ Gear Mechanism suitable for 11KV VCB
Supply of A4 Papers 75 GSM of standard Quality
Supply of Printer Cartridge suitable for HP laser Printer (110 A)( HP OEM Make)
Supply, Carriage upto site (including Loading/Unloading),Testing of 30-36 VDC Tripping coils suitable for 11KV VCB
Supply, Carriage upto site (including Loading/Unloading),Testing of Manila Rope
Supply, Carriage upto site (including Loading/Unloading) of Gas Nozle suitable fo Heat shrink termination Kits
Supply, Carriage upto site (including Loading/Unloading),Testing of 33 KV Grade Rubber Gloves as per relevant IS (Standard Make)
IMPERIAL ENGINEERING SERVICES (BID ID -2435002)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .