Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.1 CrAdmitted-Finance | ₹2.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.1 Cr+₹25,484.52 (0.12%)Admitted-Finance | ₹2.1 Cr+₹25,484.52 (0.12%) | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical bid is non responsive |
| 4 | Rejected-Technical 4TH FLOOR 4B P 118 PS PHOOL BAGAN CIT ROAD SCHEME VI M KOLKATA KOLKATA WEST BENGAL 700034 | KOLKATA | WEST BENGAL | 700034 | - | - | Rejected-Technical bid is non responsive |
| Sl No | Description | Qty | Unit | Saklani Electrical works L1 | Shubham Traders L2 |
|---|---|---|---|---|---|
| 1.00 | Supply installation, testing, and commissioning of outdoor waether-proof LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screwless glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects.
Cubical : Supplying and erecting weather proof (IP-66) GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting, etc. and painting with one coat of red lead paint and 2 coats of enamel paint.
Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification - 1 set
Incomer: Supplying, erecting & marking FPMCCB micro-processor 63A C series in provided distribution board as per specification - 1 No.
Outgoing: Supplying, erecting & marking FP MCB 6A to 32A, C series in provided distribution board as per specification - 4 Nos.
Outgoing: Supplying, erecting & marking SPN MCB 6A to 32A, C series (for lighting) in provided distribution board as per specification - 8 Nos.
Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral as per specification no. - 1 nos.
Supplying, installation & marking of 63A FP ATS - 1 nos.
Supplying & erecting single phase 3 wire system (Channel) having inbuilt astronomical adjustable programmable timer with with auto/manual switch, 2 pole contactor with DP MCB 32 A, with maintenance mode to switch ON for outgoing circuits - 4 Nos. | 1 | nos | 2,45,551 ₹2,45,551 Lowest | 2,45,700 ₹2,45,700 |
| 2.00 | Supply,installation, testing and commissioning of 25KVA outdoor waether-proof the servo voltage stabilizer of following ratings, 3-phase, Copper winding, 50HZ Frequency, Unbalanced input voltage and unbalanced load, Volt/ampere meter CT's, input voltage range- 360V-480V, output voltage range- 410-420V adjustable | 1 | Nos | 1,24,533.5 ₹1,24,533.5 Lowest | 1,24,700 ₹1,24,700 |
| 3.00 | Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, suitable for cable termination. Built-in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 | 4 | Nos | 3,785 ₹15,140 Lowest | 3,791 ₹15,164 |
| 4.00 | Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 | 6 | Nos | 2,742 ₹16,452 Lowest | 2,745 ₹16,470 |
| 5.00 | Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011 | 8 | Nos | 2,625 ₹21,000 Lowest | 2,630 ₹21,040 |
| 6.00 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 225 mm width X 50 mm depth X 1.6 mm thickness | 20 | Mtrs | 951 ₹19,020 Lowest | 952 ₹19,040 |
| 7.00CONDUITS | |||||
| 8.00 | 25 mm dia. ISI marked, PVC conduit | 200 | Mtrs | 150 ₹30,000 Lowest | 155 ₹31,000 |
| 9.00 | 25 mm dia. ISI marked, steel conduit | 80 | Mtrs | 272 ₹21,760 Lowest | 275 ₹22,000 |
| 10.00 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | 8 | Nos | 14,650 ₹1,17,200 Lowest | 14,652 ₹1,17,216 |
Tender Value
₹2.1 Cr
EMD Value
₹4.2 L
Closing Date
11 Mar 2024, 3:00 pmClosed
PM BRIDCUL Dehradun
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
SITC of LED Illumination/Facade Lighting work at Mahasu Devta Temple at Hanol District Dehradun
2024_BRID3_70994_1
1888/BRIDCUL/233/24 Dated 27.02.2024
Open Tender
Electrical Works
Item Rate
180 days
Mahasu Devta Temple Hanol Dehradun
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
Project Manager, Project Unit Dehradun, BRIDCUL
₹4.2 L
12 Mar 2024
5 Mar 2024
11 Mar 2024
5 Mar 2024
11 Mar 2024
6 Mar 2024
Amount
Supply installation, testing, and commissioning of outdoor waether-proof LT panel suitable for 415 V, 3 phase 4 wire 50 Hz AC supply system, RYB LED indicators, VAF digital metering. Cable entry and outgoing are only with suitable sizes of screwless glands, including with all accessories copper bus bar, din rails, earth links, neutral links, glands, locks, connectors, operation complete with all respects. Cubical : Supplying and erecting weather proof (IP-66) GI sheet 1.6 mm (16 SWG) to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling, welding, riveting, etc. and painting with one coat of red lead paint and 2 coats of enamel paint. Supplying and erecting bus bar chamber triple pole with neutral with four copper bars, 500V, 100A complete as per specification - 1 set Incomer: Supplying, erecting & marking FPMCCB micro-processor 63A C series in provided distribution board as per specification - 1 No. Outgoing: Supplying, erecting & marking FP MCB 6A to 32A, C series in provided distribution board as per specification - 4 Nos. Outgoing: Supplying, erecting & marking SPN MCB 6A to 32A, C series (for lighting) in provided distribution board as per specification - 8 Nos. Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral as per specification no. - 1 nos. Supplying, installation & marking of 63A FP ATS - 1 nos. Supplying & erecting single phase 3 wire system (Channel) having inbuilt astronomical adjustable programmable timer with with auto/manual switch, 2 pole contactor with DP MCB 32 A, with maintenance mode to switch ON for outgoing circuits - 4 Nos.
Supply,installation, testing and commissioning of 25KVA outdoor waether-proof the servo voltage stabilizer of following ratings, 3-phase, Copper winding, 50HZ Frequency, Unbalanced input voltage and unbalanced load, Volt/ampere meter CT's, input voltage range- 360V-480V, output voltage range- 410-420V adjustable
Supply, installation, testing and commissioning of the PC (Polycarbonate) Termination junction box (IP66), terminal with 2 clamping units per pole 5-pole per pole, 4 x 4 mm² r / f, included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm with one cable entries M 32 from the rear side lid fasteners sealable without accessories external brackets for wall fixing included colour: grey, RAL 7035, rated insulation voltage Ui = 690 V a.c./d.c., in accordance with IEC 60670-22, suitable for cable termination. Built-in dimensions W 210 x H 155 x D 92 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. Built in dimensions W 170 x H 220 x D 96 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supply installation testing & commisioning of Empty box (IP66) with installation equipment on DIN rails or mounting plates (order separately) with opaque lid fastener for tool operation sealable box walls without knockouts external brackets for wall fixing included, colour: grey, RAL 7035, material: PC (polycarbonate) mounting plate, glands and complete with all required accessories and hardware to complete the job in all resepcts. built in dimensions W 215 x H 320 x D 106 (Tolerance ± 10%) material: PC (polycarbonate), impact strength IK 09 (10 Joule), in accordance with IEC 62208:2011
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 225 mm width X 50 mm depth X 1.6 mm thickness
CONDUITS
25 mm dia. ISI marked, PVC conduit
25 mm dia. ISI marked, steel conduit
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing of 25mmx5mm copper strip on surface or in recess for connection etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Supply installation testing and commissioning of 8.0-meter height 140mm dia, C class MS pole, anthracite grey paint, with plate mounting arrangement, plate size 450mm X 450mm X 20mm suitable for bracketless direct lighting fixture installation on pole concorete foundation.
Suppy of LT cable XLPE/PVC insulated 650/1100 volt of following size Aluminium armoured cable as per IS 7098 PART 1. 3.5C x 25 Sq.mm. Aluminum XLPE armored cable
Suppy of following size of LT cable XLPE/PVC insulated 650/1100 volt of following size Copper armoured cable as per IS 7098 PART 1.
4C x 6 Sq.mm. CU XLPE armored cable
4C x 4 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
3C x 2.5 Sq.mm. CU XLPE armored cable
Supply and Providing heavy duty double compression brass gland and lugs end terminations,IP 66 complete,SIBG type, for the cable specified under above item with Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland.
4C x 6 Sq.mm. CU XLPE armored cable
4C x 4 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
3C x 2.5 Sq.mm. CU XLPE armored cable
3.5C x 35 Sq.mm. Aluminum XLPE armored cable
Excavating trenches by mechanical means of required width for pipes,cables,etc,including excavation for socketsand dressing of sides ramming of bottoms for all depth including getting out the excavated soil and then returning the soil as required,in layers not excedding 20 cn in depth including consolidating each deposited layer by ramming within a lead of 50m.
pipes,cables not exceeeding 80mm dia
pipes,cables not exceeeding 80mm dia but not exceeding 300 mm dia
DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.in the existing trench,complete as required
63 mm dia (OD-63 mm & ID-51 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1KV grade of following size in existing RCC/DWC/HUME/METAL/overhead/open space pipeas required
Upto 35 sq. mm
EXTERIOR LIGHT FIXTURES
1000mm ±15% Linear LED 12W ±15%, 800 lumens ±15% - 2700K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, 1000mm ±15% long linear rigid light complete with visor and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 12 watts ±15%, 800 lumens delivered ±15%, 30 x 70° beam angle with a tolerance of ±15%, CCT-2700K. The housing material should be extruded aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have silicon glue between the optical cover and the LED chamber and shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
1000mm ±15% Linear LED 15W ±15%, 800 lumens ±15% - 2200K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, 1000mm ±15% long linear light complete with visor and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 15 watts ±15%, 1100 lumens delivered ±15%, 14 x 50° beam angle with a tolerance of ±15%, CCT-2200K. The housing material should be extruded aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have silicon glue between the optical cover and the LED chamber and shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
500mm ±15% Linear LED 15W/M ±15%, 800 lumens / M ±15% - 2200K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, 500mm ±15% long linear light complete with visor and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 15 watts / M ±15%, 1100 lumens /M delivered ±15%, 14 x 50° beam angle with a tolerance of ±15%, CCT-2200K. The housing material should be extruded aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have silicon glue between the optical cover and the LED chamber and shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
300mm ±15% Linear LED 15W/M ±15%, 800 lumens / M ±15% - 2200K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, 300mm ±15% long linear light complete with visor and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 15 watts / M ±15%, 1100 lumens /M delivered ±15%, 14 x 50° beam angle with a tolerance of ±15%, CCT-2200K. The housing material should be extruded aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have silicon glue between the optical cover and the LED chamber and shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
1000mm ±15% Linear LED 12W ±15%, 800 lumens ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, 1000mm ±15% long linear light complete with visor and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 12 watts ±15%, 1100 lumens delivered ±15%, 10 x 30° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be extruded aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have silicon glue between the optical cover and the LED chamber and shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
300mm ±15% Linear LED 10W ±15%, 600 lumens ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, 300mm ±15% long linear light complete with visor and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 10 watts ±15%, 700 lumens delivered ±15%, 10 x 30° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be extruded aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have silicon glue between the optical cover and the LED chamber and shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Neon flex washer LED 10W / M ±15%, 800 lumens / M ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP67, Neon flex washer mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 10 watts / M ±15%, 800 lumens / M delivered ±15%, 10 x 30° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be silicon rubber. It should have CRI>80, and SDCM≤4. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK04. The operating temperature should be of -40°C to 45°C range. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
The driver should be remote 24V DC non dimmable (IP67) with PF>0.9 & and THD<20%. Wattage will be calculated as per site fixture looping
Round flood LED 15W ±15%, 1000 lumens ±15% - 2200K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP66, round flood light complete with antiglare snoot and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 15 watts ±15%, 1000 lumens delivered ±15%, 10° beam angle with a tolerance of ±15%, CCT-2200K. The housing material should be die cast aluminum with Electrostatically applied polyester powder coating, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. It should have CRI>80, and SDCM≤4. The driver should be non integrated DC, and fixture size should not be more than 100mm dia and 200mm length, with PF>0.9 & and THD<20%. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Round flood LED 20W ±15%, 1000 lumens ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP66, round flood light complete with antiglare snoot and mounting with the bracket on an 8m high pole. The power consumption should be 20 watts ±15%, 1000 lumens delivered ±15%, 3° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be die cast aluminum with Electrostatically applied polyester powder coating and the bracket shall be made of cold-rolled iron plate which allows tiltability of ± 90 deg, a locking mechanism to fix and secure the required tilting angle, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. The driver should be integrated, with PF>0.9 & and THD<20%. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Round flood LED 24W ±15%, 1700 lumens ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP66, round flood light complete with antiglare snoot and mounting with the bracket on an 8m high pole. The power consumption should be 24 watts ±15%, 1700 lumens delivered ±15%, 30° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be die cast aluminum with Electrostatically applied polyester powder coating and the bracket shall be made of cold-rolled iron plate which allows tiltability of ± 90 deg, a locking mechanism to fix and secure the required tilting angle, The luminaire body color should be similar to the facade color surface where the luminaire is to be installed with anti-aging and anti-UV high optical efficiency PMMA lenses and a clear tempered glass cover. Fixture shall have a breather gland to avoid condensation of water. It should have CRI>80, and SDCM≤4. The driver should be integrated, with PF>0.9 & and THD<20%. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range and storage temperature shall be -40°C to 70°C. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The product shall comply to and shall have test repots for IEC 60598-2-5:2015, IEC 60598-1:2014 + A1, IEC TR 62778:2014 (for LED chips), EN IEC 55015:2019+A11, EN 61547:2009, EN 61000-3-2:2019, EN 61000-3-3:2013, IS 10322 (Part 5/Sec5):2013, LM80. Manufacturers self-declaration shall be uploaded confirming to compliance of CE Declaration of Conformity, CQC declaration of conformity, RoHS compliance & ASTM B117 for 500 hours. All hardwired connections to LED fixture shall be reverse-polarity protected and shall provide high-voltage protection in the event that connections are reversed or shorted during installation. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Square wall mounted downlight, 6W ±15%, 300 lumens ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor/wall mounted IP66, square wall-mounted downlight fixture complete with and mounting with 3M VHB/UHB tape or adhesive without any clips/crew/any hardware which shall damage the surface of the temple. The power consumption should be 6 watts ±15%, 300 lumens delivered ±15%, 15° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be die cast aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface. It should have CRI>80, and SDCM≤4. The driver should be remote 24V DC non dimmable (IP67) with PF>0.9 & and THD<20%. Leader cables, jumper cables, and IP68 connectors are included. Minimum IK06. The operating temperature should be of -20°C to 50°C range. The lifetime of the luminaire (L70 @ Ta-35deg C) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. All mounting accessories shall be stainless steel (Minimum -316) for all lighting fixtures. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Round 450mm-600mm high bollard, 10W ±15%, 400 lumens ±15% - 3000K: Supply installation testing and commissioning of exterior-rated architectural floor-mounted IP65, round 450-500mm high bollard fixture complete with mounting on a concrete foundation. The power consumption should be max 10 watts ±15%, 400 lumens delivered ±15%, 360° beam angle with a tolerance of ±15%, CCT-3000K. The housing material should be extruded aluminum, a powder-coated finish, The luminaire body color should be similar to the facade color surface. It should have CRI>70, and SDCM≤5. The driver should be integrated 24V DC non dimmable (IP67) with PF>0.9 & and THD<20%. IP68 connectors are included. Minimum IK08. The operating temperature should be of 0°C to 45°C range. The lifetime of the luminaire (L70) should be at least 50,000 burning hours. Luminaire should have corrosion resistance with self-declaration of ASTM B117 for 500 hours of salt spray test. The luminaire should be BIS-certified. This includes all the required hardware for the successful operation of the luminaire. (All the technical parameters of the luminaire need approval from the lighting consultant)
Supply installation testing & commissioning of OF12-Channel Mixing Console Max. 6 Mic / 12 Line Inputs (4 mono + 4 stereo). 2 GROUP Buses + 1 Stereo Bus. 2 AUX (incl. FX). D-PRE” mic preamps with an inverted Darlington circuit. 1-Knob compressors. High-grade effects: SPX with 24 programs. 24-bit / 192kHz 2in / 2out USB Audio functions. Works with the iPad (2 or later) through the Apple iPad Camera Connection Kit / Lightning to USB Camera Adapter. Includes Cubase AI DAW software download version. PAD switch on mono inputs. +48V phantom power XLR balanced outputs. Internal universal power supply for worldwide use.
Supply installation testing & commissioning of Dynamic cardioid microphone for speech and vocals with noiseless on/ off switch Cuts through high on-stage levels Clear reproduction with a high presence Consistent sound quality (varying distances, moving off-axis) Handles high sound pressure levels Isolates handling noise, hum compensating coil Excellent feedback rejection.
Supply installation testing & commissioning of 2 core 14 AWG/2.5 Sq mm, Twisted, unshielded Speaker cable with stranded annealed bare copper conductors, Semi-rigid PVC insulation, NEC CL3R, CEC CMG, RoHS compliant.
Supply installation testing & commissioning of 2 core Twisted, shielded balanced Audio and control cable with 22AWG or better 7 strand annealed bare copper conductors, Semi-Rigid PVC insulation, Riser rated PVC jacket. UL 444, UL 13 CMR rated.
Customised Floor Raceway
Supply installation testing and commissioning of Outdoor rated surface-mounted powder-coated aluminum alloy having wall thickness of a minimum of 3MM on all sides, with width limited to 300 MM or less and height limited to 60 MM or less, to house IP66-rated light fixtures as per the BoQ, wiring management and IP68 GEL connectors for internal connections, and to withstand load of 20 MM to 50 MM thick stone on top, for walkover application. It should have proper end caps to cover and protect the wiring. as per the detailed drawing given.
Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
REINFORCED CONCRETE & PLAIN CEMENT CONCRETE
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
FLOORING WORKS
Regional Stone work (machine cut edges) for wall lining,flooring etc. (veneer work) upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade :
50 mm thick fine dressed & chamferd stone flooring over 20 mm (average) thick base of cement mortar 1:5 (1 cement : 5 coarse sand), including pointing with cement mortar 1:2 (1 cement : 2 stone dust) with an admixture of pigment to match the shade of stone.
Local Hammer dressed stone of size (450x300x50)mm
Providing, mixing and applying bonding coat of approved adhesive on chipped portion of Stone as per specifications and direction of Engineer-In-charge complete in all respect. Epoxy bonding adhesive having coverage 2.20 sqm/kg of approved make
Shubham Traders
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_85246.xls
BOQ • 0.39 MB
SBDNEW.pdf
Tender Documents • 1.96 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .