Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.8 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹3.9 L+₹8,738.04 (2.27%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹4.0 L+₹14,404.04 (3.75%)Rejected-AOC 72 1 HARINATH SEN ROAD PURBA PARA BARASAT KOL 124 | BARASAT | NORTH 24 PARGANAS | WEST BENGAL | 124 | L3 | Rejected-AOC L3 |
Tender Value
Refer Docs
EMD Value
₹4,000
Closing Date
17 Mar 2025, 3:00 pmClosed
SE and Area Manager
Office of the Area Manager Kharagpur 400KV Area Office Dewanmaro 3 Hiradihi Kharagpur Paschim Medinipur
Supply Delivery Installation of Wall mounted Split type Air Conditioners having individual OUTDOOR INDOOR units in Battery Room at Kharagpur 400KV Sub Station under Kharagpur 400KV Area Office WBSETCL
2025_SETCL_800833_1
WBSETCL/KGP 400KV AO/E-TENDER(E)/08
Open Tender
Air-Conditioner
Turn-key
90 days
Kharagpur 400KV sub station WBSETCL
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹4,000
Kharagpur 400KV AO WBSETCL
30 Jul 2025
22 Jan 2025
20 Mar 2025
22 Jan 2025
17 Mar 2025
31 Jan 2025
22 Jan 2025 - 25 Jan 2025
28 Jan 2025
Supply part: “Supply, delivery, erection, testing and commissioning of wall mounted, 3 Star, BEE Rating, Non-Inverter type Split AC Machines (100% Copper for Condenser & Evaporator unit) with indoor and outdoor unit Ratio 1:1 & suitable for operation on 230V ± 10%, 50Hz, 1-∅ AC supply Input power <1800 W in the Battery Room at Kharagpur 400KV Sub-Station under Kharagpur 400KV Area Office, WBSETCL including supply of all required refrigerant, refrigeration pipes made up of HVAC grade hard drawn copper pipe with Nitrile Rubber tube insulation, elbows complete and allied material as per standard technical specification of WBSETCL. In all the Air-conditioning M/Cs refrigerant should be R-32 with capacity more than 700 CFM. • • Capacity of AC Machine : 6 x2.0 TR
Service part: Installation, testing & commissioning of Indoor & Outdoor units of the new split type air conditioner machines in the Battery Room at Kharagpur 400KV Substation of WBSETCL as directed by the EIC including fitting, fixing, brazing etc. as required for all refrigeration piping, required nos. of fire retardant canvas connection, laying of required drain pipes with associated works (including supply), from indoor to outdoor power connections of electrical cabling including supply, delivery, testing & commission with required conduit & fittings, with necessary civil masonry / carpentry works for making opening and proper finishing as required for completion of the work The job includes (Installation of AC Machine : 6 Nos x 2.0 TR): • Arrangement of AC supply distribution including supply of necessary Distribution boards and cables including MCB for each AC machine. • Arrangement of Ac machines for operation in group for 24 hour rotational running in the Battery Room room and PLCC room with Programmable Logic Controller.
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .