Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹11.3 L
EMD Value
₹12,000
Closing Date
23 Oct 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Executive Engineer R and B Division, Palanpur
Fire Fighting Work at Adarsh Nivasi School At Danta Ta Danta Dist : Banaskantha (Pro. Fire Fighting System for Hostel and Misc Work)
354375
14 of 2026-27
Open
Civil - All
Works
Banaskantha
13 documents required · 13 mandatory
₹900
Executive Engineer Roads and Buildings Division Palanpur
₹12,000
10 Oct 2026
10 Oct 2026
10 Oct 2026
23 Oct 2026
10 Oct 2026
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
1 Supply, Installation, Testing & 25.00 1717.61 Rmt
Commissioning of MS pipe (IS:1239) class C
including cutting, screwing, welding
necessary fittings i.e. bends, elbows
reducers, clamps, hangers, supports,
flanges,dead flange all G.I nut bolt as
required etc. of approved make and
complete in all respects. as per instruction of
engineer in charge. 100 mm dia
(MAKE : Zindal/Tata/ ASIAN)
2 Supply, Installation, Testing & 2.00 1212.10 Rmt
Commissioning of MS pipe (IS:1239) class C
including cutting, screwing, welding
necessary fittings i.e. bends, elbows
reducers, clamps, hangers, supports,
flanges,dead flange all G.I nut bolt as
required etc. of approved make and
complete in all respects. as per instruction of
engineer in charge. 80 mm dia
MAKE : Zindal/Tata/ ASIAN)
3 Supply, Installation, Testing & 2.00 944.35 Rmt
Commissioning of MS pipe (IS:1239) class C
including cutting, screwing, welding
necessary fittings i.e. bends, elbows
reducers, clamps, hangers, supports,
flanges,dead flange all G.I nut bolt as
required etc. of approved make and
complete in all respects. as per instruction of
engineer in charge. 50 mm dia
MAKE : Zindal/Tata)
4 Supply, Installation, Testing & 2.00 555.50 Rmt
Commissioning of MS pipe (IS:1239) class C
including cutting, screwing, welding
necessary fittings i.e. bends, elbows
reducers, clamps, hangers, supports,
flanges,dead flange all G.I nut bolt as
required etc. including cutting holes in brick
or RCC walls/slabs and making good the
same complete including painting with one
coat of primer and two or more coats of
synthetic enamel paint of approved make
and shade complete in all respects.25 mm
MAKE : Zindal/Tata/ ASIAN)
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
5 Providing and erecting BUTTERFLY VALVE 2.00 5262.10 Nos
(MANUAL) with C I body SS disc nitrile sheet
& O - ring & PN 16 pressure rating as
specified.
(D) 100mm dia. chapter 8 )
MAKE : KARTAR/SANT/ZOLOTO
6 Providing and erecting BUTTERFLY VALVE 2.00 3259.27 Nos
(MANUAL) with C I body SS disc nitrile sheet
& O - ring & PN 16 pressure rating as
specified.
(G) 50mm dia. chapter 8 )
MAKE : KARTAR/SANT/ZOLOTO
7 Providing and erecting NON - RETURN 1.00 5859.01 Nos
VALVE with dual plate of C I body SS
plates vulcanized NBR seal flanged end
& PN 16 pressure rating as specified.
(D) 100mm dia. chapter 8 )
MAKE : KARTAR/SANT/ZOLOTO
8 Supply, Installation, Testing & 4.00 5555.00 Nos
Commissioning of: stainless steel ISI marked
oblique pattern hydrant landing valve with
mm dia flanged inlet and 63 mm dia
instantaneous type female outlet complete
with cap ABS and G.I. chain,twist release
type plug and all accessories as per 13:5290-
1983 (Type 'A') with g.i. nut bolt.
MAKE : NEWAGE / PROTECTO / AAAG
9 Supply, Installation, Testing & 1.00 7125.55 Nos
Commissioning of Stainless steel Fire
Brigade connection (Suction collecting head)
consisting of 4 nos. 63 mm dia
instantaneous type male coupling with built-
in check valves and 150 mm dia.flanged
outlet complete with bolts, nuts and rubber
insertions as required as per IS:904-1983
with butter fly valve and Non-Return Valve.
MAKE : NEWAGE / PROTECTO / AAAG
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
10 Supply, Installation, Testing & 8.00 5706.50 Nos
Commissioning of Non-percolating flexible
hose (RRL type- 'A') ISI marked (IS:636)
mm dia x 15 M long complete with
instantaneous type Stainless steel 63 mm
dia. IS marked Male and female couplings
(IS:903) bound and rivetted to hose pipe with
copper rivets and 1.5 mm copper wire. For
internal hydrant with Fixing support
MAKE : NEWAGE / PROTECTO / AAAG
11 Supply,Installation, Testing & Commissioning 4.00 3181.50 Nos
of stainless steel 63mm dia short size branch
pipes with 20 mm dia nozzles with 63mm
instantaneous coupling ISI marked (IS:903)
MAKE : NEWAGE / PROTECTO / AAAG
12 Supply,Installation, Testing & Commissioning 4.00 7878.00 Nos
of First-Aid Fire Hose Reel wall mounting
swinging type complete with drum,bracket,
25 mm dia. Ball valve and 20 mm dia.x
M long high pressure Hose Reel tubing as
per IS:444 with stainless steel shut-off
nozzle having 5mm dia.orifice. The
Hose Reel shall strictly confirm to IS;884-
1985 with piping.
MAKE : NEWAGE / PROTECTO / AAAG
13 Supply, Installation, testing and 4.00 3484.50 Nos
commissioning of Weather proof standard
M.S. Fire hose cabinet (400 mmx 400 mmx
200 mm) floor mounted for Yard hydrants
with Single opening doors with 4 mm thick
glass including necessary locking
arrangement and powder coated paint of
P.O. Red and marked on the front as " FIRE
MAKE : NEWAGE / PROTECTO / AAAG
14 Supply, installation, testing & commissioning 1.00 3585.50 Nos
of air vent valves (PN10) of following sizes
along with ball valve. (25 mm)
MAKE:SANT /KARTAR /ZOLOTO
15 Supply, installation, testing and 1.00 2020.00 Nos
commissioning of SS Ball Valve. a) 25mm
dia MAKE : SANT / KARTAR / ZOLOTO
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
16 Supply, fabication and installation of MS 100.00 196.95 Kg.
support as per required for support of pipe
and Other Accessories.
17 Applying priming coat over new steel and 200.00 34.68 Sqm.
other metel surface after and including
preparing the surface bythroughly cleaning,
oil,grease, dirt and other foreign matter and
scoured with brushes fine steel wood,
scrapers and sand paper with ready mixed
priming paint brushing red lead.
18 Painting two coats (excluding priming coat) 200.00 87.81 Sqm.
on new steel and other metal surface with
enamel paint, brushing,interior to give an
even shade including cleaning the surface an
even shade including cleanicn the surface of
all dirt, dust and other foreign matter.
19 Supplying and fixing 3 Layer Anti bacteria 10000.00 8.59 Ltr.
UPVC water Tank (Brand Astal, Syntex or
equivalent) with all labour charges etc
complete as directed by Engineer in charge.
20 Supplying, fixing, testing and commissioning 1.00 176750.00 Set
of electrically driven main Fire Pump a,
suitable for automatic operation consisting
of the following: 'Horizontally mounted, end
suction type centrifugal fire pump having
C.I. body, bronze impeller and S.S. Shaft
with Gland packing, capable for deliverying
900 LPM at 35 Mtrs with all accessories
such as standard coupling guard, relief valve
etc., End suction back pull out type pump.
Depth of suction of pump from pump bottom
MAKE : LUB I /KIRLOSKAR / WILO/PE
21 Supplying, installing ,testing and 1.00 95950.00 Set
commissioning of precharged air (pressure)
vessel (size 400 mm dia & 1200 mm height
having thickness of minimum 8 mm) for
pressurization of hydrant / sprinkler system
complete with adequate pressure switches
(as per design / requirement) with valves to
operate as per operating sequences
including 25 mm dia drain valve, air
release valve with stop cock on the top,
mm dia inlet with isolating valve duly painted
from inside and outside complete as
required. Shall be installed at the - Plant
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
22 Providing and erecting Y - STRAINER of 1.00 18476.94 Nos
Ductile CI Body flanged ends with stainless
steel strainer for chilled / hot water circulation
including insulation as specified.
(B) 150mm dia.
MAKE : KARTAR/SANT/ZOLOTO
23 Supplying, installing ,testing and 1.00 3550.15 Set
commissioning of Pressure switches of
suitable range for pump sets with Ball valves,
Fittings like unions / colors / reducers etc.
MAKE:DANFOSS/ANCHOR
24 Providing and fixing in position the 2.00 1276.64 Nos
industrial type pressure gauges with gun
metal / brass valves complete as required.
25 Supplying & erecting D.C.P. type fire 6.00 1712.96 Nos
extinguisher for following capacity cartridge
type with gun metal cap 150 gram CO2 gas
cartridge, powder and brackets confirming to
IS 2171 1985 and complete erected with
necessary clamps made from 50 x 6 mm M
S Flat with nuts and bolts grouted in wall
26 Supplying & erecting carbon dioxide (CO2) 6.00 6591.26 Nos
fire extinguisher user of following capacity
with necessary clamps made from 50 x
mm M.S. Flat with nut & bolts grouted in wall
complete. [A] For 4.5 Kg Capacity
27 Supply and installation of auto glow reflective 6.00 4094.54 Nos
film stainless steel body signages for building
at placed required bycode and competent
authority "CO2 extingushier" size of plate
shall be :8"x16". MAKE: KANEX / SAFEX /
FIRE STONE
28 Supply and installation of auto glow reflective 6.00 1599.84 Nos
film stainless steel body signages for building
at placed required bycode and competent
authority "ABC extingushier" size of plate
shall be : 8"x16". MAKE: KANEX / SAFEX /
FIRE STONE
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
29 Supply and installation of auto glow reflective 6.00 3599.64 Nos
3 MM FOAM SHEETsignages for building at
placed required bycode and competent
authority "Fire Exit" size of plate shall be :
30 Supply and installation of auto glow reflective 6.00 4099.59 Nos
3 MM FOAM SHEET signages for building
at placed required bycode and competent
authority "Arrow Signages" size of plate shall
31 Supply and installation of auto glow reflective 1.00 3599.64 Nos
3 MM FOAM SHEETsignages for building at
placed required bycode and competent
authority "Exit plan" for each building - with
proper frame.
32 Supply and installation of auto glow reflective 1.00 3599.64 Nos
film signages for building at placed required
bycode and competent authority "Assemply
points" size of shall be : 3' x 2' .
33 Obtaining fire NOC From Chief Fire officer 1600.00 18.18 Sq.mt.
with required Details, Layouts and Testing as
required and submitting to concern
Department incl. all charges
34 Design, supply, installation, tesing and 1.00 126250.00 Set
comissioning of Fire pump cotrol panel
Panel(IP54) having consturction of 16 G MS
box for the main pumps (Electric driven
pumps ), jockey pumps, Diesel engine driven
pump icluding MCB/MCCB, Starter for all
pumps, push button switches, MFM, various
fault indicators, hooter for indication,
sufficient number of NO/NC point to
communicate with fire alarm panel. this shall
be complete as per require IS code.
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
35 Supplying, laying, testing and commissioning 15.00 330.27 Rmt
1.1 KVgrade, XLPE insulated, standard
aluminium conductor, galvanized steel flat
stip/ round wire armourd, extruded PVC
typeST2 sheathed, heavy duty cable (to
belaid on wall surface with neccessary
clamps/in existingcable trench/ cabletrays/
conduit/ pipe sleeves at road crossing or
floor as per site requirement) conferming to
IS:7098 (part 1) and IEC:60502 (part 1) of
following sizes : (1100 V GRADE POWER /
CONTROL CABLES ) 3.5 C x 50 sq.mm
Aluminum cable for main pumps.
36 Supplying, laying, testing and commissioning 20.00 151.50 Rmt
1.1 KVgrade, XLPE insulated, standard
aluminium conductor, galvanized steel flat
stip/ round wire armourd, extruded PVC
typeST2 sheathed, heavy duty cable (to
belaid on wall surface with neccessary
clamps/in existingcable trench/ cabletrays/
conduit/ pipe sleeves at road crossing or
floor as per site requirement) conferming to
IS:7098 (part 1) and IEC:60502 (part 1) of
following sizes : (1100 V GRADE POWER /
CONTROL CABLES ) Providing and erecting
XLPE (IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 KV.
to be laid on wall with necessary clamps or
in existing trench / pipe of following size of
37 Supplying, laying, testing and commissioning 30.00 317.14 Rmt
1.1 KVgrade, XLPE insulated, standard
aluminium conductor, galvanized steel flat
stip/ round wire armourd, extruded PVC
typeST2 sheathed, heavy duty cable (to
belaid on wall surface with neccessary
clamps/in existingcable trench/ cabletrays/
conduit/ pipe sleeves at road crossing or
floor as per site requirement) conferming to
IS:7098 (part 1) and IEC:60502 (part 1) of
following sizes : (1100 V GRADE POWER /
CONTROL CABLES ) Supplying & erecting
XLPE(IS:7098)(I)-88 ISI unarmoured copper
cable 1.1 KV grade to be erected as directed
of following size. 4C X16 SQ.MM.
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
38 Supply and erection required sizehot deep 50.00 90.90 Kg.
galvanized iorn strip for earthing of H.T.,
Ocb/ ACB/ Transformer LT panel board,
Motors etc., using proper clamp. 50mm x
6mm thick -GI strip.
39 SITC of 2 Zone manual fire alarm control 1.00 5252.00 Nos
panel made out of MS sheet to
accommodate the following items duly stove
enameled painted in approved colour swith
louvers for ventilation’s locking arrangement.
etc complete as reqd.
40 SITC of Hooter. 4.00 1868.50 Nos
41 Supplying, Installing, Testing & 4.00 32320.00 Nos
commissioning of Beam Detector.
42 Supplying & erecting XLPE(IS:7098) (I)-88 200.00 33.33 Rmt
ISI unarmoured Aluminium cable 1.1 KV.
grade to be erected as directed of following
size. (A) 2 core 2.5 Sq. mm
43 Supplying and fixing ON / OFF push buttons 4.00 404.00 Nos
with pipe & 2c x 2.5 sqmm cable warming on
each floor etc.
44 Providing and erecting Approved make Four 1.00 17843.77 Nos
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.
withvariable Thermal & magnetic release
suitable to work on A.C. supply 50 c/s. with
all internal connections, spreader tinned
copper & complete erected in ICS=100% of
ICU only Cat III
Description of Item
(with brief specification and reference to Quantity Rate In figures Unit Amount
book of specifications)
45 Providing and erecting Approved make 4.00 3040.10 Nos
RCCBs conforming to IS: 12640 and having
sensitivity of 30 mA and Short Circuit
withstand capacity of 10 KA and suitable for
operation on 3 phase and neutral 415V,
50Hz. having characteristic of quick action &
tripping with all advance feature & do not
incorporate any electronic component for
following Max. rating erected as directed.
(iii) 63 Amps. FP
46 Supply, Installation, testing and 4.00 454.50 Nos
commissioning of break glass manual call
pointl, Wall mounting, resettable key option
with back box.
Total Rs.
Rupees Eleven Lakh ThirtyFour Thousand Two Hundred NinetySix Only
I / We am / are willing to carry out the work at ________________________________% above / below
percent (should be written in figure and words) of the estimated rate mentioned above. Amount of my /
our tender works out as under.
Estimated amount put to tender Estimated amount put to tender
Deduct_________% Below Add_________% Above
Net Rs.__________________ Net Rs.__________________
In words __________________ In words __________________
1 The Contractor shall exhibit a board with detailed specification and details of work as directed by
the Engineer-In-Charge for which no extra payment shall be made.
2 The labour cess will be deducted as per prevailing rules i.e. 1% of the work done.
3 GST and Income tax TDS will be deducted at a source while making payments of bills.
4 In all R.C.C. Items in Rate Analysis Standard Cement Consumption has been taken as per Govt.
G.R.: PRC-10/2017 Cement Consumption/16/C Date:11/05/2017 as stated in S.O.R. therefore in
R.C.C. items where there is a change as per actual mix design the cost of difference of cement
consumption have been deducted from the rate of original item at the rate of input rate mentioned
in all the tender.
Signature of Contractor
Deputy Executive Engineer Executive Engineer
R.& B. Sub Division R.& B. Division
Ambaji Palanpur
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
GR - 1.pdf
GR - 2.pdf
GR - 3.pdf
GR - 4.pdf
GR - 5.pdf
S B D Fire_Part1.pdf
S B D Fire_Part2.pdf
S B D Fire_Part3.pdf
S B D Fire_Part4.pdf
S B D Fire_Part5.pdf
S B D Fire_Part6.pdf
S B D Fire_Part7.pdf
S B D Fire_Part8.pdf
S B D Fire_Part9.pdf
S B D Fire_Part10.pdf
S B D Fire_Part11.pdf
02-1 Special Condition - Fire Hydrant System Danta.pdf
02-2 Approved Make List Fire Hydrant System Danta.pdf
BOQ.pdf
06 Specification Index - Fire Hydrant System Danta.pdf
07 Details Specification - Fire Hydrant System Danta.pdf
08 Testing - Fire Hydrant System for Adarsh Nivasi School At Danta.pdf
SCHEDULE FOR TESTING OF MATERIALS_0001.pdf
IS Code Fire All_Part1.pdf
IS Code Fire All_Part2.pdf
IS Code Fire All_Part3.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .