Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.6 LAccepted-AOC | L1 | Accepted-AOC L1, hence accepted | |
| 2 | L2₹33.1 L+₹2.5 L (8.17%)Rejected-AOC CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | L2 | Rejected-AOC L2, hence rejected |
Tender Value
₹31.8 L
EMD Value
₹50,000
Closing Date
7 Apr 2025, 2:00 pmClosed
Executive Engineer
Minor Irrigation Division, 4th Floor,Civil Station, Kakkanad, Ernakulam
Conversion of Deemed HT scheme into HT by adding new 11 KV 500 KVA Substation, including HT pole structure, UTS, HT/LT cabling, metering and mandatory electrical, mechanical and civil works as per Electrical Inspectorate standards at Thiruvila
2025_Irrig_755472_1
EE/MIDVN/EKM/18/ET/2024-25/S Tender
Open Tender
Electrical Works
Item Rate
180 days
Thiruvilamchuzhi
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,760
Yes
₹50,000
Yes
1 Sept 2025
27 Mar 2025
8 Apr 2025
27 Mar 2025
7 Apr 2025
27 Mar 2025
Amount
Supply, Testing and commissioning of 500 KVA transformer
OD90083/2024-2025:Transportation, Supply, erection, testing and commissioning of 500 KVA Out door type Unitised substation with TECHNICAL PARTICULARS: 500 KVA out door type Unitised Sub Station consists of 500 KVA Cast Resin Transformers, Reference Standards : IS 2026/IS 11171, Type & Make of Transformer : INTRANS/UNITECH or euqivalent make Cast Resin Dry Type , Normal continuous Rating (KVA) 500, Voltage Ratio - 11 kV/433 V Rated Frequency - 50 Hz , Number of Phases – 3, Type of Cooling - AN(Air Natural), Vector Group – Dyn 11, Connections ( HV / LV) - Delta / Star, Winding Material – Copper, Type of Tap changer- Off- Circuit Tap Links, Tapings on HV side : +5% to -5% in steps of 2.5% , Class of insulation - Class F, Lamination - CRGO (M-4 Grade), Reference Ambient Temperature - 50°C, Temperature rise of windings above ambient - 90°C, Insulation level -a) Impulse withstand voltage (HV), b) Power frequency withstand voltage (HV/LV), 75 kV ( Peak), 28 kV (rms) / 3 kV (rms), Terminal Arrangement (HV/ LV) - Coupled to 11 KV HT panel / Cable Box, Fittings - Lifting lugs, winding Temperature Indicator, hooter, Rating and Diagram Plate, Earthling Terminals, , LV side cable box with 800A MCCB and HV side terminal connected to 11KV VCB panel including outdoor type 11KV,630A,26.3KA for 3 seconds Horizontal draw out type VCB fitted with manual/motor operated spring charging mechanism with 230V AC motor and motor control switch ,shunt trip coil of 24V DC, Closing coil of 24V DC, Auxiliary contact 2NO+2NC ,Mechanical ON/OFF indicator ,Mechanical operation counter, Protection CT(-5A,5P 10,15VA,11KV,110V,class .2S,25VA PT instantaneous IDMT relay with microprocessor based 3O/C+1 IEF protection relay strip heater with thermostat, Digital ammeter and digital voltmeter, Power pack of 230V AC,24V DC emergency OFF push button with HT Metering, Control Wiring with appropriate colors, Provision for receiving incoming and outgoing cable - Through bottom entry, with HT Metering (3nos CT & 1 no PT Unit), Provision for TOD Meter, All inter connections from HT switch to transformer and to LT breaker shall be given using electrolytic copper bus bar insulated wit heat shrink sleeves and tinned all the point of contacts. all internal earth connections are to be given as per standards Necessary protection shall be made for giving cable connection on the HT side as well as the LT side. Phase barriers and shrouding as per rules has to be given, Enclosure – IP54- The enclosure shall be powder coated over a suitable primer after seven tank processing. The TOD meter compartment and CT/PT unit compartment shall be fabricated to so as to enable the KSEBL authority to seal it and commissioning including warranty services, arranging the entire work till commissioning, to the satisfaction of site supervisor from/self/ or higher authorities of the Asst. Engineer in charge.
2 pole structure, AB, DO, LA, insulators , cross arms and stays
OD90065/2024-2025:Supply and erection of two pole structure consisting of 2 nos 11 mtrs long 175x85 RSJ poles and fixing the pole and neatly painted the pole with 2 coat aluminium paint over a coat of primer as required. excluding excavation of trench
OD90066/2024-2025:Supply and fixing of channel iron 100 mm X 50 mm X 6 mm (9.56 kg per meter) for placing and fixing ABS/ Lightning arrestor using suitable size bolt and nuts , painting 2 coat aluminium paint over a coat of primer, as per directions of departmental officers
OD90067/2024-2025:Supply, conveyance, fitting and commissioning of approved make 11 KV,400 Amps, out door type gang operated Air Break triple pole switch (3 Piece full set) with all necessary accessories including adequate length of GI pipe as operating lever, operating handle with insulation and locking arrangements on suitable height, with necessary clamps, nut, bolt, washer etc. as required.
13.10:Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required
13.13:Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire. 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KSA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required.
OD90068/2024-2025:Supply, conveyance, fitting and commissioning of approved make 11 KV, Drop Out Fuse Unit with all standard accessories GI / MS channel, properly fixing on cross arm including giving connections etc. as required.
13.1:Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
Earthing
OD90069/2024-2025:Supply and providing plate earthing as per IS 3043 with 1200x1200x12 mm GI/CI earth plate, 50 mm GI watering pipe fixed to the earth plate with 25 x 3mm GI clamps, GI funnel with weld mesh, filling required quantity of charcoal including construction of inspection chamber with a bed concrete of 1:4:8 PCC using 40 mm broken stone (10 cm thick), brick work in cement mortar 1:6, plastering the surface of brick masonry and the exposed surface of PCC bed with cement mortar 1:4, 12 mm thick, (the finished inside dimension shall be 450 x 450 x 450 mm) but excluding test joint, earth continuity conductor to the plate, and covering at the top. (in ordinary soil)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD90073/2024-2025:supply and providing test joint for the earthing system using 25xm6 mm GI strips including cutting and bending and bend to shape drilling necessary holes and fixed to the watering pipe etc as required
OD90072/2024-2025:Supply and providing test joint for the earthing system using 32x6 mm copper strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required.
OD90075/2024-2025:supply and providing earth lead from the test joint to the earth plate including 25 x6 mm GI strip including cutting drilling necessary holes and fixing firmly with plate test joint etc as required
OD90074/2024-2025:supply and providing earth lead from the test joint to the earth plate including 32 x6mm copper strip including cutting drilling necessary holes and fixing firmly with plate test joint etc as required
90.16.3.3:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm GI strip
90.16.3.12:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)32 x 6 mm copper strip
OD90077/2024-2025:Supply and laying 25 x 6 mm GI strip tinned at the points of contacts laid 0.60 m below ground level including excavating trench of suitable size and refilling etc. as required (in ordinary soil).
OD90076/2024-2025:Supply and laying 32 x 6 mm copper strip tinned at the points of contacts laid 0.60 m below ground level including excavating trench of suitable size and refilling etc. as required (in ordinary soil).
OD90078/2024-2025:Supply and providing 25 x 6 mm brass bolt & nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
OD90071/2024-2025:Supply and providing the following sizes of cast iron gully trap with covering at the top of the inspection chamber of earth pit as required . - 300 x 300 x 10 mm cast iron gully trap with covering
90.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
Out door HT cable
OD90079/2024-2025:Supply and laying of 3 core 300 sq.mm 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC ape, galvanized steel flat strip armored, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments, on existing GI cable trays
90.12.12.8:Supply & laying of DWC pipe in ordinary soil 1.2 m below ground level including excavation125/109 mm or nearest size
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
OD90080/2024-2025:Supplying siemens / trapdoor type nickel plated Double compression brass cable gland for PVC insulated and PVC sheathed armored aluminum/ copper conductor cable 11 KV grade, and making end termination suitable for 2/ 3/ 3½/ 4 core cable of the following sizes as required. 300 sq.mm
TOD metering
OD90113/2024-2025:Supply, conveyance, errection testing and commissioning of approved make 3 phase, 4 wire, 110 V ( L-L), -/1 A CT or -/5A CT with DLMS compliant, having RS 485 port of class 0..2 S class TOD meter in the existing meter box after submitting the test certificate from KSEB TMR Division, giving all connections etc. as required. (excluding testing fees)
LT cable 3.5 core, 400 Sq mm Aluminum,3 runs
90.12.7.37:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm
90.12.1.37:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 400 sq mm
90.12.2.37:Supply and laying of one number additional PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground in the same trench in one tier horizontal formation including widening the trench by 20 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil)3.5 core 400 sq mm
90.12.38.1:Supply and Laying of one number additional PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in ground in the same trench in one tier horizontal formation including widening the trench by 20 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil)2 core 4 sq mm
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.41.1:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp
90.12.9.6:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench110/94 mm or nearest size
90.12.7.36:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 300 sq mm
90.12.7.35:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 240 sq mm
90.12.7.27:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp
9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
OD90081/2024-2025:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required.(4 sq - 16sq mm with 12 mm wide x 1.20 mm thick clip)
OD90082/2024-2025:Supply and providing20x3mm earth clamps made out of copper strip including cutting and bending the flat exactly tot the shape of the gland drilling necessary holes for nut and bolts tinning the points of contact and giving to the main earthing system as required for earthing gland of size 120sqmm to 400sqmm
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
Replacement of damaged panel boards & switch gears
90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.3:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardSupply and providing 'U' section PVC beeding in the panel board
OD90084/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps for interconnecting the control devices/ equipments including providingsuitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring,keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.-1.50 sq mm single run with required sockets.
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD90085/2024-2025:Supply & fixing Illuminated Flush head Actuator - Red with legend "OFF" (Contact - 1NC)
OD90086/2024-2025:Supply & fixing Illuminated Flush head Actuator - Green with legend 'ON', (Contact - 1 NO)
OD90087/2024-2025:Supply and Fixing of 800/5 A, 15 VA, accuracy class 1, Resin Cast Metering CT
OD90088/2024-2025:Supply and installation of 400/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT
OD90089/2024-2025:Supply and installation of Three phase Voltmeter (V - RY, YB, BR, R, Y, B) of accuracy class 1
OD90091/2024-2025:Supply and fixing 3 phase digital Ammeter accuracy class 1 in existing panel board
OD90092/2024-2025:Supply and fitting Multifunction meter to read: V, A, F, 3 phase accuracy class 1
OD90093/2024-2025:Supply and installation of LED indicators for power/on-off/trip-different Colors
OD90094/2024-2025:Supply, fixing testing and commissioning of suitable type Standby lowest Earth fault relay L & amp; T MC12AB50X00 or Equivalent
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.14.8.11:800 A, 4 pole, manual draw out type, microprocessor based ACB with overload , instantaneous SC , delayed SC and ground fault protection 50kA
2.1.8:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.400 Amp TP&N
2.1.7:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.320 Amp TP&N
2.1.4:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N
OD109200/2024-2025:Supply and fixing following capacity switch fuse unit with ISI marked HRC fuses in sheet enclosure, making connections, etc. as required.400 amps TPN
OD109195/2024-2025:Supply and fixing following capacity switch fuse unit with ISI marked HRC fuses in sheet enclosure, making connections, etc. as required.315 amps TPN
OD90096/2024-2025:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 2.50 cm, 4 cm or 5 cm height
OD90097/2024-2025:Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red color.
OD90098/2024-2025:Disconnecting all electrical connections, dismantle the existing panel board , conveying panels to suitable place
OD90099/2024-2025:Supply and providing 6 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD90100/2024-2025:Supply and providing 2.0 mm thick Elastomeric fire retardant insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength.
OD90101/2024-2025:Supply and providing 11 KV rubber hand long glove
OD90103/2024-2025:Supply and fixing 8 stage 440 / 110 V 5A/1A , Intelligent Power Factor Controllers (IPFC)
OD203583/2024-2025:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 10 sq. mm
1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
OD90104/2024-2025:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks 20 kVAR with AC Coil
OD202570/2024-2025:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks 10/7.5 kVAR with AC Coil
OD90106/2024-2025:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks 5 kVAR with AC Coil
90.14.24.37:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
90.14.24.36:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
90.14.24.34:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
90.14.24.33:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.7.5 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
90.14.24.31:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
OD90107/2024-2025:Supplying and fixing 63 amps rating, 415 volts, Triple pole "D" curve, miniature circuit breaker in the existing panel board complete with connections, testing and commissioning etc. as required.
OD90108/2024-2025:Supplying and fixing 6 amps to 32 amps rating, 415 volts, Triple pole D curve, miniature circuit breaker in the existing panel board complete with connections, testing and commissioning etc. as required.
OD90110/2024-2025:Electrical drawing preparation charge for getting approval from Electrical Inspectorate , A3 sheet for first copy
OD90109/2024-2025:Electrical drawing preparation charge for getting approval from Electrical Inspectorate , A3 sheet - additional copy
OD90111/2024-2025:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD90112/2024-2025:Supply and providing 9 Liter capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, color washing etc. as required.
ELCON ELECTRICALS (BID ID -2189547)
Bidder Name
Kittu Electricals private limited
ELCON ELECTRICALS
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1226809.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .