Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.2 LAccepted-AOC GROUND FLOOR F 11 PHASE II MAYAPURI WEST DELHI DELHI 110064 | DELHI | WEST DELHI | DELHI | 110064 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹34.7 L+₹15.0 L (76.2%)Rejected-Finance 490 41 ROORKEE ROAD NEAR SHAHARANPUR BUS STAND MUZAFFARNAGAR UTTAR PRADESH 251002 | MUZAFFARNAGAR | UTTAR PRADESH | 251002 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹36.8 L+₹17.1 L (87.0%)Rejected-Finance 59 NEW MARKET CLOCK TOWER DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹37 L
EMD Value
₹74,000
Closing Date
11 May 2023, 6:00 pmClosed
GE AF AMBALA
GE AF AMBALA
GE AF/AMB-T-65/2022-23 REPAIR/MAINT OF PUMP SETS, DG SETS, STP, WATER PIPE LINES, UNDERGROUND SUMPS, SWT, INTERNAL ELECTRIFICATION, CEILING FANS, COOLING APPLIANCES, DESERT COOLERS, VOLTAGE STABILIZERS, EARTHING PITS, REPAIR TO LT PANELS, STREET
2023_MES_587785_1
GE AF/AMB-T-65/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
GE AF AMBALA
ALL AS PER NIT AND TENDER DOCUMENTS
10 documents required · 10 mandatory
₹500
Yes
GE AF AMBALA
₹74,000
Yes
13 Jun 2023
31 Mar 2023
13 May 2023
31 Mar 2023
11 May 2023
29 Apr 2023
1 Apr 2023 - 8 Apr 2023
Amount
Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps,cills, sunshades, shelves, lintels, etc.and cutting chases for concealed water tubing or concealed conduit wiring, etc. and making good, cutting exceeding 20cm girth complete all as specified and directed by EIC.
Taking down existing sub main wiring of any size complete all as specified and directed.
M&L for Sub main wiring with two single core 4Sqmm stranded copper conductor PVC insulated and unsheathed cable ISI marked drawn in 25mm dia, medium grade, PVC conduit concealed in wall for sub main connection including 4Sqmm PVC insulated unsheathed copper conductor ISI marked as earth wire complete all as specified and directed by Engr-in-charge.
M&L for Sub main wiring with two single core 6Sqmm stranded copper conductor PVC insulated and unsheathed cable ISI marked drawn in 25mm dia, medium grade, PVC conduit concealed in wall for sub main connection including 6.0Sqmm PVC insulated unsheathed copper conductor ISI marked as earth wire complete all as specified and directed by Engr-in-charge.
Taking down carefully any type of battens or conduit point wiring with or without conduit (light, fan, socket or power) complete including fittings and fixtures such as switches, sockets, ceiling roses, etc removing material from site and making good disturbed surfaces of walls, ceilings etc including two coats of white / colour washing / distempering etc to match the existing surface complete all as specified and directed.
M&L for point wiring with PVC insulated and unsheathed cable 1.5 Sqmm (nominal area) ISI marked multi-stranded copper conductor single core including suitable size of PVC conduit, concealed terminal boxes not less than 1.6 mm thick of required size with top cover 2.8 mm thick of plastic laminated sheet (Hylum) of required colour complete metal flush terminal boxes with all accessories including 1.5 Sq mm PVC insulated and unsheathed stranded copper wire conductor cable to common earth and connecting to earth dolly including colour coding of cable shall be Phase - Red, Neutral- Black and Earth- Green complete all as specified and directed for:- Note: Cost of making good disturbed surface matching with existing shall be beemed included in the quoted rate.
One light/fan point controlled by one, one way switches
One bell point controlled by push button on same board with other switches.
One socket outlet point 3 pin 5 Amps on the same board.
One socket outlet point 3 pin 5 Amps on independent board.
M&L for point wiring with PVC insulated and unsheathed cable 2.5 Sqmm (nominal area) ISI marked multi-stranded copper conductor single core including suitable size of PVC conduit, concealed terminal boxes not less than 1.6 mm thick of required size with top cover 3 mm thick of plastic laminated sheet (Hylum) of required colour complete metal flush terminal boxes with all accessories including 2.5 Sqmm PVC insulated and unsheathed stranded copper wire conductor cable to common earth and connecting to earth dolly including colour coding of cable shall be Phase - Red, Neutral- Black and Earth- Green for 15 Amps socket outlet complete all as specified and directed Note: Cost of making good disturbed surface matching with existing shall be beemed included in the quoted rate.
M&L for point wiring with PVC insulated and unsheathed cable 4 Sqmm (nominal area) ISI marked multi-stranded copper conductor single core including suitable size of PVC conduit, concealed terminal boxes not less than 1.6 mm thick of required size with top cover 3 mm thick of plastic laminated sheet (Hylum) of required colour complete metal flush terminal boxes with all accessories including 4 Sq mm PVC insulated and unsheathed stranded copper wire conductor cable to common earth and connecting to earth dolly including colour coding of cable shall be Phase - Red, Neutral- Black and Earth- Green for 15 Amps AC socket outlet complete all as specified and directed Note: Cost of making good disturbed surface matching with existing shall be beemed included in the quoted rate.
S&F switch piano, flush type, 05 / 06Amps, single pole, one way, 240 volts complete all as specified & directed
S&F switch piano, flush type, 15 / 16Amps, single pole, one way, 240 volts complete all as specified & directed
Supply & fixing socket outlet 3 pin, 05 / 06 Amps, flush type, 240 volts complete all as specified & directed. Make:- Anchor/ cona/SSK
S&F for socket outlet flush type 2 in 1, 6 pin , 5 and 15 Amps complete all as specified and directed. Make:- Anchor/ cona/SSK
S&F bell push flush type switch, 5Amp complete all as specified and directed by Engr-in-charge. Make:- Anchor/ cona/SSK
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc complete all as specified and directed
M&L for point wiring with PVC insulated and unsheathed cable 1.5 Sqmm (nominal area) ISI marked multi-stranded copper conductor single core including minimum 20 mm dia medium grade PVC conduit concealed in wall / false ceiling, concealed metal flush boxes, including white cover plates with frame for fixing of modular switches/sockets etc with all accessories including 1.5 Sq mm PVC insulated and unsheathed stranded copper wire conductor cable to common earth and connecting to earth dolly including colour coding of cable shall be Phase - Red, Neutral- Black and Earth- Green complete all as specified and directed by Engr-in-charge for:- Notes: Cost of making good disturbed surfaces matching with existing shall be deemed to be included in the quoted rate.
One light/fan point/Exhaust fan controlled by one, one way switch 6 amps.
One bell point controlled by push button on the same board with other switch or independent.
One 5 pin, 5 Amp switch socket out let on the same board with other switches.
One 5 pin, 5Amp switch socket out let on the independent board.
M&L for point wiring with PVC insulated and unsheathed cable 2.5 Sqmm (Nominal area) stranded copper conductor single core including ISI marked including minimum 20 mm dia medium grade PVC conduit for point wiring, concealed in wall / metal flush boxes including white cover plates and frame for mounting switch/socket (modular) with all accessories including 2.5 Sqmm PVC insulated and unsheathed stranded copper wire conductor cable to common earth and connecting to earth dolly for one 5 pin, 15 Amps switch socket out let point on an independent board including colour coding of cable shall be Phase- Red, Neutral- Black and Earth- Green complete all as specified and directed by Engr-in-charge. Notes: Cost of making good disturbed surfaces matching with existing shall be deemed to be included in the quoted rate.
M&L for point wiring with PVC insulated and unsheathed cable 4Sqmm (Nominal area) stranded copper conductor single core including ISI marked including minimum 20mm dia medium grade PVC conduit for point wiring, concealed in wall / metal flush boxes including white cover plates and frame for mounting switch/socket (modular) with all accessories including 4Sqmm PVC insulated and unsheathed stranded copper wire conductor cable to common earth and connecting to earth dolly for one 20 Amps AC switch socket out let point on an independent board including colour coding of cable shall be Phase- Red, Neutral- Black and Earth- Green complete all as specified and directed by Engr-in-charge. Notes: Cost of making good disturbed surfaces matching with existing shall be deemed to be included in the quoted rate.
S&F modular switch flush type, 5Amps, single pole, one way 1 module complete all as specified and directed
S&F modular switch flush type, 16Amps, single pole, one way 1 module complete all as specified and directed
S&F modular socket , 5 pin, 5 Amps, multipurpose 2module complete all as specified and directed. Make : Legrend/ABB/L&T
S&F modular socket , 5 pin, 6/16 Amps, multipurpose 2module complete all as specified and directed. Make : Legrend/ABB/L&T
S&F ceiling rose, surface bakelite, size as per relevant IS, three terminals complete all as specified and directed. Make : Legrend/ABB/L&T
S&F modular fan step regulator 120W 2 module complete all as specified and directed. Make : Legrend/ABB/L&T
S&F in repair modular bell push switch complete all as specified and directed by Engr-in-charge. Make:- Legrend/ABB/L&T
S&F in repair Buzzer, Ding Dong AC 230volts complete all as specified and directed by Engr-in-charge. Make:- Legrend/ABB/L&T
S&F in repair lamp holder,insulated body, with back PVC rectangular block for fixing of holder with screw complete all as specified and directed.
M&L for wiring with (2x1.5Sqmm and 1x1.5Sqmm) (nominal area) PVC insulated unsheathed single core multistranded copper conductor cable1100 volts grade concealed in Steel conduit with all fittings and accessories including MS clamp for mounting of flame proof switches/sockets etc, including 1.5sqmm copper multi stranded conductor cable earth continuity wire connected to earth dolly complete all as specified and directed.
S&F Switch flame proof rotary type with termination box in LM6,16A ,single pole 250 V complete all as specified and directed. Make: Sudhir/ Baliga/Shyaam Switchgear
S&F flame proof switch socket & plug combined in LM6 cable termination box in LM6 ,16 A 250V ,2P+ earth complete all as specified and directed. Make: Sudhir/ Baliga/Shyaam Switchgear
Supply and fixing LED light fitting 2x16 Watt flameproof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size. Make: Sudhir/ Baliga/Shyaam Switchgear
Taking down of MCB DB with MCB 's and making good disturbed surfaces of wall complete all as specified and directed
S&F double door VTPN 4 way suitable for 4 pole MCCB as incoming & SP/TP MCB as outgoing, 200 Amps rated busbar, inter connection link, cable ties, earth bar etc complete all as specified and directed. Note:- (MCCB & MCB to be measured and paid seperately) Make : L&T/Schneider/Legrand/Hager
S&F double door MCB DB sheet enclosure single pole and neutral 240V with 100 Amp suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete confirming to IP 42/43 without MCB and with enclosure blank plates for unused way suitable for 4 way complete all as specified and directed. Make : L&T/Schneider/Legrand/Hager
S&F double door MCB DB sheet enclosure single pole and neutral 240V with 100 Amp suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete confirming to IP 42/43 without MCB and with enclosure blank plates for unused way suitable for 8 way complete all as specified and directed. Make : L&T/Schneider/Legrand/Hager
S&F double door MCB DB sheet enclosure single pole and neutral 240V with 100 Amp suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete confirming to IP 42/43 without MCB and with enclosure blank plates for unused way suitable for 12 way complete all as specified and directed. Make : L&T/Schneider/Legrand/Hager
S&F in repair single pole and neutral enclosure with 2 pin plug and socket with one MCB 20 Amp complete all as specified and directed. Make : L&T/Schneider/Legrand/Hager
S&F MCCB 100Amps, 240v, 4pole breaking capacity 16 KA complete all as specified and directed. Make : L&T/Schneider/Legrand/Hager.
S&F MCB, TP 25 To 63 Amp, 415V 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning.
S&F MCB, single pole & neutral, 240 Volts (16 to 32) Amps,10KA complete all as specified and directed. Make : L&T/ Schneider/Legrand/Hager
S&F MCB, single pole, 240 Volts (05 to 32) Amps,10Ka complete all as specified and directed . Make : L&T/Schneider/ Legrand/Hager
Taking down light fitting any description complete all as specified and directed .
Supply and fixing LED light fittings 1x 20W, 220V, worm white AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. Make :- Philips/ Wipro/ Orient/ Osram
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. Make :- Philips/ Wipro/ Orient/ Osram
Supply and fixing LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed/ Surface type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. Make :- Philips/ Wipro/ Orient/ Osram
Supply and fixing round shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete. Make :- Philips/ Wipro/ Orient/ Osram
S & F LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed.
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. Make :- Philips/ Wipro/ Orient/ Osram
Taking down fan, dismantling blades and removing fan and blades to store, complete all as specified and directed.
Hanging only ceiling fan after repair and connecting up including provision of cable from ceiling rose or connector to fan, complete all as specified and directed.
M&L Painting of ceiling fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc, complete all as specified and directed.
M&L for rewinding of following fans with same gauge of super enameled copper wire complete,varnishing ,baking , connecting properly with sleeves assembling the same including replacement of unserviceable shackle and clamps with nots /bolts/washer /split pin and blade screws etc testing,complete all as specified and directed. NOTE: (a) Spare parts like bearing,capacitor,bushes if required will be measured and paid separately. (b) The rates shall be deemed to include dismantling of fan and reassembling after repair /replacement of worn out parts
Ceiling fan 1200 /1400mm sweep
Exhaust fan 300mm sweep
Exhaust fan 450mm sweep
Wall mounted fans 400mm /450mm sweep
Supply only new metal bush bearing made out of gun metal/brass of same size suitable for ceiling fans,wall mounted fan and exhaust fans complete all as specified and directed.
Supply only ball bearing suitable Ceiling fan 1200 /1400 mm sweep, complete all as specified and directed. Make NBC/SKF/Tata
Supply only ball bearing suitable Exhaust fan 300 mm sweep, complete all as specified and directed. Make NBC/SKF/Tata
Supply and fix new wall mounted fan motor single phase 240 Volt 50Hz, complete all as specified and directed.
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM five star rated with brushless direct current motor (BLDC), complete all as specified and directed. Make:- USHA, Orient, Havells.
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers, complete all as specified and directed. Make:- USHA, Orient, Havells.
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz RPM 1200, Copper winding of sweep 300m, complete all as specified and directed. Make:- USHA, Orient, Havells.
Supply and fix electric water heater,storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate,NRV, connection piece etc, complete all as specified and directed. Make:- USHA, Orients, Havells.
Dismantling electric/water connection and taking down of storage type water heater,servicing,cleaning of inner tank etc.at site.and replacement of burnout parts etc. and refixing in situ complete all as specified and directed. Note- (a) Detection and rectification of leakage of inner tank of gyser by brazing/welding/soldring. (b) Painting of gyser included in quoted rate. (c)wornout parts shall be measured as seperatly.
Supply only Heating element (round/ triangular) of size 1.5KW complete all as specified and directed. Make :- Theeta/Racold/Bajaj
Supply only Thermostat for 25ltrs capacity geyser, complete all as specified and directed. Make :- Theeta/Racold/Bajaj
Supply only Rubber Gasket for Inner Tank 25Ltrs Capacity, complete all as specified and directed.
Supply only Air release Valve for 25Ltrs capacity, complete all as specified and directed.
Supply only Fusible lead nut for safety pressure of existing type, complete all as specified and directed.
Supply only Indicator Lamps for Geyser, complete all as specified and directed.
Supply only PVC connections 15 mm size with PTMT nuts of up to length 600mm length (for hot and cold water inlet and outlet ) complete all as specified and directed.
Attending complaint for Comprehensive maintainance and servicing of split type air conditioner cap 1.5/2.0 Ton, cleaning of cooling/condensing coil,oiling of condenser fan motor, cleaning of air filter , detection of defective parts & replacement with new parts testing smooth functioning complete at site all as specified and directed. Note :- (a) Defective parts will be measured and paid separately under supply only . (b) Job includes servicing , rectification of defects as one job
Supply only Run capacitor 45/36 MFD
Supply only PCB with cardless Remote
Supply only Condensor motor with Blade
Supply only Condenser fan blades for spilt type AC units of capacity 1.5T/2T
Supply only Indoor swing motor of capacity 1.5T/2T
Supply only wiring kit for split type AC units 1.5/2TR
Supply only Suction and discharge valve set for type split AC 1.5/2T
M & L for detection of refrigerent leakage from split type AC repair of cooling coil / condensing coil for minor leakage if any,flushing of system and gas charging in the system up to required and sealing / closing of charging valve of slpit type AC / window AC capacity 1.5 TR complete at site all as specified and directed. Note:- (i) Leak detection with Nitrogen (ii) Evacation is carried out by using a vaccum pump and a recovery bottle , once the system evacuates.
All as per srl item No. 88.00 here-in-before but split type AC / window AC capacity 2 TR, complete all as specified and directed.
M & L for rewinding of condensor fan motor of split type AC of capacity 1.5 / 2.0 TR with same gauge of copper insulated winding wire including insulating material complete all as specified and directed.
M & L for taking down unserviceable burnt Indoor blower fan motor of split AC of capacity 1.5 / 2.0 TR , repairing / rewinding the same with super enamelled copper conductor of existing gauge, replacing the set of bearing including lathe work for making bearing seat complete & installing the same & commissioning all as specified and directed.
Attending complaint for Comprehensive maintainance and servicing of water cooler cooling cap 40 litre/storage cap 80 litre cleaning of cooling/condensing coil, oiling of condenser fan motor, cleaning of drain pipe testing for smooth functioning complete all as specified and directed. Note :- (a) Defective parts will be measured and paid separately under supply only. (b) Job includes servicing , rectification of defects as one job.
Supply only Condensor fan motor with blade for water cooler 40/80 ltrs, complete all as specified and directed.
Supply only Thermostate, complete all as specified and directed.
Supply only CP self closing push cock 15mm dia, complete all as specified and directed.
Detection of refrigerent leakage from water cooler cooling cap 40liter, repair of cooling coil/condensing coil for minor leakage if any flushing of system and gas charing in the system up to required qty, and sealing / brazing/soldering all as specified & directed.
Attending complaint for Comprehensive maintainance and servicing of refrigerator / deep freezer of capacity 165 to 310litres including labour for detecting the leakage of gas ,repairing leakage and recharging refrigerant, cleaning of cooling coil, condenser, compressors, with vaccum cleaner and cleaning solution, checking servicability of electrical / electronic circuits relays, wiring kit, thermostat switches, knobs, etc. and keeping the units in satisfactory working conditions complete all as specified and as directed. Note: (a) Spares / parts / componenets/ refrigerant gas will be measured and paid separately under relevant items hereinafter and labour charges for replacement shall be deemed to be included in this unit rate quoted.
Supply only thermostat switch with knob, complete all as specified and directed.
Supply only starting relay 1/8HP to 1/6HP with OLP, complete all as specified and directed.
Supply only copper filter, single capillary, pencil type, complete all as specified and directed.
Attending complaint for Comprehensive maintainance and servicing of desert cooler,servicing of fan motor, water pump cleaning of PVC pipe testing including replacement of wood wool pad (set of three) etc for smooth functioning all as specified & directed. Note: (a) Spares / parts / componene will be measured and paid separately under relevant items hereinafter and labour charges for replacement shall be deemed to be included in this unit rate quoted.
Supply only Fan motor with blade and clamp 106 watt or nearest cap single phase, complete all as specified and directed. Make:- khaitan/CG/Vansal
Supply only water pump or desert cooler, complete all as specified and directed. Make ;- khaitan/CG/Vansal
M & L for rewinding of desert cooler motor of same gauge of copper insulated winding including material complete all as specifed and directed
M&L for preparation of surfaces of desert Cooler by scrapping old paint with sand paper, cleaning inner & outer surfaces of body and spray painting the inner surfaces and grills with two coats of black anticorrosive paint and outer surfaces with two coats of aluminium paint, over one coat of zinc chrome primer, complete all as specified and directed.
M&L for earthing with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 m below normal GL with the top edge of the plate not less then 1.5 m below the normal GL connected to GI wire 4mm dia protected by 15mm GI pipe (light grade) and watering pipe 20mm bore GI pipe (light grade) and chamber with PCC (1:4:8) type D2 using 40mm graded stone aggregate, coping with (1:3:6) type CI using 20mm graded stone aggregate and with RCC pit cover (50 mm thick) in 1:2:4 type B1 using 20mm stone aggregate, reinforced with 8mm for MS bar at 80mm c/c both way in lieu of CI pit cover with angle iron frame including excavation and earth work and removal of surplus soil of earth complete all as shown in electrical plate No 3 of SSR Part I and including charcoal dust, common salt and earth lead connected to earthing test point testing of earthing complete all as specified and directed. NOTE: (i) Main earthing lead and protection GI pipe from earth electrode to test point up to 7.5 m is to be provided and the cost for the same shall deemed to be included in the above quoted rate. earthing lead beyond 7.5 m shall be measured and paid for separately under respective item. (ii) Earthing resistance shall be maintained less than 5 Ohm.
M&L for earthing with copper earth plate electrode 600 x 600 x3.15 mm thick buried directly in ground earth pit not less than 3.75 m below normal GL with the top edge of the plate not less then 2.50 m below the normal GL connected to copper strip 20x3mm protected by 50mm GI pipe (light grade) and watering pipe 20mm bore GI pipe (light grade) and chamber with PCC (1:4:8) type D2 using 40mm graded stone aggregate, coping with (1:3:6) type CI using 20mm graded stone aggregate and with RCC pit cover (50 mm thick) in 1:2:4 type B1 using 20mm stone aggregate, reinforced with 8mm for MS bar at 80mm c/c both way in lieu of CI pit cover with angle iron frame including excavation and earth work and removal of surplus soil of earth complete all as shown in electrical plate No 3 of SSR Part I and including charcoal dust, common salt, magnesium sulphate in layer 150mm thick in all side of plate and earth lead connected to earthing test point testing of earthing complete all as specified and directed.
NOTE: (i) Main earthing lead and protection GI pipe from earth electrode to test point up to 7.5 m is to be provided and the cost for the same shall deemed to be included in the above quoted rate. earthing lead beyond 7.5 m shall be measured and paid for separately under respective item of Sch Part III Section I. (ii) Earthing resistance shall be maintained less than 2 Ohm.
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr deep in soft/loose soil for Erection of pole/laying cables etc., and getting out complete including forming bottom surfaces to required levels/slopes etc complete all as specified and as directed
Excavation in trenches for foundation n.exc 1.5 metre wide and depth exc. 1.5 metre but n. exc 3m and not exc. 10sqm on plan and getting out in soft/loose soil for laying cable of defferent size and errection of pole and assay etc complete all as specified and directed.
Returning, filling-in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed.
Removing excavated material(soils) n.exc 50m and depositing where directed at a level n.exceeding 1.5m above the starting point complete all as specified and directed.
Supply and lay double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall conforming to ISI 14930 ( Part I and II) for protection of underground cables of size 90 mm outer dia with all fittings. laid in trenches / road/ nallah or fixed along walls poles or laid under floor (including cutting floor/Road and making good to match with existing adjoining surface etc for cable protection all as specified (excavation and earth work shall be measured and paid separately). Make: Rex/Poly/Gemini
Supply and lay double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall conforming to ISI 14930 ( Part I and II) for protection of underground cables of size 120 mm outer dia with all fittings. laid in trenches / road/ nallah or fixed along walls poles or laid under floor (including cutting floor/Road and making good to match with existing adjoining surface etc for cable protection all as specified (excavation and earth work shall be measured and paid separately). Make: Rex/Poly/Gemini
M&L for boring/auguring suitable hole & insertion of 80mm dia GI pipe including supply and inserting pipe not less than 600mm below existing PCC/road/hard standing complete all as specified and directed. Notes:- Cost of equipment, tools & plants & material required for boring shall be deemed to be included in the rates quoted
M & L for PCC,1:4:8 type D-2 (using 40 mm graded aggregate) as in foundation, base of pole and in embedding blocks for stays complete all as specified and directed.
M&L for PCC,1:3:6 type C2 (using 40mm graded stone aggregates) as in coping/collar of electric poles including use of necessary form work and concrete finished even and smooth without using extra cement complete all as specified and directed.
M&L for PCC, (1:2:4) type B-1, (using 20 mm graded stone aggregates) as in coping etc including necessary form work complete all as specified and directed.
M&L for crimping type heavy duty copper lugs/ferrule suitable for cable of cross sectional area16/25Sqmm complete all as specified and directed.
M&L for crimping type heavy duty copper lugs/ferrule suitable for cable of cross sectional area 50/70Sqmm complete all as specified and directed.
M&L for crimping type heavy duty copper lugs/ferrule suitable for cable of cross sectional area95/120Sqmm complete all as specified and directed.
S&F of LT End termination heat shrinkable End joints of size 70 to 120sqmm 3.5 core complete all as specified and directed
S&F of LT End termination heat shrinkable End joints of size 16 to 50sqmm 3.5 core complete all as specified and directed
S&F of LT heat shrinkable straight through joints of size 70 to 120sqmm 3.5 core complete all as specified and directed
S&F of LT heat shrinkable straight through joints of size 16 to 50sqmm 3.5 core complete all as specified and directed
Taking UP/down the existing cables any description from trenches /poles/ walls etc complete all as specified and directed. Note :- Earth work shall be measured and paid separetly
Supply, laying, jointing and testing XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 4.0 core X 25Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed. Make : Havells, KEI, RR cables, Gloster
Supply, laying, jointing and testing XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5 core X 50Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed. Make : Havells, KEI, RR cables, Gloster
Supply, laying, jointing and testing XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5 core X 95Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed. Make : Havells, KEI, RR cables, Gloster
Supply and fixed as in repair MCCBs 415V,16KA, 4 Pole 63Amp with Adjustable thermal magnetic release as specified as directed. Make:- L&T, Seimens,Schneider.
Supply and fixed as in repair MCCBs 415V,16KA, 4 Pole 100Amp with Adjustable thermal magnetic release as specified as directed. Make:- L&T, Seimens,Schneider.
Supply and fixed as in repair MCCBs 415V,16KA, 4 Pole 125Amp with Adjustable thermal magnetic release as specified as directed. Make:- L&T, Seimens,Schneider.
S&F in repairs MCB TPN, 415V, 63A, 10kA complete all as specified and as directed Make:- L&T, Seimens,Schneider.
Supply and fix as in repair Voltmeter Digital type suitable for 50-520 VAC(P-P), flush mounting 96x96mm class 0.5 complete all as specified and directed.
Supply and fix as in repair Amp meter, Digital type suitable for 0-200Amps flush mounting 96x96mm class 0.5 complete all as specified and directed.
Comprehensive maintenance & servicing /cleaning of Automatic power factor panel,replacement of worn out part detection of faulty component /wiring & testing complete all as specified and directed . Notes: (i) Spare parts shall be measured and paid separately as supply only. (ii) Contractor will arrange skilled electrician for repair servicing of APFC panel. (iii) Minor parts if required for functioning of APFC panel deemed to be included in unit rate.
S&F in repairs power capacitor for APFC panel, power quality,heavy duty 25kVAR, 440V, 50Hz, double dielectric capacitor, with rated current 32.8A, required phase discharge device with resistance appropriate insulation level and rated current including suitable sized copper conductor cable, thimbles and testing on fixing and connecting up complete all as specified and as directed. Make : Legrand /L&T /ABB
Comprehensive maintainance of oil cooled servo voltage stablizer 3x50 KVA 3 Phase by isolating ,disconnecting of input/output ,supply cable,opening of top of voltage stablizer,detecting of fault ,U/S component in control panel /dimmerstat /PCB etc,cleaning of serviceable parts/ component ,including replacement of worn out spare parts etc, if required complete all as specified and directed. Location : AF Net Bldg Note: (i) Cost of replacement of worn out cable for wiring deemed to be included in quoted rates: (ii) Centrifuging of transformer oil deemed to be included in quoted rate. (iii) Minor parts if required for completion of work deemed to be included in unit rate.
Material and labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engr-in-charge.
Dismantling pre stressed cement concrete poles 9 mtr long complete all as specified and directed.
Supply, erecting and fixing, in true vertical position/as strut, Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type type 410 SP-31 (9.00 metres long) complete with painting on exterior portion of pole with two coats of synthetic enamel paint over a coat of primer complete including taking out of existing unserviceable pole all as specified and directed.
Material and Labour for painting of PCC/steel poles 9/11m long alongwith road/ perimetre upto 1.5 m height from pedestal, with two coats of synthetic enamel paint in 30 cm height 5 block of each airforce pattern incl painting of pole, coping with black paint and writing pole numbers with white paint on black circular base incl. marking of HT/LT with Painting of pole cross arms bracket with two coats of aluminum paint over a coat of red oxide primer complete all as specified all as directed by EIC .
Material and Labour for painting of LT panels of any size and capacity, with two coats of synthetic enamel paint with two coats of aluminum paint over a coat of red oxide primer complete all as specified all as directed by EIC .
Earthing complete with galvanized steel earth plate electrodes 600x600x6mm thick buried directly in ground earth (earth pit not less 2.25 m deep below ground level) with top edge of the plate not less then 1.5 mtr below normal ground level connected to galvanised iron earthing strip 32mm x6mm thick by means of bolt nuts check nuts and washers of galvanized iron or steel all as specified & shown in electrical plate No.3 of MES SSR part-I 2009 connected to earth test point as specified and testing on completion including provision of 50 mm dia light grade pipe up to 7.5 mtr length as protection & watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of soil incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal , salt, funnel, complte all as specified and directed at site. Notes: (i) Earthing resistance shall be maintained less than 5 Ohm.
M&L for earthing with copper earth plate electrode 600 x 600 x3.15 mm thick buried directly in ground earth pit not less than 3.75 m below normal GL with the top edge of the plate not less then 2.50 m below the normal GL connected to copper strip 20x3mm protected by 50mm GI pipe (light grade) and watering pipe 20mm bore GI pipe (light grade) and chamber with PCC (1:4:8) type D2 using 40mm graded stone aggregate, coping with (1:3:6) type CI using 20mm graded stone aggregate and with RCC pit cover (50 mm thick) in 1:2:4 type B1 using 20mm stone aggregate, reinforced with 8mm for MS bar at 80mm c/c both way in lieu of CI pit cover with angle iron frame including excavation and earth work and removal of surplus soil of earth complete all as shown in electrical plate No 3 of SSR Part I and including charcoal dust, common salt, magnesium sulphate in layer 150mm thick in all side of plate and earth lead connected to earthing test point testing of earthing complete all as specified and directed. NOTE: (i) Main earthing lead and protection GI pipe from earth electrode to test point up to 7.5 m is to be provided and the cost for the same shall deemed to be included in the above quoted rate. earthing lead beyond 7.5 m shall be measured and paid for separately under respective item of Sch Part III Section I (ii) Earthing resistance shall be maintained less than 2 Ohm.
Material and labour for copper earthing strip 20mm x3mm laid in trenches / fixed on wall for inter connecting /extension in earthing including excavation and earth work complete all as specified and directed.
Taking up/down steel tubing GI pipelines/connection from trenches incl connected fittings/accessories and cleaning for refixing or removal to store for 15mm bore complete all as specified and directed
Taking up/down steel tubing GI pipelines/connection from trenches incl connected fittings/accessories and cleaning for refixing or removal to store for 20mm bore complete all as specified and directed
Taking up/down steel tubing GI pipelines/connection from trenches incl connected fittings/accessories and cleaning for refixing or removal to store for 25mm bore complete all as specified and directed
Taking up/down steel tubing GI pipelines/connection from trenches incl connected fittings/accessories and cleaning for refixing or removal to store for 40mm or 50mm bore complete as specified and directed.
Supply and laying in trenches steel water tubing galvanised 15mm bore medium grade ISI marked with all fittings complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches steel water tubing galvanised 20mm bore medium grade ISI marked with all fittings complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches steel water tubing galvanised 25mm bore medium grade ISI marked with all fittings complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches steel water tubing galvanised 40mm bore medium grade ISI marked with all fittings complete all as specified and directed by Engineer-in-Charge.
Supply and laying in trenches steel water tubing galvanised 50mm bore medium grade ISI marked with all fittings complete all as specified and directed by Engineer-in-Charge.
Supply, fixing and testing Gun metal Gate valve 50mm dia screwed body ends and cast iron hand wheel conforming to IS :778 –1984 and ISI marked complete all as specified and directed.
Supply, fixing and testing Gun metal Gate valve 40mm dia screwed body ends and cast iron hand wheel conforming to IS :778 –1984 and ISI marked complete all as specified and directed.
Supply, fixing and testing Gun metal Gate valve 25mm dia screwed body ends and cast iron hand wheel conforming to IS :778 –1984 and ISI marked complete all as specified and directed.
Supply, fixing and testing Gun metal Gate valve 20mm dia screwed body ends and cast iron hand wheel conforming to IS :778 –1984 and ISI marked complete all as specified and directed.
Supply, fixing and testing Gun metal Gate valve 15mm dia screwed body ends and cast iron hand wheel conforming to IS :778 –1984 and ISI marked complete all as specified and directed.
Supply, fixing, testing and commissioning Double flanged non-rising stem type cast iron sluice valve suitable for 150 mm dia bore pipe with hand wheel and suitable for pressure rating of PN :1.6 duly drilled holes for fixing of nuts and bolts, stem made of high tensile brass ISI marked and conforming to IS : including rubber gasket, nuts, bolts and washers complete all as specified and directed.
Supply, fixing, testing and commissioning Double flanged non-rising stem type cast iron sluice valve suitable for 100 mm dia bore pipe with hand wheel and suitable for pressure rating of PN :1.6 duly drilled holes for fixing of nuts and bolts, stem made of high tensile brass ISI marked and conforming to IS : including rubber gasket, nuts, bolts and washers complete all as specified and directed.
Supply, fixing, testing and commissioning Double flanged non-rising stem type cast iron sluice valve suitable for 80 mm dia bore pipe with hand wheel and suitable for pressure rating of PN :1.6 duly drilled holes for fixing of nuts and bolts, stem made of high tensile brass ISI marked and conforming to IS : including rubber gasket, nuts, bolts and washers complete all as specified and directed.
S& F as in repair for CI/DI any size spigot socketed pipe bends only (any type radius and angle), tappers any type (Straight, bend, increasing, decreasing or double socket etc), Tee pieces single branch double branch, cross (all sockets or socket and spigot ) collars, caps and plugs up to 150 mm capacity.
Material & labour for cutting cast iron 200/150/100mm bore pipe in position for insertion of new Tees, branches and reducing to required length complete all as specified and directed. ( both sides cut shall be measured as one unit)
Material and labour run lead joints of spigot and socket pipes and fittings for DI/CI pipe 150 mm bore size of pipe including provision of bolts, washers and white lead or mineral oil complete all as specified. Note;- Earth work will be measured and paid separately.
Material and labour run lead joints of spigot and socket pipes and fittings for DI/CI pipe 100 mm bore size of pipe including provision of bolts, washers and white lead or mineral oil complete all as specified. Note;- Earth work will be measured and paid separately.
Supply only calcium based white to off white free flowing solid granuals chemicals having chlorine content of minimum 60% for chlorination in 45kg packing Make : Jal Aqua International/ M/s Dodhiya chemi Tex pvt limited or Approved make by E-in-C branch
Supply and fix Single tank type electronic chemical dosing system consist of dozing pump 230V Ac 50HZ capacity upto 10LPH at rate of 5KG/Sqcm pressure , pump head PP with Glass filled, Teflon Diaphram.with suction and discharge tubing 3mtr along with PVC injector with NRV, FRP tank 150Ltr comprising agitator 0.25hp three phase motor 990RPM with SS sweep blade complete. Note : Old unserviceable item deposited to MES Store yard Make: Toschon Jesco or M/s Satya sai
Supply and lifting of column pipe, flanged 100mm/80mm bore with submersible cable from bore hole of tube well, pump set of any capacity and lowering after repair in borewell complete all as specified and directed by Engr-in-Charge. Note: (i) Lifting & lowering of pump set upto 120 mtrs deep will be deemed to be included in unit rate. (ii) Lifting & lowering of pump set to be completed out within 24 hrs from intimation. (iv) Rubber gasket, nuts & bolts for replacement deemed to be included in unit rate.
Opening of submersible motor for rewinding with PVC coated copper winding wire as per existing gauge insulation material after stripping of existing worn out winding, M&L for sealing kit, O- ring, Gasket, water drain plug, sand guard, cable packing ring, cable gland ring, upper/lower bearing, adopter piece, motor key, upper lower flange, neck ring, suction case, Hex bolt, Circlip washer, Motor coupling, thurst plate,motor bush etc complete, reassembling with pump set of the capacity 30 Hp or nearest size, complete all as specified and directed by Engineer-in-charge.
M&L for Repair/Overhauling of submersible pump set including replacement of Hex bolt, Circlip washer, bowl stud, pump shaft, rotor bleach, pump bush etc complete and reassembling pump set of capacity upto 30 HP or nearest size, complete all as specified and directed Note : Impeller shall be measured and paid seperately however labour rates inclusive shall deemed to be in quoted rate.
M&L for rewinding of Induction motor 5HP with Copper winding wire as per exisiting size and type incl all type packing/gaskit/nutbolt along with all insulation material & motor winding provided with thermal switches for protection against excesive temperature rise complete all as specified and as directed.
Supply only galvanized iron column pipe 100mm medium grade (approximately 3mtr length) each duly flanged at both ends by welding with slots for housing two Nos submersible cable and holes for fixing nut bolts complete all as specified and directed. Make : TATA/Jindal/ Surya prakash
M&L for Cleaning, Desludging/ dewatering of valve pit chamber, Bailing out the leakage water and fill the gland packing & rubber packing in sluice valve etc complete all as specified and directed by Engineer-in-Charge.
Potable water chemical analysis testing of water to be conducted by laboratories authosied by NABL, PPCB & CPCB. The test will analys pH,colour, Odour, Taste, Turbidity, total Hardness, Total Alkalinity, Iron, chloride, Residual Free Chlorine, Fluroide, Total Dissolved Solid, Sulphate, Nitrate, Total Coliform, E.coli etc including collecting of water from the source in a spacilised glass bottel used for this purpose, and collecting the reports from the Lab, complete all as specified and directed
Cleaning of SWT of 50000 Gln water throughly by removing mud grits etc complete all specified and directed. Notes : rates quoted shall deemed to be included for following :- (i) Cleaning inner surfaces of capacity tanks complete with scraping with steel wire bruses, pressure wash, removing mud, sludge collected inside the tank manualy, removal of mud to a distance not exceeding 50mtrs. (ii) Washing with clean water and bleaching powder or with high strength calcium chloride mixture thoroughly internally removing left out sludge if any to a distance not exceeding 50 mtrs including writing capacity of SWT, cleaning date, due date for cleaning with black synthetic enamel paint with existing pattern.
Cleaning of OHT of capacity 75000 Gln water throughly by removing mud grits etc complete all specified and directed. Notes : rates quoted shall deemed to be included for following :- (i) Cleaning inner surfaces of tanks complete with scraping with steel wire brushes, pressure wash, removing mud, sludge collected inside the tank manualy, removal of mud to a distance not exceeding 50mtrs. (ii) Washing with clean water and bleaching powder or with high strength calcium chloride mixture thoroughly internally removing left out sludge if any to a distance not exceeding 50 mtrs including writing capacity of OHT, cleaning date, due date for cleaning with black synthetic enamel paint with existing pattern. (iii) Apply two coats of duraguard (cement based polymer/acrylic modified highly flexible waterproof coating) from inside after surface preparations.
Periodical, preventive and comprehensive maintenance of DG set of Capacity 10 to 15 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect, inspection/testing of engine and alternator for smooth functioning of the DG set and including the replacement of following :- (i) Fuel/ lub filter one set (ii) Coolent in radiator (iii) Testing of engine control panel (iv) Cleaning of radiator, minor repair of leakages to be rectified. (v) Hose pipe set (vi) Fuel pipe/lubricant pipe (vii) Engine oil. Make of DG set: Kirloskar/Cummins Note: (i) The rates shall be deemed to be inclusive of one visit per quarter & breakdown complaints and repairs. (ii) Worn out parts repair/replacement if any other than above shall be measured and paid seprately.
Periodical, preventive and comprehensive maintenance of DG set of Capacity 40 to 63 by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect, inspection/testing of engine and alternator for smooth functioning of the DG set and including the replacement of following :- (i) service kit for elements of fuel/air/lub filter one set (ii) top up of coolent in radiator (iii) Testing of engine control panel (iv) Cleaning of radiator, minor repair of leakages to be rectified. (v) hose pipe set (vi) fuel pipe/lubricant pipe (vii) Engine oil. Make of DG set: Kirloskar/Cummins Note: (i) The rates shall be deemed to be inclusive of one visit per quarter & breakdown complaints and repairs. (ii) Worn out parts repair/replacement if any other than above shall be measured and paid seprately.
Periodical, preventive and comprehensive maintenance of DG set of Capacity 100 by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect, inspection/testing of engine and alternator for smooth functioning of the DG set and including the replacement of following :- (i) service kit for elements of fuel/air/lub filter one set (ii) top up of coolent in radiator (iii) Testing of engine control panel (iv) Cleaning of radiator, minor repair of leakages to be rectified. (v) hose pipe set (vi) fuel pipe/lubricant pipe (vii) Engine oil. Make of DG set: Kirloskar/Cummins Note: (i) The rates shall be deemed to be inclusive of one visit per quarter & breakdown complaints and repairs. (ii) Worn out parts repair/replacement if any other than above shall be measured and paid seprately.
Supply only following spare parts of DG set of kirloskar/Cummins DG set all as specified and directed.
V belt
Battery Terminal
Battery 90AH, maintenance free Genplus 12volts complete all as specified and directed.
Taking down old unservicable any type street lights and refixing after repair of street light /security lights including cleaning of perplex cover where ever required and tightening of loose connection on the pole, Complete all as specified and directed.
Supply and Fixing of PVC 3 core Cord Flexible copper insulated cable 1.5Sqmm/core in size Black/Grey colour omplete all as specified and as directed.
Taking down the unserviceable bracket and marerial & labour for new bracket made out of 40mm GI tubing light grade 1.5m lay bent to shape suitable for fixing of any type street light fitting fixed to steel/concrete pole with two MS clamps made out of 50 x 6 flat iron, 16mm dia bolts nuts and washers of suitable length all as specified and directed.
M & L for FRP looping box with hinged cover weather proof with locking arrangement and appropriate size of aluminium bus bar of capacity 100 amps for single phase 230 V, 50 Hz electric supply mounted on PVC insulaters and fixed to pole by means of MS clamps, nuts bolts and washers including cables connection including one MCB SP 6 amps including taking down existing looping box complete all as directed.
Supplying and fixing 1100 volts grade heavy duty two single core cables PVC insulated stranded aluminium conductor of size 6 sqmm served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including4mm suspension wire, one twin core cable flat or circular and including taking down old unserviceable wire dispose from site complete all as specified and directed.
Supply and fixing LED street light fitting 60 Watt 230 V AC worm white outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection and including taking down old unserviceable wire dispose from site complete all as specified and directed. Make : Wipro/Philips/Osram
Supply and fixing LED street light fitting 90 Watt 230 V AC worm white outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection and including taking down old unserviceable wire dispose from site complete all as specified and directed. Make : Wipro/Philips/Osram
Supply and fixing LED flood light 210 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp and including taking down old unserviceable wire dispose from site complete all as specified and directed. Make : Wipro/Philips/Osram
Supply and fixing three phase timer switch with nature switch -02 EC infra rays sensor with pre-drawn switching off timer, MCB power contractor, glass wool panel of maximum load capacity of 5 KWs, 415 volts, 50 Hz, degree of protection conforms to IP-66 complete all as specified and as directed. Make: Kakatiya energy system/ Bajaj/ Havells
Removing/taking out non clog type submersible sewage pumping set capacity 3 to 5 HP from sewage well after dewatering of sewage water and Rewinding of motor 3 to5HP of Non clog type submersible pumping set with suitable size of copper winding wire incl all insulation material & motor winding with pump dismantling the same for assessing & carrying out the repair/service as involved in subsequent items making good in running condition by repair/replacement of all unserviceable spare parts etc re-assembling, lowering the same into the well and making necessary connections, testing complete all as directed.
SAI ENGINEERING CO
M/s badrinath Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .