Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹16.1 L+₹1.2 L (8.07%)Rejected-Finance SHOP NO 13 MOHINI MARKET KISHORE BAGH MANDORE JODHPUR RAJ | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-Finance HIGHEST | |
| 3 | L3₹16.8 L+₹1.9 L (13.0%)Rejected-Finance 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L3 | Rejected-Finance HIGHEST | |
| 4 | L4₹18.5 L+₹3.6 L (23.9%)Rejected-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L4 | Rejected-Finance HIGHEST | |
| 5 | L5₹19.4 L+₹4.5 L (30.2%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L5 | Rejected-Finance HIGHEST |
Tender Value
Refer Docs
EMD Value
₹39,800
Closing Date
10 Aug 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SHRI T C SHISHODIYA, DCWE (C)
MULTAN LINE ARMY AREA JODHPUR
Repair and Maintenance of 33 KV network and other allied works including improvement of infrastructure in Army Area Jodhpur
2021_MES_449772_2
CWE (A) JODH-08 OF 2021-22
Open Tender
Civil Works
Item Rate
150 days
GE(Army) Utility
Please refer Tender documents.
4 documents required · 4 mandatory
₹500
Yes
GE(Army) Utility
₹39,800
Yes
30 Sept 2021
6 Jul 2021
11 Aug 2021
6 Jul 2021
10 Aug 2021
27 Jul 2021
90 days
Amount
Excavation in trenches manually not exceeding 1.5 m wide and not exceeding 1.5 mtr in depth for laying of cables, erection of poles, struts/stays, leveling of yard etc not exceeding 10 Sqm on plan and not exceeding 1.5 mtr in depth and getting out in soft/loose soil.
Material and labour for sand cushioning to underground cable screened un-washed river sand including watering and consolidation complete all as specified and as directed.
Supplying and laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50mm complete laid over the cable perpendicular to the cable for protection complete all as specified and as directed.
Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cm in soil.
Removing of excavated soil not exc. 50 M from starting points all as directed by EIC.
M&L for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with multistranded aluminium conductor, 33000 volts Earthed, grade cross sectional area 120 sq. mm, 3 core conforming to IS 7098 (Part-II) 2011 with upto date amendments complete all as specified and as directed.
Supply and fix GI tubing light grade in repairs incl. accessories for protection of cables on poles / under road crossing of following sizes : - (a) 100 mm dia
All as per Srl Item No 07 above but 150 mm dia
M&L for Auguring/ Driling /Boring of holes under road, pavement, hard standing by trenchless technology by manual /machine, including supply and fixing of HDPE pipe of 110 mm dia complete all as specified and directd by EIC.
Material and labour in replacement of unserviceable end jointing kit, outdoor type heat shinkable, 120 to 185 sq. mm 3 core suitable for 33KV 3 Core, XLPE electric cable complete all as specified and directed: Note :- (i) Earth work for joints shall be measured and paid separately against respective item. (ii) The cost of disconnection of faulty cable and connection of same after replacing the end termination is deemed to be included in quoted rate.
All as per Srl Item No 07 above but Straight through cable joint.
Cleaning of area of 33 KV yards including cutting of shrubs & bushes including surface dressing n.exc 15 cm deep in any type of soil and site clearance in soft and loose soil all as directed at site whenever required at site.
Dismantling of U/S HT insulators (Pin /shackle/Disc & Loop) type from existing OH lines.
Fixing only of any type any size of dismantled insulators (Retrieved from item No 12 ) including replacement of any type of hardware such as nuts, bolts, washers etc all as directed at site.
Supply & Fix Pin type, porcelain , vitreous, white , green & brown insulator including one galvanised iron long steel spindle, two galvanised iron washer and one galvanised iron nut, working pressure 33000 Volts and of size 290 mm dia x 290 mm height, ISI marked, for 10 KN max failing load complete all as specified and as directed.
Supply & Fix loop type porcelain insulator , vitreous white brown or green , overall dimension 90x140 mm and clearance of hole 25.5 mm complete all as specified and as directed.
Supply and fixing of disc type porcelain vitreous, white brown or green 145mm height and 255mm dia ball and socket type three disk assembly for tension with three bolted tension clamp for conductor working pressure 33000 volt grade, conform to IS-13134, for 7.5 KN max failing load complete all as specifed and as directed.
Material and labour in replacement for steel structure, cross arms, bracing supports, clamps, back plates of any type, section incl. nuts, bolts, washers, welding, fabrication/bending cold or hot in any size and shape required at site complete applying of two coats of aluminum paints over a coat of red oxide primer incl dismantling complete all as directed by Engr-in-charge.
Restringing and straightening of ACSR conductor of any size mounted on insulators and binding with aluminium taps /binding wire /conductor jumper etc on 33 KV lines all as directed by Engr-in-charge.
Material and labour for stay assembly complete with 300 x 300 x 6 mm thick plate and 20 mm dia stay rod all as shown in elect plate NO-1 of SSR-part -1 including stay wire of 7/4 mm dia of suitable length all as directed by Engr in charge. Note : - (i) Rates includes earth work, foundation PCC (1:3:6), dismantling of old stay assy, demolition and removal of concrete from site and making good. (ii) Loop insulators shall be measured and paid seperatly.
Under ground Cable Testing / fault detection by authorised agency with Computerised Fault Detection Van complete to find the fault location for 33/11 KV rated UG cables as directed by Engineer in Charge at site. Note :- Any excavation and earth work and cable joint work involved shall be measured and paid separately against respective item.
Material and labour for Cement concrete (1:3:6) type C -2 using 40 mm graded stone aggregate for foundation of pole /struts/stay assembly etc complete all as directed by EIC.
Material and labour Cement concrete (1:2:4) type B -1 using 20 mm graded stone aggregate for pedestal of poles/copping including necessary frame work ,fair finishing to exposed surfaces using extra cement complete form, all as directed by EIC.
Material and labour in replacement of Prestressed concrete pole, 11 metres long. 152mm x 152mm at top and 152mm x 260mm at bottom, class 9 complete all as directed by Engr-in-Charge.
Material and labour in replacement of old unserviceable LA station class heavy duty, gap less confirming to IS 3070 having having system voltage 33 KV highest system voltage 36 KV, system fault level 25 KA, LA rated voltage 42 KV, maximum continuous operationg voltage 36 KV rms, nominal discharge current 10 KA, rated frequency 50Hz complete with all fittings suitable for 33 KV, 3 phase, earth distribution system complete all as specified.
Repairing of damaged/unserviceable gang operate devices 33 KV male & female contacts, flexible jumpers, MS jumper carrier and back connector plate incl cleaning and greasing of complete contacts of GOD unit, DO fuse unit and reluging of aluminium conductors connected to top & bottom contacts of GOD and DO units incl. welding and threading of operating rod mechanism complete making serviceable all as directed by Engr-in-Charge. Note:- (i) Necessary parts like knife, male/female contacts and aluminium conductor for jumpering, GI pipe and handle will be Measured and paid separately against respective item. (ii) Rates for welding machine, threading arrangements, grease and binding wire deemed to be included in quoted rates.
Supply and fix male contact / moving contact pipe assembly complete suitable for 33 KV GOD horizontal type.
Supply and fix female contact / fix contact assembly complete suitable for 33 KV GOD horizontal type.
Supply and fix HT 33 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 polymer/porcelain insulators of rating upto 200 Amps complete all as specified and as directed.
Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 m in depth upto 3.0 m for erection of poles, struts/stays, leveling of yard etc not exceeding 10 M² on plan and getting out in soft/loose soil.
Sachiyay maa Electricals
SANJOLI CONSTRUCTION COMPANY
Shri Electrical Enterprises
Anil Builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .