| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.3 LAccepted-AOC 17 1 ABHOY HALDER LANE KOLKATA | KOLKATA | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹3.3 L+₹4,095.78 (1.26%)Rejected-Finance 6 KRIPANATH DUTTA ROAD KOLKATA 700 002 | KOLKATA | KOLKATA | WEST BENGAL | 700002 | L2 | Rejected-Finance GREATER THAN L1 | |
| 3 | L2₹3.3 L+₹4,095.78 (1.26%)Rejected-Finance 138 CANNING STREET GROUND FLOOR KOLKATA | KOLKATA | WEST BENGAL | L2 | Rejected-Finance GREATER THAN L1 | |
| 4 | L3₹3.3 L+₹5,699.40 (1.75%)Rejected-Finance 01 BALIA BALIA SAGARDIGHI MURSHIDABAD WEST BENGAL 742237 | MURSHIDABAD | WEST BENGAL | 742237 | L3 | Rejected-Finance GREATER THAN L1 |
Tender Value
₹3.3 L
EMD Value
₹6,604
Closing Date
14 Oct 2022, 2:00 pmClosed
EE, NMD ,PHE Dte,
OFFICE OF THE EXECUTIVE ENGINEER ,NORTHERN MECHANICAL DIVISION ,PHE Dte,SUKANTA SARANI, PARESH NAGAR, SILIGURI, PIN 734001
Restoration of power for 33 KV Indoor type VCB after repairing, replacement and servicing of some accessories at Intake Pumping Station under Darjeeling W/S Pumping Scheme.
2022_PHED_406781_1
WBPHED/EE/NMD/NIeT- 17 OF 2022-2023
Open Tender
Miscellaneous Works
Item Rate
20 days
Darjeeling
Please refer tender documents
4 documents required · 4 mandatory
₹6,604
Yes
11 Nov 2022
16 Sept 2022
17 Oct 2022
19 Sept 2022
14 Oct 2022
19 Sept 2022
Amount
Inspection of 33KV VCB Panel at Site by technical person after dismantling of side, front panel & opening of bus bars, Vacuum Interrupters resin phase barring, fixed & moving contacts, Drive Insulator etc. (WBSEDCL & PHE Dte. VCB Panel)
Dismantling of busbar, vacuum Interrupters, moving & fixed contacts, charging lever, tripping lever, locking drum, mechanism springs, trip prop, racking arm, secondary plug flap coil assembly release roller, tripping plunger, operating spring etc part by part for proper assessment of fault.
Cleaning of operating Mechanism of VCB / associated equipment as required (tripping lever, charging lever, Inter lock lever, locking drum, mechanism springs, setting screw, stop pin, trip prop, set screw, spindle, lock nut, Trip roller, racking arm, secondary plug flap, coil assembly, release roller, ratchet, coil pot, main toggle, Tripping plunger, operating spring, trip coil etc.
Supply of following materials at Site:-
Spray paint for Quick drying, excellent adhesion high coverage rust resistant formulation. RAL 7032
Electrical Insulating Sealer Red 1602 - R
CRC - 226.(500 ml.) of approved make.
Three core HT Heat shrinkable termination kit 33KV Indoor type. (for 185 sq.mm. 3 core 33KV grade cable).
Three core HT Heat shrinkable termination kit 33KV Indoor type. (for 300 sq.mm. 3 core 33KV grade cable).
Three core HT Heat shrinkable termination kit 11KV Indoor type. (for 185 sq.mm. 3 core 11KV grade cable). [ for Sindhap]
Three core HT Heat shrinkable termination kit 11KV Indoor type. (for 240 sq.mm. 3 core 11KV grade cable). [ for Sindhap]
Fitting, fixing of all above supplied materials of sl no. 5.00 by dismantling the damaged / burnout parts as per direction of EIC.
Testing of 2 Panel VCB and all relays of VCB, Charging circuit along with control circuit up to the entire satisfaction of EIC.
Making all arrangement for making 33KV VCB Panel totally moisture free by providing with 8 nos. 1000w halogen lamp, hot blower & necessary allied items to make the panel complete ok including painting primer inside the panel.
Add GST @18% (CGST@9% + SGST@9%)
WEST BENGAL ENGINEERING CO.
B T PROJECTS PRIVATE LIMITED
DAS ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .